TELEINFORMASI DATA UNTUK PEMELIHARAAN INSTALASI SISTEM TENAGA LISTRIK

dokumen-dokumen yang mirip
TELEINFORMASI DATA UNTUK OPERASI JARINGAN TENAGA LISTRIK

Teleinformasi Data. Fungsi Operasi & Fungsi Pemeliharaan Sistem Otomasi Gardu Induk

Teleinformasi Data. Sistem Otomasi Gardu Induk. Standardisasi Bidang SCADA

LAMPIRAN. Gambar. Konfigurasi PLC module

DAFTAR ISI ABSTRAK... KATA PENGANTAR... DAFTAR ISI... DAFTAR GAMBAR... DAFTAR TABEL...

PERENCANAAN DAN PEMBANGUNAN SISTEM SCADA

BAB IV PEMBAHASAN. Dari hasil analisa gangguan, dapat ditentukan sistem proteksi yang akan

MENGOPERASIKAN SCADA SISTEM PENGOPERASIAN UNIT GENERATOR PEMBANGKIT. Menjelaskan operasional SCADA. Teknik Pembangkit Listrik 1 st Class Semester 2

1. IED berkomunikasi dengan Gateway menggunakan protokol standard

BAB III TINJAUAN UMUM SISTEM SCADA DALAM KOMUNIKASI RADIO

BAB III DASAR TEORI. pembangkit-pembangkit tenaga listrik, jaringan transmisi dan jaringan distribusi

BAB III PENGAMAN TRANSFORMATOR TENAGA

BAB II TINJAUAN PUSTAKA

Jl.Prof. Sudharto, Tembalang, Semarang, Indonesia

Kata kunci : SCADA, Dispathcer

PEDOMAN OPERASI GARDU INDUK

ANALISIS GANGGUAN HUBUNG SINGKAT TRAFO TENAGA 60 MVA SHORT CIRCUIT ANALYSIS OF POWER TRANSFORMER 60 MVA

PERALATAN SCADA SISTEM TENAGA LISTRIK

Jl. Prof. Sudharto, Tembalang, Semarang, Indonesia Abstrak

OCR/FGR untuk mendeteksi gangguan fasa-fasa dan fasa-tanah.

BAB III LANDASAN TEORI. dan mengambil tindakan atas informasi tersebut secara remote atau jarak jauh

JARINGAN GARDU INDUK DISTRIBUSI

SISTEM BCU (BAY CONTROL UNIT

BAB II LANDASAN TEORI

SALURAN UDARA TEGANGAN MENENGAH (SUTM) DAN GARDU DISTRIBUSI Oleh : Rusiyanto, SPd. MPd.

PENGAMAN ARUS LEBIH BERBASIS SCADA PADA JARINGAN DISTRIBUSI PENYULANG TENGGIRI DI AREA PENGATUR DISTRIBUSI (APD) PT. PLN (PERSERO) PALEMBANG

Analisa Perancangan Gardu Induk Sistem Outdoor 150 kv di Tallasa, Kabupaten Takalar, Sulawesi Selatan

GARDU INDUK TRANSFORMATOR

III PENGUMPULAN DAN PENGOLAHAN DATA

BAB III SISTEM PROTEKSI DENGAN RELAI JARAK. terutama untuk masyarakat yang tinggal di kota-kota besar. Kebutuhan tenaga

SISTEM TENAGA LISTRIK

BAB III SISTEM PROTEKSI DAN SISTEM KONTROL PEMBANGKIT

BAB II LANDASAN TEORI

SIMULASI PROTEKSI DAERAH TERBATAS DENGAN MENGGUNAKAN RELAI OMRON MY4N-J12V DC SEBAGAI PENGAMAN TEGANGAN EKSTRA TINGGI DI GARDU INDUK

PETUNJUK SETTING RECLOSER JOONGWON, FTU R200 SERIES. Auto Recloser Control With FTU-R200 Feeder Terminal Unit For Distribution Automation System

BAB III SISTEM PROTEKSI TEGANGAN TINGGI

ANALISIS PENYEBAB KEGAGALAN KERJA SISTEM PROTEKSI PADA GARDU AB

BAB IV ANALISA DATA. Berdasarkan data mengenai kapasitas daya listrik dari PLN dan daya

DAFTAR ISI. DAFTAR ISI... i. DAFTAR GAMBAR... iv. DAFTAR TABEL... v. DAFTAR LAMPIRAN... vi

BAB IV DATA DAN PEMBAHASAN. panasbumi Unit 4 PT Pertamina Geothermal Energi area Kamojang yang. Berikut dibawah ini data yang telah dikumpulkan :

ABSTRAK Kata Kunci :

LAPORAN KERJA PRAKTIK REMOTE TERMINAL UNIT DI PT. PLN (Persero) UPB SULSELRABAR Fasilitas Operasi Unit SCADA Periode 26 Mei 30 Juni, 2016

DAFTAR ISI STANDAR KOMPETENSI TENAGA TEKNIK BIDANG TRANSMISI SUB BIDANG INSPEKSI. : Komisioning Bay Reaktor... I.19-58

Makalah Seminar Kerja Praktek APLIKASI SISTEM PENGAMAN ELEKTRIS CADANGAN GAS TURBIN GENERATOR PADA PLTGU TAMBAK LOROK BLOK II

2. PERSYARATAN PESERTA

SUB BIDANG INSPEKSI/KOMISIONING

L/O/G/O RINCIAN PERALATAN GARDU INDUK

BAB IV RELAY PROTEKSI GENERATOR BLOK 2 UNIT GT 2.1 PT. PEMBANGKITAN JAWA-BALI (PJB) MUARA KARANG

BAB I PENDAHULUAN 1.1 Latar Belakang

D. Relay Arus Lebih Berarah E. Koordinasi Proteksi Distribusi Tenaga Listrik BAB V PENUTUP A. KESIMPULAN B. SARAN...

KEMENTRIAN PENDIDIKAN DAN KEBUDAYAAN UNIVERSITAS BRAWIJAYA FAKULTAS TEKNIK JURUSAN TEKNIK ELEKTRO

BAB II LANDASAN TEORI

2.2.6 Daerah Proteksi (Protective Zone) Bagian-bagian Sistem Pengaman Rele a. Jenis-jenis Rele b.

BAB III LANDASAN TEORI

BAB II SISTEM PROTEKSI TENAGA LISTRIK

LAPORAN MINGGUAN OJT D1 MINGGU XIV. GARDU INDUK 150 kv DI PLTU ASAM ASAM. Oleh : MUHAMMAD ZAKIY RAMADHAN Bidang Operator Gardu Induk

DAFTAR ISI LEMBAR PENGESAHAN PEMBIMBING LEMBAR PERNYATAAN KEASLIAN LEMBAR PENGESAHAN PENGUJI HALAMAN PERSEMBAHAN HALAMAN MOTTO KATA PENGANTAR

PENGGUNAAN RELAY DIFFERENSIAL. Relay differensial merupakan suatu relay yang prinsip kerjanya berdasarkan

BAB IV HASIL PERANCANGAN DIAGRAM SATU GARIS SISTEM DISTRIBUSI TENAGA LISTRIK

Berikut merupakan gambaran umum arsitektur SCADA. Klik pada gambar untuk ukuran penuh.

BAB IV ANALISA GANGGUAN SWITCH GEAR 10.5 KV

2 di Indonesia, terdapat beberapa subsitem yang harus dilalui. Mulai dari sub-sistem pembangkit, jaringan listrik, pengatur beban, sampai pada sub-sis

DAFTAR ISI LEMBAR PERNYATAAN KEASLIAN HALAMAN PERSEMBAHAN HALAMAN MOTTO KATA PENGANTAR ABSTRAK DAFTAR GAMBAR DAFTAR TABEL BAB I PENDAHULUAN 1

Kata Kunci : SCADA, Remote Terminal Unit, Master Station. Mahasiswa Jurusan Teknik Elektro UNDIP Semarang 2

I S T E M O T O M A S I G A R D U I N D U K D : P D M / S G I

BAB II LANDASAN TEORI

LANDASAN TEORI Sistem Tenaga Listrik Tegangan Menengah. adalah jaringan distribusi primer yang dipasok dari Gardu Induk

BAB II TINJAUAN PUSTAKA

BAB I PENDAHULUAN. PT PLN (Persero) merupakan Perusahaan Listrik di Indonesia dan satu- satunya

Rifgy Said Bamatraf Dosen Pembimbing Dr. Ir. Margo Pujiantara, MT Dr. Dedet Chandra Riawan, ST., M.Eng.

