PENGARUH BEBAN TIDAK SEIMBANG TERHADAP EFISIENSI TRANSFORMATOR TIGA FASA PADA HUBUNGAN OPEN-DELTA



dokumen-dokumen yang mirip
PENGARUH HARMONISA PADA GARDU TRAFO TIANG DAYA 200 KVA DI PT PLN (Persero) APJ SURABAYA UTARA

PENGARUH HARMONISA PADA GARDU TRAFO TIANG DAYA 200 KVA DI PT PLN (Persero) APJ SURABAYA UTARA

AKIBAT KETIDAKSEIMBANGAN BEBAN TERHADAP ARUS NETRAL DAN LOSSES PADA TRANSFORMATOR DISTRIBUSI

PENGARUH KETIDAKSEIMBANGAN BEBAN TRANSFORMATOR KERING BHT02 RSG GA SIWABESSY TERHADAP ARUS NETRAL DAN RUGI-RUGI

Dosen Pembimbing II. Ir. Sjamsjul Anam, MT

BAB I PENDAHULUAN. yang dipakai adalah tegangan dan arus bolak-balik ( AC). Sedangkan tegangan dan arus

STUDI PENGARUH HARMONISA PADA GARDU TRAFO TIANG DAYA 200 KVA DI PT PLN (Persero) APJ SURABAYA UTARA

PENGARUH KETIDAKSEIMBANGAN BEBAN TERHADAP ARUS NETRAL DAN LOSSES PADA TRAFO DISTRIBUSI

BAB IV PEMBAHASAN KONSTRUKSI CORE PADA TRANSFORMATOR. DISTRIBUSI 20/0,4 kv, 315 kva. (Aplikasi Di PT Trafoindo Prima Perkasa)

DAFTAR ISI... DAFTAR ISI DAFTAR GAMBAR.. DAFTAR TABEL... DAFTAR LAMPIRAN...

ANALISA BERBAGAI HUBUNGAN BELITAN TRANSFORMATOR 3 PHASA DALAM KEADAAN BEBAN LEBIH (APLIKASI PADA LABORATORIUM KONVERSI ENERGI LISTRIK FT.

Jurnal Teknologi Elektro, Universitas Mercu Buana ISSN: ANALISIS VECTOR GROUP PADA HUBUNGAN PARALEL TRANSFORMATOR UNIT GARDU BERGERAK

OPTIMASI PENYEIMBANGAN BEBAN PADA TRAFO DISTRIBUSI TERHADAP SUSUT ENERGI (APLIKASI FEEDER SIKAKAP)

ABSTRAK Kata Kunci :

ESTIMASI UMUR PAKAI DAN RUGI DAYA TRANSFORMATOR. The Estimated Age of Use and Loss Power Transformer

ANALISIS KINERJA TRANSFORMATOR TIGA BELITAN SEBAGAI GENERATOR STEP-UP TRANSFORMER

ANALISIS GANGGUAN HUBUNG SINGKAT TRAFO TENAGA 60 MVA SHORT CIRCUIT ANALYSIS OF POWER TRANSFORMER 60 MVA

ANALISIS TEORITIS PENEMPATAN TRANSFORMATOR DISTRIBUSI MENURUT JATUH TEGANGAN DI PENYULANG BAGONG PADA GARDU INDUK NGAGEL

ANALISA PENGARUH BEBAN TIDAK SEIMBANG TERHADAP RUGI DAYA LISTRIK PADA JARINGAN DISTRIBUSI SEKUNDER HASBULAH

SINGUDA ENSIKOM VOL. 7 NO. 3/ Juni 2014

BAB III PERANCANGAN ALAT

EVALUASI SISTEM PENTANAHAN TRANSFORMATOR DAYA 60 MVA PLTGU INDRALAYA

ANALISIS JATUH TEGANGAN DAN RUGI DAYA PADA JARINGAN TEGANGAN RENDAH MENGGUNAKAN SOFTWARE ETAP

Studi Koordinasi Proteksi Sistem Kelistrikan di Project Pakistan Deep Water Container Port

PENGARUH ARUS NETRAL TERHADAP RUGI-RUGI BEBAN PADA TRANSFORMATOR DISTRIBUSI PLN RAYON JOHOR MEDAN

DAFTAR ISI SAMPUL DALAM...

