AVR OPERATOR TRAINING Oleh: PT. LIMAWIRA WISESA JAKARTA 1
1. Keterangan sistem Agenda Training AVR 2. Instalasi unit 3. Pengoprasian unit 4. Metering unit 5. Trouble shooting 6. Maintenace 2
Bag: 1 agenda Keterangan Sistem 3
Fungsi Fungsi Automatic Voltage Regulator (AVR) Untuk melindungi perangkat / peralatan listrik Anda dari semua fluktuasi tegangan listrik dan mengaturnya agar tetap pada tegangan nominal yang disarankan. 4
Fitur Servo Motor Controlled Technology Short circuit protection Manual Bypass Switch Electro-mechanic (breaker module) highlow voltage protection ( optional ) Output Isolation Transformer ( optional ) Digital Display (Optional) 5
Wiring Diagram AVR AVR With Breaker (Optional) Training Operator UPS SHDMP 6 3/23/2012 08/11/09
Wiring Diagram AVR AVR Without Breaker Training Operator UPS SHDMP 7 3/23/2012 08/11/09
Spesifikasi Input: Tegangan nominal Input 1 ph: 220 VAC Range teg. nom. input 1 ph: 160~245 VAC Range teg. wide input 1 ph: 135~245 VAC Tegangan nominal Input 3 ph: 380-400 VAC Range teg. nom. input 3 ph: 277~424 VAC Range teg. wide input 3 ph: 233~424 VAC Frekwensi input: 50/60 Hz Output: Regulasi teg. output : 1% Efisiensi : 96~97% 8
Kelebihan : Spesifikasi Range tegangan Input lebar Toleransi tegangan Output rendah Regulasi menggunakan servo motor, lebih awet Respon cepat untuk Fluktuasi Efisiensi tinggi pada tiap model Kemampuan untuk bekerja dengan beban non-linear 9
1 Phase AVR 10
3 Phase AVR 11
Bag: 2 agenda Instalasi Unit 12
Instalasi AVR 13
Bag: 3 agenda Pengoprasian AVR 14
PROSEDUR START UP Pastikan Pemasangan installasi AVR sudah benar. Naikan Breaker Input AVR yang ada di Panel I/O AVR (Gb. 4) dan MCB Variac Fuse yang ada AVR (Gb. 2). Pastikan juga posisi COS yang ada AVR (Gb. 2) pada posisi 2 (regulator). Led indicator merah di AVR nyala dan meter display AVR bergerak. Naikan Breaker Output AVR yang ada di Panel I/O AVR (Gb. 4). Perlu di ingat : Pada posisi sekarang BREAKER BYPASS AVR HARUS TETAP OFF / tersegel (Seperti pada Gb.4). Beban AVR siap di operasikan. Gb.1 (AVR) Gb.2 (Display AVR) Gb.3 (Panel I/O AVR) Gb.4 (Dalam Panel I/O AVR) 15
Pastikan beban AVR sudah mati. PROSEDUR SHUT DOWN Turunkan berturut- turut Breaker Output dan Input AVR (Gb. 4) yang ada di panel I/O AVR. AVR mati total. Gb.1 (AVR) Gb.2 (Display AVR) Gb.3 (Panel I/O AVR) Gb.4 (Dalam Panel I/O AVR) 16
PROSEDUR BYPASS Pastikan beban AVR sudah mati. Turunkan berturut- turut Breaker Output dan Input AVR (Gb.4) yang ada di panel I/O AVR. Buka segel Breaker Bypass AVR (Gb. 4) yang ada di panel I/O AVR lalu On-kan. AVR sekarang sudah posisi Bypass. Untuk Panel I/O AVR (Gb. 4) perlu di ingat : JIKA BREAKER BYPASS ON MAKA BREAKER INPUT & OUTPUT AVR HARUS OFF begitu juga sebaliknya JIKA BREAKER INPUT & OUTPUT AVR ON MAKA BREAKER BYPASS HARUS OFF Beban AVR siap di operasikan lagi pada posisi Bypass. Gb.1 (AVR) Gb.2 (Display AVR) Gb.3 (Panel I/O AVR) Gb.4 (Dalam Panel I/O AVR) 17
Bag: 4 agenda Metering 18
Front AVR LED Indicator METERING (Volt) FUSE LED & METERING SELECTOR SWITCH 0 OFF Position 1 Line Position 2 Regulator Position MCB / FUSE Input AVR 19
Front & Inside Panel AVR LED Indicator MCB/MCCB Input MCB/MCCB Bypass MCB/MCCB Output Training Operator UPS SHDMP 20 3/23/2012 08/11/09
Bag: 5 agenda Trouble Shooting AVR 21
? AVR bersuara dengung Tegangan Hilang 1 Phase Cek Tegangan Input AVR (PLN) Nyalakan Genset? Tegangan Input AVR (PLN) ada, tapi Output AVR / Beban mati Cek MCB/FUSE AVR Cek MCB Output pada Panel AVR Lakukan Prosedur BYPASS Hubungi Kami!? Tegangan Output AVR Unbalance, Tinggi/Kurang dari tegangan nominal Lakukan Prosedur BYPASS Hubungi Kami!? AVR normal, tetapi LED Indicator / METERING mati LED Indicator mati, FUSE LED & METERING putus Hubungi Kami! 22
Bag: 6 agenda Maintenance 23
Maintenance-1 AVR dapat diprediksikan bisa tahan lama dan bebas masalah dengan hanya maintenance yang simple Masalah kebersihan dan temperature ruangan akan berpengaruh terhadap ketahanan unit. 24
Maintenance-2 Jaga suhu operasional ruangan AVR agar tetap stabil, yang ideal adalah 15 C 25 C Usahakan ruangan selalu tertutup ini untuk menjaga kesetabilan suhu dan lingkungan agar tetap sejuk dan bersih 25
Maintenance-3 Berikan jarak bebas minimal 30cm antara belakang AVR dengan dinding, ini untuk memelihara kebebasan keluaran aliran udara Begitupun dinding sebelah kiri dan dinding sebelah kanan, ini adalah aliran udara masuk untuk pendinginan komponen di dalam AVR 26
Jika menemui kendala silahkan menghubungi kami dengan menyiapkan data data sebagai berikut : 1. MODEL AVR dan Serial No 2. Penyebab kerusakan? 3. Sampaikan Kendala yang anda hadapi kepada kami. Training Operator UPS SHDMP 27 3/23/2012 08/11/09