ANALISA TROUBLE DIFFERENTIAL RELAY TERHADAP TRIP CB ( CIRCUIT BREAKER ) 150 KV TRANSFORMATOR 30 MVA PLTGU PANARAN

ATURAN JARINGAN SISTEM TENAGA LISTRIK KALIMANTAN

BAB I PENDAHULUAN. yang menjadi salah satu penentu kehandalan sebuah sistem. Relay merupakan

DAFTAR ISI. DAFTAR GAMBAR...x. DAFTAR TABEL... xii BAB I PENDAHULUAN Latar Belakang Perumusan Masalah Tujuan Penelitian...

ANALISA TEMPERATUR MINYAK TERHADAP KINERJA TRANSFORMATOR DI UNIT 6 PLTG PAYA PASIR LAPORAN TUGAS AKHIR

BAB II LANDASAN TEORI 2.1 Sistem Distribusi Tenaga Listrik

BAB V PENUTUP 5.1 Simpulan Saran DAFTAR PUSTAKA LAMPIRAN LAMPIRAN

STUDI KOORDINASI RELE PENGAMAN PADA SISTEM BUSBAR DI GARDU INDUK KAPAL

BAB II KAJIAN PUSTAKA

Voltage sag atau yang sering juga disebut. threshold-nya. Sedangkan berdasarkan IEEE Standard Voltage Sag

DAFTAR ISI PUSPA LITA DESTIANI,2014

BAB II DASAR TEORI. 2 dengan kapasitas maksimum 425MW, unit 3 dan 4 dengan kapasitas maksimum

E M O T E S T A T I O N S C A D A D : P D M / S G I

BAB 2 GANGGUAN HUBUNG SINGKAT DAN PROTEKSI SISTEM TENAGA LISTRIK

Tugas Referensi. Pertemuan Pokok Bahasan dan TIU 1 Konsep Otomatisasi Sistem Tenaga. Teknik Pembelajaran. Media Pembelajaran

Analisa Koordinasi Over Current Relay Dan Ground Fault Relay Di Sistem Proteksi Feeder Gardu Induk 20 kv Jababeka

BAB II LANDASAN TEORI

STUDI PERENCANAAN PENGGUNAAN PROTEKSI POWER BUS DI PT. LINDE INDONESIA GRESIK

TRANSFORMATOR ARUS DAN PEMELIHARAAN TRANSFORMATOR ARUS PADA PT. PLN (PERSERO) P3B REGION JAWA TENGAH & DIY UPT SEMARANG GIS 150kV SIMPANG LIMA

POWER HOUSE DAN SWITCHYARD PADA BANGUNAN PLTA

BAB III SPESIFIKASI TRANSFORMATOR DAN SWITCH GEAR

STUDI PERENCANAAN KOORDINASI RELE PROTEKSI PADA SALURAN UDARA TEGANGAN TINGGI GARDU INDUK GAMBIR LAMA - PULOMAS SKRIPSI

MAKALAH SEMINAR KERJA PRAKTEK

Makalah Seminar Kerja Praktek PRINSIP KERJA DASAR RELAI JARAK PENYALURAN DAN PUSAT PENGATUR BEBAN JAWA BALI REGION JAWA TENGAH DAN DIY

TUGAS AKHIR. Diajukan guna melengkapi sebagian syarat Dalam mencapai gelar Sarjana Strata Satu (S1) Disusun Oleh :

TI-3222: Otomasi Sistem Produksi

BAB III PEMBAHASAN RELAY DEFERENSIAL DAN RELEY DEFERENSIAL GRL 150

Makalah Seminar Kerja Praktik

BAB II LANDASAN TEORI

Komponen Sistem Proteksi 1. Peralatan Utama Sistem Proteksi Sistem proteksi pada sistem tenaga didukung oleh beberapa peralatan utama.

Transkripsi:

STANDAR PT PLN (PERSERO) SPLN S5.002: 2008 Lampiran Surat Keputusan Direksi PT PLN (PERSERO) No: 169.K/DIR/2009 TELEINFORMASI DATA UNTUK PEMELIHARAAN INSTALASI SISTEM TENAGA LISTRIK PT PLN (PERSERO) JALAN TRUNOJOYO BLOK M-I/135 KEBAYORAN BARU JAKARTA SELATAN 12160

TELEINFORMASI DATA UNTUK PEMELIHARAAN INSTALASI SISTEM TENAGA LISTRIK Disusun oleh: Kelompok Bidang SCADA dengan Surat Keputusan Direksi PT PLN (PERSERO) No.094.K/DIR/2006 Kelompok Kerja Teleinformasi Data Untuk Pemeliharaan Instalasi Sistem Tenaga Listrik dengan Surat Keputusan General Manager PT PLN (Persero) Penelitian dan Pengembangan Ketenagalistrikan No. 006.K/LITBANG/2007 Diterbitkan oleh: PT PLN (PERSERO) Jalan Trunojoyo Blok M-I /135, Kebayoran Baru Jakarta Selatan

Susunan Kelompok Bidang SCADA Standardisasi Surat Keputusan Direksi PT PLN (PERSERO) No: 094.K/DIR/2006 1. Ir. Nur Pamudji, M.Eng, MPM : Sebagai Ketua merangkap Anggota 2. Ir. Harry Hartoyo, MM, MPM : Sebagai Wakil Ketua merangkap Anggota 3. Ir. Hernadi Buhron : Sebagai Sekretaris merangkap Anggota 4. Novrizal Erdiansyah, ST : Sebagai Wakil Sekretaris merangkap Anggota 5. Ir. Solida : Sebagai Anggota 6. Ir. Sudibyo : Sebagai Anggota 7. Agus H Maulana, ST : Sebagai Anggota 8. Ir. Joko Pramono : Sebagai Anggota 9. Ir. A. Sugeng Sugarjito : Sebagai Anggota 10. Ir. Yarid Pabisa : Sebagai Anggota 11. Ir. Ruly Chaerul : Sebagai Anggota 12. Ir. Herry Santoso : Sebagai Anggota 13. Ir. Yanuar I. Prakoso : Sebagai Anggota 14. Ir. Hesti Sayoga : Sebagai Anggota 15. Ir. Deany EA Rumengan : Sebagai Anggota Susunan Kelompok Kerja Teleinformasi Data Untuk Pemeliharaan Instalasi Sistem Tenaga Listrik Surat Keputusan General Manager PT PLN (Persero) Litbang Ketenagalistrikan No: 004.K/LITBANG/2007 1. Ir. Solida : Sebagai Ketua merangkap Anggota 2. Novrizal Erdiansyah, ST : Sebagai Sekretaris merangkap Anggota 3. Ir. A. Sugeng Sugarjito : Sebagai Anggota 4. Ir. Ruly Chaerul : Sebagai Anggota 5. Tri Hardimasyar, ST : Sebagai Anggota 6. Ir. Yarid Pabisa : Sebagai Anggota 7. Ir. Joko Pramono : Sebagai Anggota 8. Ir. Denden Ruhdani : Sebagai Anggota

DAFTAR ISI Daftar Isi... i Daftar Tabel... iii Daftar Gambar... iv Daftar Gambar... iv Daftar Lampiran... v Prakata... vii 1. Ruang Lingkup... 1 2. Tujuan... 1 3. Acuan Normatif... 1 4. Istilah dan Definisi... 1 4.1 Alarm... 1 4.2 Control center... 2 4.3 Distribution control center (DCC)... 2 4.4 Feeder colouring... 2 4.5 Gardu hubung... 2 4.6 Gardu induk... 2 4.7 Gardu tengah... 2 4.8 Inter distribution control center (IDCC)... 2 4.9 Inter regional control center (IRCC)... 2 4.10 Keypoint... 2 4.11 Maintenance center... 2 4.12 National control center (NCC)... 3 4.13 Operator... 3 4.14 Regional control center (RCC)... 3 4.15 Regu pemeliharaan... 3 4.16 Supervisory control and data acquisition (SCADA)... 3 4.17 Telecontrol... 3 4.18 Telesignal... 3 4.19 Telemetering... 3 5. Umum... 3 5.1 Fasilitas SCADA... 3 i

5.2 Teleinformasi data... 4 5.3 Struktur informasi... 4 5.4 Simbol dan warna... 4 6. Perbatasan Kebutuhan Teleinformasi Data... 4 6.1 Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC... 5 6.2 Perbatasan kebutuhan teleinformasi data antara RCC dan DCC... 6 Lampiran A Daftar Teleinformasi (Transmisi)... 7 Lampiran B Bidang Transmisi (Teleinformasi pada Berbagai Konfigurasi Gardu Induk) 17 Lampiran C Daftar Teleinformasi (Distribusi)... 133 Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi)... 141 Lampiran E Struktur Informasi... 174 Lampiran F Simbol dan Warna... 182 ii

DAFTAR TABEL Tabel 1. Struktur informasi... 175 Tabel 2. Level tegangan... 177 Tabel 3. Nama bay atau feeder... 178 Tabel 4. Kode tegangan dari primer dan sekunder trafo... 178 Tabel 5. Kode nama peralatan/alarm/elemen... 179 Tabel 6. Warna tampilan... 185 iii