BAB II TINJAUAN PUSTAKA

BAB II DASAR TEORI. melalui gandengan magnet dan prinsip induksi elektromagnetik [1].

Mesin Arus Bolak Balik

BAB II LANDASAN TEORI ANALISA HUBUNG SINGKAT DAN MOTOR STARTING

RANCANG BANGUN KAPASITOR BANK UNTUK EFISIENSI DAYA LISTRIK PADA INDUSTRI KECIL

PEMELIHARAAN TRANSFORMATOR DISTRIBUSI 20 KV / 220 V di PLN AREA LUBUK PAKAM

ANALISIS JATUH TEGANGAN DAN RUGI DAYA PADA JARINGAN TEGANGAN RENDAH MENGGUNAKAN SOFTWARE ETAP

BAB II JARINGAN DISTRIBUSI TENAGA LISTRIK. karena terdiri atas komponen peralatan atau mesin listrik seperti generator,

47 JURNAL MATRIX, VOL. 7, NO. 2, JULI 1971

DAFTAR ISI JUDUL... LEMBAR PRASYARAT GELAR... LEMBAR PERNYATAAN ORISINALITAS... LEMBAR PENGESAHAN... UCAPAN TERIMAKASIH... ABSTRAK...

BAB III METODOLOGI DAN PENGUMPULAN DATA

ANALISIS KETIDAKSEIMBANGAN BEBAN TRAFO 1 GI SRONDOL TERHADAP RUGI-RUGI AKIBAT ARUS NETRAL DAN SUHU TRAFO MENGGUNAKAN ETAP

BAB III METODE PENENTUAN VECTOR GROUP

Kata kunci : Hubung Singkat 3 Fasa, Kedip Tegangan, Dynamic Voltage Restorer, Simulink Matlab.

BAB II LANDASAN TEORI

ABSTRAK. Kata kunci : Arus Transien, Ketahanan Transformator, Jenis Beban. ABSTRACT. Keywords : Transient Current, Transformer withstand, load type.

D. Relay Arus Lebih Berarah E. Koordinasi Proteksi Distribusi Tenaga Listrik BAB V PENUTUP A. KESIMPULAN B. SARAN...

Kata Kunci : Transformator Distribusi, Ketidakseimbangan Beban, Arus Netral, Rugi-rugi, Efisiensi

BAB II EKSPERIMEN 2 RANGKAIAN TIGA FASA SERTA HUBUNGAN Y (BINTANG) DAN DELTA ( )

2.2.6 Daerah Proteksi (Protective Zone) Bagian-bagian Sistem Pengaman Rele a. Jenis-jenis Rele b.

BAB V PENUTUP 5.1 Simpulan Saran DAFTAR PUSTAKA LAMPIRAN LAMPIRAN

STUDI PENGARUH KETIDAKSEIMBANGAN PEMBEBANAN TRANSFORMATOR DISTRIBUSI 20 KV PT PLN (PERSERO) CABANG PONTIANAK

ANALISIS SISTEM JARINGAN DISTRIBUSI TEGANGAN RENDAH DI KECAMATAN BENTENG KAB. KEPULAUAN SELAYAR TAHUN 2010

BAB I PENDAHULUAN. atau penurunan tegangan yang diakibatkan pusat-pusat pembangkit tenaga listrik

ANALISA RUGI-RUGI PADA GARDU 20/0.4 KV

Pengaruh Ketidakseimbangan Beban Terhadap Arus Netral dan Losses pada Trafo Distribusi

BAB I PENDAHULUAN. 1.1 Latar Belakang Masalah

BAB II LANDASAN TEORI

BAB III LANDASAN TEORI

BAB II TINJAUAN PUSTAKA. yang lain, melalui suatu gandengan magnet dan berdasarkan prinsip induksi

BAB II TINJAUAN PUSTAKA. Gambar 2.1 Tiga Bagian Utama Sistem Tenaga Listrik untuk Menuju Konsumen

Analisis Unjuk Kerja Tiga Unit Inter Bus Transformers 500 MVA 500/150/66 kv di GITET Kediri

ANALISA PROTEKSI TRANSFORMATOR 150 kv DENGAN MENGGUNAKAN RELE DIFERENSIAL DI PLTG PAYA PASIR

BAB II SALURAN DISTRIBUSI

BAB II PRINSIP DASAR TRANSFORMATOR

Analisis Kualitas Minyak Transformator Daya 25 KVA Berdasarkan Data Citra Kamera Termal dan Data Hasil Uji Gas Chromatograph