DAFTAR GAMBAR Gambar 1. Batas wewenang antara IRCC dengan RCC (Tipe-a)... 5 Gambar 2. Batas wewenang antara IRCC dengan RCC (Tipe-b)... 5 Gambar 3. Batas wewenang antara RCC dengan DCC... 6 Gambar 4. Struktur informasi khusus (bay diameter)... 180 Gambar 5. Struktur informasi khusus (gardu induk 1½ breaker)... 181 Gambar 6. Simbol gambar... 183 Gambar 7. Tampilan status... 184 iv

DAFTAR LAMPIRAN Lampiran A Daftar Teleinformasi (Transmisi)... 7 A-1: Telesignal... 8 A-2: Telemeasurement... 14 A-3: Tap Changer Position... 15 A-4: Remote Control Digital... 16 Lampiran B Bidang Transmisi (Teleinformasi pada Berbagai Konfigurasi Gardu Induk)17 TA-01: Konfigurasi Umum Pada 1½ Breaker... 18 TA-02: Konfigurasi Umum Pada Double Busbar... 28 TA-03: Konfigurasi Umum Pada Single Busbar... 39 TB-01: Generator Combined Cycle Pada Konfigurasi 1½ Breaker... 50 TB-02: 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi 1½ Breaker... 52 TB-03: 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Double Busbar... 54 TB-04: 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Single Busbar... 56 TB-05: 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1½ Breaker... 58 TB-06: 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double Busbar... 60 TB-07: 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single Busbar... 62 TB-08: 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1½ Breaker... 64 TB-09: 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double Busbar... 66 TB-10: 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single Busbar... 68 TB-11: Interbus Transformer (Secondary Side Connected to 1½ Breaker)... 70 TB-12: Interbus Transformer73 (Secondary Side Connected to Double Busbar)... 73 TB-13: Interbus Transformer (Secondary Side Connected to Single Busbar)... 76 TB-14: Interbus Transformer (Secondary Side Connected to 1½ Breaker Dilengkapi Shunt Reaktor Pada Kumparan Tersier)... 79 TB-15: Interbus Transformer (Secondary Side Connected to Double Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier)... 82 TB-16: Interbus Transformer (Secondary Side Connected to Single Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier)... 85 TB-17: Bay Trafo Tenaga Pada Konfigurasi 1½ Breaker... 88 TB-18: Bay Trafo Tenaga Pada Konfigurasi Double Busbar... 91 TB-19: Bay Trafo Tenaga Pada Konfigurasi Single Busbar... 94 TB-20: Bay Reaktor Pada Konfigurasi 1 ½ Breaker... 97 TB-21: Bay Reaktor Pada Konfigurasi Double Busbar... 99 TB-22: Bay Reaktor Pada Konfigurasi Single Busbar... 101 TB-23: Bay Capasitor Pada Konfigurasi Double Busbar... 103 TB-24: Bay Capasitor Pada Konfigurasi Single Busbar... 105 TB-25: Bay Penghantar Pada Konfigurasi 1 ½ Breaker... 107 TB-26: Bay Penghantar Pada Konfigurasi Double Busbar... 110 TB-27: Bay Penghantar Pada Konfigurasi Single Busbar... 113 TB-28: Bay Penghantar Paralel Dengan Reaktor Pada Konfigurasi Double Busbar... 116 TB-29: Bay Penghantar Paralel Dengan 1 Reaktor Pada Konfigurasi 1½ Breaker... 120 TB-30: Bay Penghantar Paralel Dengan 2 Reaktor Seri Pada Konfigurasi 1½ Breaker.. 123 TB-31: Bay Kopel Pada Konfigurasi Double Busbar... 126 v

TB-32: Bus Section... 128 TB-33: Bay Diameter Pada Konfigurasi 1½ Breaker... 130 TB-34: Bus Bar... 132 Lampiran C Daftar Teleinformasi (Distribusi)... 133 C-1: Telesignal... 134 C-2: Telemeasurement... 138 C-3: Tap Changer Position... 139 C-4: Remote Control Digital... 140 Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi)... 141 DA-01: Konfigurasi Umum Pada Double Busbar... 142 DA-02: Konfigurasi Umum Pada Single Busbar... 145 DB-01: Trafo 150/20 kv dan 70/20 kv Tipe 1... 148 DB-02: Trafo 150/20 kv dan 70/20 kv Tipe 2... 150 DB-03: Trafo 150/20 kv dan 70/20 kv Tipe 3... 152 DB-04: Generator Pada Konfigurasi Double Busbar... 154 DB-05: Generator Pada Konfigurasi Single Busbar... 156 DB-06: Feeder 20 kv Tipe 1... 158 DB-07: Feeder 20 kv Tipe 2... 160 DB-08: Feeder 20 kv Tipe 3... 162 DB-09: Bus Section 20 kv Tipe 1... 164 DB-10: Bus section 20 kv Tipe 2... 165 DB-11: Kopel... 166 DB-12: Capacitor Bay... 167 DB-13: SUTM radial dengan keypoint dan PBO... 168 DB-14: SUTM radial dengan keypoint tanpa PBO... 170 DB-15: SUTM loop dengan beberapa keypoint... 171 DB-16: Spindle 20 kv... 172 Lampiran E Struktur Informasi... 174 A. Nomor ID... 175 B. Time stamp... 177 C. Nama GI/GH/GT... 177 D. Level Tegangan... 177 E. Nama Bay / Feeder... 178 F. Kode Nama Peralatan atau Nama Alarm atau Nama Elemen... 179 G. Status Peralatan atau Status Alarm... 179 H. Nama user yang melakukan aksi... 179 I. Prioritas Alarm... 180 Struktur Informasi Khusus... 180 Lampiran F Simbol dan Warna... 182 vi

PRAKATA Standar SCADA ini merupakan pengganti dari Pola SCADA SPLN No. 109 Tahun 1996, dalam rangka mengikuti perkembangan teknologi SCADA. Standar ini menjelaskan mengenai master station, komunikasi dan remote station yang terdiri dari enam bagian, yaitu: 1. S3.001:2008 Peralatan SCADA sistem tenaga listrik 2. S5.001:2008 Teleinformasi data untuk operasi jaringan tenaga listrik 3. S5.002:2008 Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik 4. S4.001:2008 Pengujian sistem SCADA 5. S6.001:2008 Perencanaan dan pembangunan sistem SCADA 6. S7.001:2008 Operasi dan pemeliharaan sistem SCADA Keenam standar di atas adalah yang telah diselesaikan dalam tahun 2008 dan direncanakan akan ditambah dengan beberapa standar lainnya mengenai SCADA. Standar ini mencakup definisi, perangkat keras, perangkat lunak, kebutuhan teleinformasi data, pengujian, kinerja, kajian kelayakan dalam pembangunan, operasi dan pemeliharaan yang memiliki hubungan dengan sistem SCADA. Standar ini dapat menjadi acuan dalam setiap perencanaan, pembangunan, operasi dan pemeliharaan sistem SCADA di PT PLN (PERSERO) secara nasional. vii

SPLN S5.001: 2008 Teleinformasi Data Untuk Pemeliharaan Instalasi Sistem Tenaga Listrik 1. Ruang Lingkup Teleinformasi data terdiri dari telecontrol, telesignal dan telemetering. Sesuai dengan penggunaannya, teleinformasi data dibedakan untuk kepentingan operasi dan kebutuhan pemeliharaan. Standar ini dimaksudkan untuk menetapkan standar teleinformasi data yang diaplikasikan untuk kebutuhan pemeliharaan sistem tenaga listrik dan mencakup sistem transmisi dan sistem distribusi. Standar ini, berlaku untuk sistem SCADA: a. National Control Center, disingkat NCC; b. Inter Regional Control Center, disingkat IRCC; c. Regional Control Center, disingkat RCC; d. Inter Distribution Control Center, disingkat IDCC; e. Distribution Control Center, disingkat DCC. 2. Tujuan Standar ini ditujukan untuk memberikan pedoman yang terarah dan seragam dalam penerapan teleinformasi data bagi kebutuhan pemeliharaan sistem transmisi dan sistem distribusi tenaga listrik yang mengutamakan mutu, keandalan dan ekonomi. Standar ini merupakan acuan dalam pembangunan sistem SCADA baru dan pengembangan sistem SCADA yang telah ada. 3. Acuan Normatif Dokumen normatif berikut berisi persyaratan-persyaratan yang menjadi referensi dalam pembuatan standar SCADA: Teleinformasi Data Untuk Pemeliharaan Instalasi Sistem Tenaga Listrik. a. SNI 04-7021.1.1-2004: 2004, Peralatan dan Sistem Telekontrol Bagian 1: Pertimbangan Umum Seksi 1: Prinsip Umum; b. Keputusan Menteri Energi dan Sumberdaya Mineral Nomor: 150K/30/MEM/2004, Aturan Jaringan Sistem Tenaga Listrik Jawa-Madura-Bali. 4. Istilah dan Definisi 4.1 Alarm Perubahan kondisi dari peralatan atau sistem yang telah terdeteksi sebelumnya karena fungsi yang tidak dilakukan oleh operator/dispatcher, atau kegagalan peralatan untuk merespon secara benar. Indikasi alarm berupa audible atau visual, atau keduanya. 1

4.2 Control center Pusat kendali pengoperasian sistem tenaga listrik dimana master station ditempatkan. 4.3 Distribution control center (DCC) Pusat kendali jaringan distribusi. 4.4 Feeder colouring Pewarnaan penyulang pada jaringan tenaga listrik dalam kondisi bertegangan. 4.5 Gardu hubung Gardu yang mempunyai fungsi utama melakukan manuver antar feeder. 4.6 Gardu induk Gardu yang mempunyai fungsi sebagai pusat pembagi beban. 4.7 Gardu tengah Gardu yang merupakan titik tengah beban atau titik tengah feeder. 4.8 Inter distribution control center (IDCC) Pusat kendali yang terhubung dengan beberapa distribution control center. 4.9 Inter regional control center (IRCC) Pusat kendali yang terhubung dengan beberapa regional control center. 4.10 Keypoint Peralatan switching dimana bisa dilakukan manuver antara dua feeder atau lebih. 4.11 Maintenance center Workstation di luar control center yang digunakan untuk keperluan pemeliharaan. 2

SPLN S5.001: 2008 4.12 National control center (NCC) Pusat kendali yang terhubung dengan beberapa inter regional control center. 4.13 Operator Petugas yang mengawasi dan mengeksekusi secara lokal peralatan di gardu induk. 4.14 Regional control center (RCC) Pusat kendali jaringan transmisi tegangan tinggi. 4.15 Regu pemeliharaan Petugas yang melakukan pemeliharaan pada instalasi sistem tenaga listrik. 4.16 Supervisory control and data acquisition (SCADA) Sistem yang mengawasi dan mengendalikan peralatan proses yang tersebar secara geografis. [ IEC 870-1-3 ] 4.17 Telecontrol Kendali peralatan operasional jarak jauh menggunakan transmisi informasi dengan teknik telekomunikasi. [IEV 371-01-01] CATATAN: Telekontrol dapat berisi kombinasi perintah, alarm, indikasi, metering/pengukuran, proteksi dan fasilitas tripping, tidak menggunakan pesan suara. 4.18 Telesignal Pengawasan status dari peralatan operasional dalam jarak tertentu dengan menggunakan teknik telekomunikasi seperti kondisi alarm, posisi switch atau posisi katup. [IEV 371-01- 04] 4.19 Telemetering Transmisi nilai variabel yang diukur dengan menggunakan teknik telekomunikasi. [IEV 371-01-03] 5. Umum 5.1 Fasilitas SCADA Setiap pembangunan pembangkit, gardu induk, gardu hubung, gardu tengah, key point dan fasilitas sistem tenaga listrik yang baru harus dapat dipantau dari control center dan 3

dilakukan pengujian sebelum diintegrasikan ke sistem transmisi atau sistem distribusi tenaga listrik. 5.2 Teleinformasi data Standar ini membedakan teleinformasi data untuk transmisi dan distribusi. Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik dapat dilihat pada pada Lampiran A Daftar Teleinformasi (Transmisi) sampai dengan Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi). Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi maka master station dapat digunakan untuk fungsi RCC dan DCC. Dalam hal ini teleinformasi yang digunakan mengacu pada teleinformasi data transmisi dan distribusi. Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik ditampilkan pada Maintenance Center dan Local HMI (Human Machine Interface). Konfigurasi workstation di luar control center yang difungsikan untuk Maintenance Center, menampilkan kebutuhan teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik, dapat dilihat pada SPLN S3.001: 2008 Butir 5.2 dan untuk Local HMI (Human Machine Interface) dapat dilihat pada SPLN S3.001: 2008 Butir 7.2. Setiap pembangunan SCADA untuk fasilitas sistem tenaga listrik, kebutuhan teleinformasi datanya harus mengacu pada SPLN S5.001:2008 Teleinformasi data untuk operasi jaringan tenaga listrik dan SPLN S5.002: 2008 Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik. 5.3 Struktur informasi Event dan alarm pemeliharaan merupakan informasi kepada regu pemeliharaan dan operator tentang kejadian pada peralatan sistem tenaga listrik yang tampil di monitor dan disimpan di data historikal. Struktur informasi event dan alarm SCADA dapat dilihat pada Lampiran E Struktur Informasi. 5.4 Simbol dan warna Simbol dan warna diperlukan untuk penyajian diagram sistem tenaga listrik pada monitor dan layar tayang. Simbol dan warna untuk tiap jenis dan kondisi peralatan bersifat informatif dan dipilih sedemikian rupa sehingga jenis dan kondisi peralatan tersebut mudah dikenali oleh regu pemeliharaan dan operator. Simbol dan warna dapat dilihat pada Lampiran F Simbol dan Warna. 6. Perbatasan Kebutuhan Teleinformasi Data Teleinformasi data yang dikirim ke/dari suatu control center ditentukan oleh kewenangannya dalam operasi sistem, sehingga dibutuhkan adanya batas yang jelas antara kewenangan IRCC dan RCC serta RCC dan DCC. Berikut ini dijelaskan perbatasan kebutuhan teleinformasi data antara IRCC dan RCC serta antara RCC dan DCC. 4

SPLN S5.001: 2008 6.1 Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC adalah di titik pelayanan tegangan ekstra tinggi atau tegangan tinggi yang ditentukan, dan atau seperti Gambar 1 dan Gambar 2. a. Bila sisi sekunder IBT terhubung dengan konfigurasi double busbar BUSBAR TET/TT IRCC RCC BUSBAR TT Gambar 1. Batas wewenang antara IRCC dengan RCC (Tipe-a) b. Bila sisi sekunder IBT terhubung dengan konfigurasi 1½ Breaker BUSBAR TET/TT BUSBAR TT IRCC RCC BUSBAR TT Gambar 2. Batas wewenang antara IRCC dengan RCC (Tipe-b) 5

6.2 Perbatasan kebutuhan teleinformasi data antara RCC dan DCC Perbatasan kebutuhan teleinformasi data antara RCC dan DCC di gardu induk ditunjukan pada Gambar 3. BUSBAR TT L/R P Q V I RCC DCC BUSBAR TM Gambar 3. Batas wewenang antara RCC dengan DCC Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi (belum dipisahkan antara fungsi RCC dan DCC) maka perbatasan kebutuhan teleinformasi data dapat mengacu pada perbatasan fungsi RCC dan DCC atau disesuaikan dengan SOP yang berlaku di daerah tersebut. 6

SPLN S5.001: 2008 Lampiran A Daftar Teleinformasi (Transmisi) 7

A-1: Telesignal No Kode Fungsi Implementasi 1 BI Bus isolator switch closed/opened Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor Single (S) or Double (D) Indication D Alarm (A) or Event/ Indication (I) I 2 CAM Capasitor Auto/Manual Capasitor D I 3 CB Circuit breaker closed/opened Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor 4 CD Control disable switch RTU D I 5 CSO Check synchronizing override Gardu induk, Kopel, Feeder, D I Diameter 6 DCBC Dummy breaker closed/opened Gardu induk D I 7 ES Earth Switch Closed/Opened Kopel, Feeder, Trafo, Diameter, D I Capasitor, Reaktor 8 GUC Generator unit run/stop Generator D I 9 LFA Load frequency available/not available Generator D I 10 LFC Load frequency control on/off switch Generator D I 11 LFR Load frequency request on/off Generator D I 12 LI Line isolator switch closed/opened Feeder, Trafo D I 13 LR Local remote Gardu induk, Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor 14 LRT Local remote switch for tapchanger Trafo D I 15 PSO Power station operated Generator D I 16 RACK Circuit Breaker Rack-In/Rack-Out Distribution Transformer D I 17 RMT Reset Master Trip Gardu induk D I 18 SAM Synchronization Auto/Manual Gardu induk, Kopel, Feeder, D I Trafo, Diameter 19 TC Tap changer raise/lower Trafo D I 20 TCC Tap changer auto/manual Trafo D I 21 TFAM Transformer Fan Auto/Manual Transformer D I 22 110RF 110 VDC Rectifier failure Gardu Induk S A 23 110SF 110 VDC Supply failure Gardu Induk S A 24 220F 220 VAC Failure Gardu Induk S A 25 220RF 220 VDC Rectifier failure Gardu Induk S A 26 220SF 220 VDC Supply failure Gardu Induk S A 27 24RF 24 VDC Rectifier failure Gardu Induk S A 28 24SF 24 VDC Supply failure Gardu Induk S A 29 380F 380 VAC Failure Gardu Induk S A 30 48RF 48 VDC Rectifier failure Gardu Induk S A 31 48SF 48 VDC Supply failure Gardu Induk S A 32 AIRCF Air conditioning failure Gardu Induk S A 33 AQR Automatic power factor regulator Generator S I D D I I 8

SPLN S5.001: 2008 No Kode Fungsi Implementasi Single (S) or Double (D) Indication Alarm (A) or Event/ Indication (I) active 34 AR Circuit breaker auto reclose Feeder S I 35 ARO Auto reclose off Feeder S I 36 AVR Automatic voltage regulator on/off Generator S I 37 BPA Busbar protection (a) Busbar S A 38 BPAF Busbar protection (a) failure Busbar S A 39 BPB Busbar protection (b) Busbar S A 40 BPBF Busbar protection (b) failure Busbar S A 41 CBDF Circuit breaker drive failure Kopel, Feeder, Trafo, Diameter, S A Capasitor, Reaktor 42 CBFA Circuit breaker failure (a) operate Kopel, Feeder, Trafo, Diameter, S A Capasitor, Reaktor 43 CBFB Circuit breaker failure (b) operate Kopel, Feeder, Trafo, Diameter, S A Capasitor, Reaktor 44 CBM Circuit breaker maintenance Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor S I 45 CBTR Circuit breaker trip Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor, Generator 46 CCPA Circulating current protection (a) operate Diameter S A 47 CCPB Circulating current protection (b) operate Diameter S A 48 CCPF Circulating current protection failure Diameter S A 49 CDAF Current differential relay (a) failure Feeder S A 50 CDAR Current differential (a) phase R Feeder S A 51 CDAS Current differential (a) phase S Feeder S A 52 CDAT Current differential (a) phase T Feeder S A 53 CDBF Current differential relay (b) failure Feeder S A 54 CDBR Current differential (b) phase R Feeder S A 55 CDBS Current differential (b) phase S Feeder S A 56 CDBT Current differential (b) phase T Feeder S A 57 CF Carrier faulty Feeder S A 58 CSP Check synchronizing in progress Gardu induk S I 59 CTE Cabinet temperatur Remote station S I Kopel, Feeder, 60 DCF DC supply failure Trafo, Capasitor, S A Reaktor 61 DCG DC ground Gardu Induk S A 62 DEARX Directional earth fault (a) relay receive Feeder S A 63 DEATX Directional earth fault (a) relay transmit Feeder S A 64 DEBRX Directional earth fault (b) relay receive Feeder S A 65 DEBTX Directional earth fault (b) relay transmit Feeder S A 66 DEFAF Directional earth fault (a) failure Feeder S A 67 DEFAR Directional earth fault (a) phase r Feeder S A 68 DEFAS Directional earth fault (a) phase s Feeder S A 69 DEFAT Directional earth fault (a) phase t Feeder S A S A 9

No Kode Fungsi Implementasi Single (S) or Double (D) Indication Alarm (A) or Event/ Indication (I) 70 DEFBF Directional earth fault (b) failure Feeder S A 71 DEFBR Directional earth fault (b) phase r Feeder S A 72 DEFBS Directional earth fault (b) phase s Feeder S A 73 DEFBT Directional earth fault (b) phase t Feeder S A 74 DFRF Disturbance fault recorder faulty Gardu Induk S A 75 DIFF Differential failure Trafo S A 76 DOOR Door activated Gardu Induk S I Busbar, Kopel, 77 DSDF Disconnecting switch driving fault Feeder, Trafo, S A Capasitor 78 DTARX Direct transfer trip (a) receive Feeder S I 79 DTATX Direct transfer trip (a) transmit Feeder S I 80 DTBRX Direct transfer trip (b) receive Feeder S I 81 DTBTX Direct transfer trip (b) transmit Feeder S I 82 DZ1AR Distance (a) phase R zone 1 Feeder S A 83 DZ1AS Distance (a) phase S zone 1 Feeder S A 84 DZ1AT Distance (a) phase T zone 1 Feeder S A 85 DZ1BR Distance (b) phase R zone 1 Feeder S A 86 DZ1BS Distance (b) phase S zone 1 Feeder S A 87 DZ1BT Distance (b) phase T zone 1 Feeder S A 88 DZ2AR Distance (a) phase R zone 2 Feeder S A 89 DZ2AS Distance (a) phase S zone 2 Feeder S A 90 DZ2AT Distance (a) phase T zone 2 Feeder S A 91 DZ2BR Distance (b) phase R zone 2 Feeder S A 92 DZ2BS Distance (b) phase S zone 2 Feeder S A 93 DZ2BT Distance (b) phase T zone 2 Feeder S A 94 DZ3AR Distance (a) phase R zone 3 Feeder S A 95 DZ3AS Distance (a) phase S zone 3 Feeder S A 96 DZ3AT Distance (a) phase T zone 3 Feeder S A 97 DZ3BR Distance (b) phase R zone 3 Feeder S A 98 DZ3BS Distance (b) phase S zone 3 Feeder S A 99 DZ3BT Distance (b) phase T zone 3 Feeder S A 100 DZAF Distance relay (a) failure Feeder S A 101 DZARX Distance (a) relay receive Feeder S I 102 DZATX Distance (a) relay transmit Feeder S I 103 DZBF Distance relay (b) failure Feeder S A 104 DZBRX Distance (b) relay receive Feeder S I 105 DZBTX Distance (b) relay transmit Feeder S I 106 ERF Event recorder failure Busbar, Kopel, Bus Section, Feeder, Trafo, Reaktor, S A Diameter 107 FOTF FO terminal faulty Gardu Induk S A 108 FPO Fire protection operated Trafo S I 109 FRA Fire alarm Gardu Induk S A 110 FRSF Fire alarm system failure Gardu Induk S A 111 GFRF Ground fault relay failure Gardu Induk, Kopel, Bus Section, Feeder, Trafo, S A Capasitor 112 GOV Free acting governor active Generator S I 10

SPLN S5.001: 2008 No Kode Fungsi Implementasi Single (S) or Double (D) Indication Alarm (A) or Event/ Indication (I) 113 GRE Genset ready Gardu Induk S I 114 GTT Generator transformer trip Trafo Generator S A 115 IR Internal remote station Remote Station S A 116 LFF Load frequency control unit failure Generator S A 117 LOWCT Low oil pressure cable trip Cable Feeder S A 118 LPA Low pressure alarm Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, S A Diameter, Generator 119 LPB Low pressure block Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, S A Diameter, Generator 120 LPT Low pressure trip Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, S A Diameter, Generator 121 MTO Master trip operate Gardu Induk S A 122 OCPA Oil cable pressure alarm Cable Feeder S A 123 OCRF Over current relay failure Kopel, Bus Section, Feeder, Trafo, S A Capasitor 124 OTA Oil temperature alarm Trafo S A 125 OTT Oil temperatur trip Trafo S A 126 OVR Over voltage relay operate Busbar, Feeder, Trafo, Capasitor S A 127 OVRF Over voltage relay failure Busbar, Feeder, Trafo, Capasitor S A 128 P1DIF Differential Trafo, Capasitor, Reaktor S A 129 P1REF Restricted earth fault Trafo S A 130 P2GFR Ground fault relay Kopel, Bus Section, Feeder, Trafo, S A Capasitor, Reaktor 131 P2OCR Over current relay Kopel, Feeder, Bus Section, Trafo, S A Reaktor, Capasitor 132 PBXF PABX faulty Gardu Induk S A 133 PD Pole discrepancy Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, S A Diameter 134 PHR Trip phase R Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, S A Diameter 135 PHS Trip phase S Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, S A Diameter 136 PHT Trip phase T Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, S A Diameter 137 PLCF PLC terminal faulty Gardu Induk S A 11

No Kode Fungsi Implementasi 138 POT Protection on test Busbar, Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter 139 PRDT Pressure relay device trip Trafo, Reaktor Single (S) or Double (D) Indication S Alarm (A) or Event/ Indication (I) 140 PTF Protection faulty Gardu induk S A 141 PWF Pilot wire failure Feeder S A 142 RADF Radio link faulty Gardu Induk S A 143 RBUC2 Reaktor bucholz trip Reaktor S A 144 RBUCA Reaktor bucholz alarm Reaktor S A 145 RCBF Relay circuit breaker fail failure Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, S A Diameter 146 RCFF Reaktor cooling fan failure Reaktor S A 147 REFF Restrcited earth fault failure Trafo S A 148 RF Reactor failure Reaktor S A 149 RFDP Reaktor fire detection & protection Reaktor S A 150 ROLA Reaktor oil level alarm Reaktor S A 151 RSPA Reaktor sudden pressure alarm Reaktor S A 152 RSPT Reaktor sudden pressure trip Reaktor S A 153 RSTA Reset alarm Gardu Induk S I 154 RTN Relay tegangan nol Gardu Induk S I 155 RTUA Remote Station Alarm Gardu Induk S A 156 SIA Station intruder alarm Gardu Induk S A 157 SYNF Synchronizing failure Gardu induk S A 158 SZPA Short zone protection (a) operate Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, S A Diameter 159 SZPB Short zone protection (b) operate Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, S A Diameter 160 SZPF Short zone protection failure Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, S A Diameter 161 TAF Tranformer AVR failure Trafo S A 162 TBUC2 Transformer Bucholz trip Trafo S A 163 TBUCA Transformer Bucholz alarm Trafo S A 164 TCA Tap changer alarm Trafo S A 165 TCFF Transformer cooling fan failure Trafo S A 166 TCH Tap changer high limit Trafo S A 167 TCL Tap changer low limit Trafo S A 168 TCPF Transformer cooling pump failure Trafo S A 169 TCS1 Trip coil supervisory 1 Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, S A Diameter 170 TCS2 Trip coil supervisory 2 Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter S A I 12

SPLN S5.001: 2008 No Kode Fungsi Implementasi Single (S) or Double (D) Indication Alarm (A) or Event/ Indication (I) 171 TFDP Transformer fire detection & protection Trafo S A 172 TJANT Transformer jansen trip Trafo S I 173 TOLA Transformer oil level alarm Trafo S I 174 TOOS Transformer out of step alarm Trafo 175 TPAF Teleprotection (a) failure Feeder 176 TPBF Teleprotection (b) failure Feeder S A 177 TPIF Tap position indication failure Trafo S A 178 TSPA Transformer sudden pressure alarm Trafo S A 179 TSPT Transformer sudden pressure trip Trafo S A 180 UFR Under frequency relay operate Feeder, Trafo S A 181 UT Unit trip Generator S A 182 UVR Under voltage relay Busbar S A 183 UVRF Under voltage relay failure Busbar, Feeder, Trafo S A 184 VS Voltage status Busbar S I 185 VTF Voltage transformer failure Busbar, Feeder, Trafo, Capasitor S A 186 WTHVA HV winding temperatur alarm Trafo S A 187 WTHVT HV winding temperatur trip Trafo S A 188 WTLVA LV winding temperatur alarm Trafo S A 189 WTLVT LV winding temperatur trip Trafo S A 190 SIB Software interlocking bypass Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, S A Diameter 191 IEDF IED Faulty Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, S A Diameter 192 SOTF Switch on to fault Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, S A Diameter 193 PD Partial discharge (primary-secondarytersier) Trafo S I 194 OFO Online filtering OLTC Trafo S I 195 DGA Dissolve gas analysis Trafo S I 196 NVD Neutral voltage displacement (tersier) Trafo S I 197 TCT Tap changer trip Trafo S A KETERANGAN: A = Announciation of abnormal condition (audible alarm, flashing display, etc) I = Event/Indication (normal condition) 13

A-2: Telemeasurement No Kode Fungsi Implementasi 1 AMF Amperes fault ( per phase ) Feeder, Trafo, Capasitor Reaktor 2 CCB Counter of circuit breaker Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor 3 CNTA Counter arester Feeder, Trafo 4 CTPI Counter tap position indication Trafo 5 F Frekuensi Gardu induk 6 I Arus Feeder, Trafo, Kopel 7 KVARH Kilovar hour Feeder, Trafo 8 KWH Kilowatt hour Feeder, Trafo 9 P Daya Aktif Feeder, Trafo, Generator 10 POAQ Real power setting Generator 11 PRAQ Maksimum power variation setting Generator 12 PRES Pressure 13 Q Daya Reaktif Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor Feeder, Trafo, Generator, Capasitor, Reaktor 14 RH Relative humidity Gardu Induk 15 TEMP Temperature Trafo, Reaktor 16 V Tegangan Feeder, Trafo, Generator, Busbar 14

SPLN S5.001: 2008 A-3: Tap Changer Position No Kode Fungsi Implementasi 1 TPI Tap position indication Transformer 15

A-4: Remote Control Digital No Kode Fungsi Implementasi 1 BI Bus isolator switch closed/opened 2 CB Circuit breaker closed/opened Kopel, Feeder, Transformer, Capasitor, Reaktor, Diameter Kopel, Feeder, Transformer, Capasitor, Reaktor, Diameter 3 CD Control disable switch Remote Station 4 CSO Check synchronizing override Gardu induk 5 DCBC Dummy circuit breaker closed/opened Remote Station 6 LI Line isolator switch closed/opened 7 LR Local remote Feeder, Transformer, Capasitor, Reaktor Gardu Induk, Kopel, Bus Section, Feeder, Transformer, Capasitor, Reaktor, Diameter 8 LRT Local/remote switch for tapchanger Trafo 9 RMT Reset master trip Gardu Induk 10 SAM Synchronization auto/manual Gardu Induk, Kopel, Bus Section, Feeder, Transformer, Diameter 11 TC Tap changer raise/lower Trafo 12 TCC Tap changer auto/manual Trafo 13 TFAM Transformer fan auto/manual Trafo 16

SPLN S5.001: 2008 Lampiran B Bidang Transmisi (Teleinformasi pada Berbagai Konfigurasi Gardu Induk) 17

TA-01: Konfigurasi Umum Pada 1½ Breaker KONFIGURASI UMUM PADA 1½ BREAKER TA-01 BAY REAKTOR BAY GENERATOR P Q V Q P Q I BUSBAR -A V L/R L/R L/R L/R L/R L/R L/R L/R V BUSBAR -B L/R P Q V I P Q V I L/R P Q V I BAY TRANSMISI BAY IBT BAY TRAFO TENAGA 18

SPLN S5.001: 2008 Teleinformasi Data Untuk Konfigurasi Umum Pada 1½ Breaker Group Bay GARDU INDUK BUSBAR 1 F Frekuensi 1 TM 14 RH Relative humidity 1 15 TEMP Temperature 1 22 110RF 110 VDC rectifier failure A 1 23 110SF 110 VDC supply failure A 1 24 220F 220 VAC failure A 1 25 220RF 220 VDC rectifier failure A 1 26 220SF 220 VDC supply failure A 1 27 24RF 24 VDC rectifier failure A 1 28 24SF 24 VDC supply failure A 1 29 380F 380 VAC failure A 1 30 48RF 48 VDC rectifier failure A 1 31 48SF 48 VDC supply failure A 1 32 AIRCF Air conditioning failure A 1 61 DCG DC ground A 1 TSS 76 DOOR Door activated A 1 107 FOTF FO terminal faulty A 1 109 FRA Fire alarm A 1 110 FRSF Fire alarm system failure A 1 111 GFRF Ground fault relay failure A 1 113 GRE Genset ready I 1 121 MTO Master trip operate A 1 132 PBXF Pabx faulty A 1 137 PLCF PLC terminal faulty A 1 142 RADF Radio link faulty A 1 153 RSTA Reset alarm A 1 154 RTN Relay tegangan nol A 1 155 RTUA Remote station alarm A 1 157 SIA Station intruder alarm A 1 5 CSO Check synchronizing override I 1 TSD 13 LR Local remote I 1 17 RMT Reset master trip I 1 18 SAM Synchronization auto/manual I 1 3 CSO Check synchronizing override 1 RCD 7 LR Local remote 1 9 RMT Reset master trip 1 10 SAM Synchronization auto/manual 1 TM 7 V Tegangan 2 37 BPA Busbar protection (a) A 2 38 BPAF Busbar protection (a) failure A 2 39 BPB Busbar protection (b) A 2 40 BPBF Busbar protection (b) failure A 2 77 DSDF Disconnecting switch driving fault A 2 TSS 106 ERF Event recorder failure A 2 126 OVR Over voltage relay operate A 2 127 OVRF Over voltage relay failure A 2 138 POT Protection on test I 2 182 UVR Under voltage relay operate A 2 183 UVRF Under voltage relay failure A 2 19

Group Bay REMOTE STATION DIAMETER 184 VS Voltage status I 2 TSD 7 ES Earth switch closed/opened I 2 TSS 59 CTE Cabinet temperatur A 1 115 IR Internal remote station A 1 TSD 4 CD Control disable switch I 1 3 CD Control disable switch 1 RCD Dummy circuit breaker 5 DCBC closed/opened 1 TM 2 CCB Counter of circuit breaker 3 12 PRES Pressure 3 41 CBDF Circuit breaker drive failure A 3 42 CBFA Circuit breaker failure (a) operate A 3 43 CBFB Circuit breaker failure (b) operate A 3 44 CBM Circuit breaker maintenance I 3 46 CCPA Circulating current protection (a) A operate 1 47 CCPB Circulating current protection (b) A operate 1 48 CCPF Circulating current protection A failure 3 58 CSP Check synchronizing in progress I 3 106 ERF Event recorder failure A 3 118 LPA Low pressure alarm A 3 119 LPB Low pressure block A 3 120 LPT Low pressure trip A 3 TSS 121 MTO Master trip operate A 1 133 PD Pole discrepancy A 3 134 PHR Trip phase R A 3 135 PHS Trip phase S A 3 136 PHT Trip phase T A 3 138 POT Protection on test I 1 145 RCBF Relay circuit breaker fail failure A 3 157 SYNF Synchronizing failure A 3 158 SZPA Short zone protection (a) operate A 3 159 SZPB Short zone protection (b) operate A 3 160 SZPF Short zone protection failure A 3 169 TCS1 Trip coil supervisory 1 A 3 170 TCS2 Trip coil supervisory 2 A 3 190 SIB Software interlocking bypass A 3 191 IEDF IED Faulty A 3 192 SOTF Switch on to fault A 3 1 BI Bus isolator switch closed/opened I 6 TSD 3 CB Circuit breaker closed/opened I 3 5 CSO Check synchronizing override I 3 13 LR Local remote I 3 18 SAM Synchronization auto/manual I 3 Bus isolator switch 1 BI 6 closed/opened RCD 2 CB Circuit breaker closed/opened 3 4 CSO Check synchronizing override 3 20

SPLN S5.001: 2008 Group Bay BAY TRANSMISI TM TSS 7 LR Local remote 3 10 SAM Synchronization auto/manual 3 1 AMF Amperes fault ( per phase ) 1 3 CNTA *) Counter arester 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1 12 PRES Pressure 1 13 Q Daya reaktif 1 16 V Tegangan 1 49 CDAF Current differential relay (a) A failure 1 50 CDAR Current differential (a) phase R A 1 51 CDAS Current differential (a) phase S A 1 52 CDAT Current differential (a) phase T A 1 53 CDBF Current differential relay (b) A failure 1 54 CDBR Current differential (b) phase R A 1 55 CDBS Current differential (b) phase S A 1 56 CDBT Current differential (b) phase T A 1 57 CF *) Carrier faulty A 1 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 *) Directional earth fault (a) relay A 62 DEARX receive 1 *) Directional earth fault (a) relay A 63 DEATX transmit 1 *) Directional earth fault (b) relay A 64 DEBRX receive 1 *) Directional earth fault (b) relay A 65 DEBTX transmit 1 66 DEFAF *) Directional earth fault (a) failure A 1 67 DEFAR Directional earth fault (a) phase R A 1 68 DEFAS Directional earth fault (a) phase S A 1 69 DEFAT Directional earth fault (a) phase T A 1 70 DEFBF *) Directional earth fault (b) failure A 1 71 DEFBR Directional earth fault (b) phase R A 1 72 DEFBS Directional earth fault (b) phase S A 1 73 DEFBT Directional earth fault (b) phase T A 1 74 DFRF Disturbance fault recorder faulty A 1 77 DSDF Disconnecting switch driving fault A 1 78 DTARX *) Direct transfer trip (a) receive I 1 79 DTATX *) Direct transfer trip (a) transmit I 1 80 DTBRX *) Direct transfer trip (b) receive I 1 81 DTBTX *) Direct transfer trip (b) transmit I 1 82 DZ1AR *) Distance (a) phase R zone 1 A 1 83 DZ1AS *) Distance (a) phase S zone 1 A 1 84 DZ1AT *) Distance (a) phase T zone 1 A 1 85 DZ1BR *) Distance (b) phase R zone 1 A 1 86 DZ1BS *) Distance (b) phase S zone 1 A 1 21

Group Bay 87 DZ1BT *) Distance (b) phase T zone 1 A 1 88 DZ2AR *) Distance (a) phase R zone 2 A 1 89 DZ2AS *) Distance (a) phase S zone 2 A 1 90 DZ2AT *) Distance (a) phase T zone 2 A 1 91 DZ2BR *) Distance (b) phase R zone 2 A 1 92 DZ2BS *) Distance (b) phase S zone 2 A 1 93 DZ2BT *) Distance (b) phase T zone 2 A 1 94 DZ3AR *) Distance (a) phase R zone 3 A 1 95 DZ3AS *) Distance (a) phase S zone 3 A 1 96 DZ3AT *) Distance (a) phase T zone 3 A 1 97 DZ3BR *) Distance (b) phase R zone 3 A 1 98 DZ3BS *) Distance (b) phase S zone 3 A 1 99 DZ3BT *) Distance (b) phase T zone 3 A 1 100 DZAF *) Distance relay (a) failure A 1 101 DZARX *) Distance (a) relay receive I 1 102 DZATX *) Distance (a) relay transmit I 1 103 DZBF *) Distance relay (b) failure A 1 104 DZBRX *) Distance (b) relay receive I 1 105 DZBTX *) Distance (b) relay transmit I 1 106 ERF Event recorder failure A 1 111 GFRF Ground fault relay failure A 1 117 LOWCT** A Low oil pressure cable trip ) 1 121 MTO Master trip operate A 1 122 OCPA**) Oil cable pressure alarm A 1 123 OCRF Over current relay failure A 1 126 OVR *) Over voltage relay operate A 1 127 OVRF *) Over voltage relay failure A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 138 POT Protection on test I 1 141 PWF Pilot wire failure A 1 145 RCBF Relay circuit breaker fail failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 175 TPAF *) Teleprotection (a) failure A 1 176 TPBF *) Teleprotection (b) failure A 1 180 UFR Under frequency relay operate A 1 182 UVR *) Under voltage relay operate A 1 183 UVRF *) Under voltage relay failure A 1 185 VTF Voltage transformer failure A 1 190 SIB Software interlocking bypass A 1 191 IEDF IED Faulty A 1 192 SOTF Switch on to fault A 1 7 ES Earth switch closed/opened I 1 TSD Line isolator switch 12 LI closed/opened I 1 RCD 6 LI Line isolator switch 1 22

SPLN S5.001: 2008 Group Bay BAY IBT closed/opened TC 1 TPI Tap position indication I 3 1 AMF Amperes fault ( per phase ) 3 3 CNTA Counter arester 3 4 CTPI Counter tap position indication 3 6 I Arus 3 7 KVARH Kilovar hour 1 TM 8 KWH Kilowatt hour 1 9 P Daya aktif 1 12 PRES Pressure 3 13 Q Daya reaktif 1 15 TEMP Temperature 12 16 V Tegangan 3 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance I 1 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1 108 FPO Fire protection operated A 3 111 GFRF Ground fault relay failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 121 MTO Master trip operate A 1 123 OCRF Over current relay failure A 1 TSS 124 OTA Oil temperature alarm A 3 125 OTT Oil temperatur trip A 3 128 P1DIF Differential A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test I 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 147 REFF Restricted earth fault failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 161 TAF Tranformer AVR failure A 3 23

Group Bay TSD RCD 162 TBUC2 Transformer bucholz trip A 3 163 TBUCA Transformer bucholz alarm A 3 164 TCA Tap changer alarm A 3 165 TCFF Transformer cooling fan failure A 3 166 TCH Tap changer high limit A 3 167 TCL Tap changer low limit A 3 168 TCPF Transformer cooling pump failure A 3 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 171 TFDP Transformer fire detection & protection A 3 172 TJANT Transformer jansen trip A 3 173 TOLA Transformer oil level alarm A 3 174 TOOS Transformer out of step alarm A 3 177 TPIF Tap position indication failure A 3 178 TSPA Transformer sudden pressure alarm A 3 179 TSPT Transformer sudden pressure trip A 3 180 UFR Under frequency relay operate A 1 185 VTF Voltage transformer failure A 3 186 WTHVA HV winding temperatur alarm A 3 187 WTHVT HV winding temperatur trip A 3 188 WTLVA LV winding temperatur alarm A 3 189 WTLVT LV winding temperatur trip A 3 190 SIB Software interlocking bypass A 1 191 IEDF IED Faulty A 1 192 SOTF Switch on to fault A 1 193 PD Partial discharge (primarysecondary-tersier) I 9 194 OFO Online filtering OLTC I 3 195 DGA Dissolve gas analysis I 3 196 NVD Neutral voltage displacement I (tersier) 3 197 TCT Tap changer trip A 3 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 7 ES Earth switch closed/opened I 2 12 LI Line isolator switch closed/opened I 1 13 LR Local remote I 1 14 LRT Local/remote switch for tapchanger I 3 18 SAM Synchronization auto/manual I 1 20 TCC Tap changer auto/manual I 3 21 TFAM Transformer fan auto/manual I 3 2 CB Circuit breaker closed/opened 1 4 CSO Check synchronizing override 1 6 LI Line isolator switch closed/opened 1 7 LR Local remote 1 8 LRT Local/remote switch for 3 24

SPLN S5.001: 2008 Group Bay BAY TRAFO TENAGA tapchanger 10 SAM Synchronization auto/manual 1 11 TC Tap changer raise/lower 3 12 TCC Tap changer auto/manual 3 13 TFAM Transformer fan auto/manual 3 TC 1 TPI Tap position indication I 1 1 AMF Amperes fault ( per phase ) 1 3 CNTA Counter arester 1 4 CTPI Counter tap position indication 1 6 I Arus 1 7 KVARH Kilovar hour 1 TM 8 KWH Kilowatt hour 1 9 P Daya aktif 1 12 PRES Pressure 1 13 Q Daya reaktif 1 15 TEMP Temperature 1 16 V Tegangan 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1 108 FPO Fire protection operated A 1 111 GFRF Ground fault relay failure A 1 121 MTO Master trip operate A 1 123 OCRF Over current relay failure A 1 124 OTA Oil temperature alarm A 1 125 OTT Oil temperatur trip A 1 126 OVR Over voltage relay operate A 1 127 OVRF Over voltage relay failure A 1 128 P1DIF Differential A 1 129 P1REF Restricted earth fault A 1 TSS 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 138 POT Protection on test I 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 147 REFF Restricted earth fault failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 161 TAF Tranformer avr failure A 1 162 TBUC2 Transformer bucholz trip A 1 163 TBUCA Transformer bucholz alarm A 1 164 TCA Tap changer alarm A 1 165 TCFF Transformer cooling fan failure A 1 166 TCH Tap changer high limit A 1 167 TCL Tap changer low limit A 1 168 TCPF Transformer cooling pump failure A 1 25

Group Bay BAY REAKTOR TSD RCD TM TSS 171 TFDP Transformer fire detection & protection A 1 172 TJANT Transformer jansen trip A 1 173 TOLA Transformer oil level alarm A 1 174 TOOS Transformer out of step alarm A 1 177 TPIF Tap position indication failure A 1 178 TSPA Transformer sudden pressure alarm A 1 179 TSPT Transformer sudden pressure trip A 1 180 UFR Under frequency relay operate A 1 182 UVR Under voltage relay operate A 1 183 UVRF Under voltage relay failure A 1 185 VTF Voltage transformer failure A 1 186 WTHVA HV winding temperatur alarm A 1 187 WTHVT HV winding temperatur trip A 1 188 WTLVA LV winding temperatur alarm A 1 189 WTLVT LV winding temperatur trip A 1 190 SIB Software interlocking bypass A 1 191 IEDF IED Faulty A 1 192 SOTF Switch on to fault A 1 7 ES Earth switch closed/opened I 1 12 LI Line isolator switch closed/opened I 1 14 LRT Local/remote switch for tapchanger I 1 20 TCC Tap changer auto/manual I 1 21 TFAM Transformer fan auto/manual I 1 6 LI Line isolator switch closed/opened 1 8 LRT Local/remote switch for tapchanger 1 11 TC Tap changer raise/lower 1 12 TCC Tap changer auto/manual 1 13 TFAM Transformer fan auto/manual 1 1 AMF Amperes fault ( per phase ) 1 12 PRES Pressure 1 13 Q Daya reaktif 1 15 TEMP Temperature 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 106 ERF Event recorder failure A 1 121 MTO Master trip operate A 1 128 P1DIF Differential A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 138 POT Protection on test A 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 148 RF Reaktor failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 26

SPLN S5.001: 2008 Group Bay BAY GENERATOR 160 SZPF Short zone protection failure A 1 190 SIB Software interlocking bypass A 1 191 IEDF IED Faulty A 1 192 SOTF Switch on to fault A 1 7 ES Earth switch closed/opened I 1 TSD 12 LI Line isolator switch closed/opened I 1 21 TFAM Transformer fan auto/manual I 1 Line isolator switch 6 LI RCD closed/opened 1 13 TFAM Transformer fan auto/manual 1 6 I Arus 1 7 KVARH Kilovar hour 1 TM 8 KWH Kilowatt hour 1 9 P Daya aktif 2 13 Q Daya reaktif 2 16 V Tegangan 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 106 ERF Event recorder failure A 1 114 GTT Generator transformer trip A 1 121 MTO Master trip operate A 1 129 P1REF Restricted earth fault A 1 TSS 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 138 POT Protection on test A 1 147 REFF Restricted earth fault failure A 1 190 SIB Software interlocking bypass A 1 191 IEDF IED Faulty A 1 192 SOTF Switch on to fault A 1 7 ES Earth switch closed/opened I 1 TSD Line isolator switch 12 LI closed/opened I 1 RCD 6 LI Line isolator switch closed/opened 1 KETERANGAN: *) = Khusus untuk OHL Feeder **) = Khusus untuk Cable Feeder A = Alarm I = Indikasi Rincian Teleinformasi diatas adalah rincian per bay 27

TA-02: Konfigurasi Umum Pada Double Busbar KONFIGURASI UMUM PADA DOUBLE BUSBAR TA-02 BAY REAKTOR BAY GENERATOR P Q V Q P Q I BAY KOPEL L/R L/R L/R I BUSBAR - A V BUSBAR - B V L/R L/R L/R P Q V I P Q V I P Q V I L/R BAY TRANSMISI BAY TRAFO TENAGA BAY IBT Teleinformasi Data Untuk Konfigurasi Umum Pada Double Busbar Group Bay GARDU INDUK TM TSS 1 F Frekuensi 1 14 RH Relative humidity 1 15 TEMP Temperature 1 22 110RF 110 VDC rectifier failure A 1 23 110SF 110 VDC supply failure A 1 24 220F 220 VAC failure A 1 25 220RF 220 VDC rectifier failure A 1 26 220SF 220 VDC supply failure A 1 27 24RF 24 VDC rectifier failure A 1 28 24SF 24 VDC supply failure A 1 29 380F 380 VAC failure A 1 28

SPLN S5.001: 2008 Group Bay BUSBAR REMOTE STATION KOPEL 30 48RF 48 VDC rectifier failure A 1 31 48SF 48 VDC supply failure A 1 32 AIRCF Air conditioning failure A 1 61 DCG DC ground A 1 76 DOOR Door activated A 1 107 FOTF FO terminal faulty A 1 109 FRA Fire alarm A 1 110 FRSF Fire alarm system failure A 1 111 GFRF Ground fault relay failure A 1 113 GRE Genset ready I 1 132 PBXF Pabx faulty A 1 137 PLCF PLC terminal faulty A 1 142 RADF Radio link faulty A 1 153 RSTA Reset alarm A 1 154 RTN Relay tegangan nol A 1 155 RTUA Remote station alarm A 1 157 SIA Station intruder alarm A 1 5 CSO Check synchronizing override I 1 TSD 13 LR Local remote I 1 17 RMT Reset master trip I 1 18 SAM Synchronization auto/manual I 1 3 CSO Check synchronizing override 1 RCD 7 LR Local remote 1 9 RMT Reset master trip 1 10 SAM Synchronization auto/manual 1 TM 7 V Tegangan 2 37 BPA Busbar protection (a) A 2 38 BPAF Busbar protection (a) failure A 2 39 BPB Busbar protection (b) A 2 40 BPBF Busbar protection (b) failure A 2 77 DSDF Disconnecting switch driving fault A 2 TSS 106 ERF Event recorder failure A 2 126 OVR Over voltage relay operate A 2 127 OVRF Over voltage relay failure A 2 138 POT Protection on test I 2 182 UVR Under voltage relay operate A 2 183 UVRF Under voltage relay failure A 2 184 VS Voltage status I 2 TSD 7 ES Earth switch closed/opened I 2 TSS 59 CTE Cabinet temperatur A 1 115 IR Internal remote station A 1 TSD 4 CD Control disable switch I 1 RCD 3 CD Control disable switch 1 5 DCBC Dummy circuit breaker closed/opened 1 2 CCB Counter of circuit breaker 1 TM 6 I Arus 1 12 PRES Pressure 1 TSS 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 29

Group Bay BAY TRANSMISI TSD RCD TM 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance I 1 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1 111 GFRF Ground fault relay failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 121 MTO Master trip operate A 1 123 OCRF Over current relay failure A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test I 1 145 RCBF Relay circuit breaker fail failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 190 SIB Software interlocking bypass A 1 191 IEDF IED Faulty A 1 192 SOTF Switch on to fault A 1 1 BI Bus isolator switch closed/opened I 2 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 13 LR Local remote I 1 18 SAM Synchronization auto/manual I 1 1 BI Bus isolator switch closed/opened 2 2 CB Circuit breaker closed/opened 1 4 CSO Check synchronizing override 1 7 LR Local remote 1 10 SAM Synchronization auto/manual 1 1 AMF Amperes fault ( per phase ) 1 2 CCB Counter of circuit breaker 1 3 CNTA *) Counter arester 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1 12 PRES Pressure 1 13 Q Daya reaktif 1 16 V Tegangan 1 30