ABSTRAK. Kata Kunci : Perumahan Nuansa Kori Jimbaran, drop tegangan, JTR. vii

Monitoring Kondisi Transformator Daya Secara Online Berbasis Analisis Data Suhu, Tegangan, dan Arus pada Transformator Distribusi

STUDI PENGGUNAAN SISTEM PENDINGIN UDARA TEKAN UNTUK MENINGKATKAN EFISIENSI TRANSFORMATOR PADA BEBAN LEBIH

Rudi Salman Staf Pengajar Program Studi Teknik Elektro Universitas Negeri Medan

ANALISIS KETIDAKSEIMBANGAN BEBAN PADA JARINGAN DISTRIBUSI SEKUNDER GARDU DISTRIBUSI DS 0587 DI PT. PLN (Persero) DISTRIBUSI BALI RAYON DENPASAR

Pengujian Transformator

BACK UP SISTEM KELISTRIKAN PLTGU PT. INDONESIA POWER UBP SEMARANG DENGAN START UP DIESEL GENERATOR 6,3KV DAN 400V

Kata Kunci Pentanahan, Gardu Induk, Arus Gangguan Ketanah, Tegangan Sentuh, Tegangan Langkah, Tahanan Pengetanahan. I. PENDAHULUAN

BAB IV DATA DAN PEMBAHASAN. Pengumpulan data dilaksanakan di PT Pertamina (Persero) Refinery

ANALISA PENYETELAN RELAI GANGGUAN TANAH (GFR) PADA PENYULANG TRAFO 2 30 MVA 70/20 KV DI PT. PLN (PERSERO) GARDU INDUK BOOM BARU PALEMBANG

Transformator : peralatan listrik elektromagnetik statis yang berfungsi untuk memindahkan dan mengubah daya listrik dari suatu rangkaian listrik ke ra

STUDI SUSUT UMUR TRANSFORMATOR DISTRIBUSI 20 kv AKIBAT PEMBEBANAN LEBIH DI PT.PLN (PERSERO) KOTA PONTIANAK

Perencanaan Kebutuhan Distribusi Sekunder Perumahan RSS Manulai II

Total Loss Energy Efisiensi Transformator Kualitas Daya Listrik (Power Quality) Harmonisa

PENGARUH KETIDAKSEIMBANGAN BEBAN PADA TRAFO DISTRIBUSI DI PT. PLN (PERSERO) WS2JB AREA PALEMBANG RAYON KAYU AGUNG. LAPORAN AKHIR.

REKONDISI TRANSFORMATOR UNTUK MENGATASI MENURUNNYA KEMAMPUAN ISOLASI PADA TRANSFORMATOR DISTRIBUSI 20 kv

ANALISA KEDIP TEGANGAN PADA SISTEM DISTRIBUSI TENAGA LISTRIK 20 KV AKIBAT HUBUNG SINGKAT PADA PENYULANG PEDAN 1 KLATEN

Prosiding Seminar Nasional Aplikasi Sains & Teknologi (SNAST) 2014 ISSN: X Yogyakarta, 15 November 2014

Latihan Soal dan Quiz II

WATAK HARMONIK PADA INVERTER TIGA FASA TAK BERBEBAN

ANALISIS KEDIP TEGANGAN AKIBAT GANGGUAN HUBUNG SINGKAT PADA PENYULANG ABANG DI KARANGASEM

Jurnal Media Elektro, Vol. 1, No. 3, April 2013 ISSN

OPTIMALISASI PEMBEBANAN TRANSFORMATOR DISTRIBUSI DENGAN PENYEIMBANGAN BEBAN

PROSEDUR PENGUJIAN TAHANAN ISOLASI TRAFO

BAB III SPESIFIKASI TRANSFORMATOR DAN SWITCH GEAR

BAB III. Transformator

ANALISIS KEDIP TEGANGAN AKIBAT GANGGUAN HUBUNG SINGKAT PADA PENYULANG ABANG DI KARANGASEM

BAB II TRANSFORMATOR. elektromagnet. Pada umumnya transformator terdiri atas sebuah inti yang terbuat

PERANCANGAN PROTOTIPE REAL TIME MONITORING BEBAN TRANSFORMATOR DISTRIBUSI 20 KV BERBASIS MIKROKONTROLER

KONDISI TRANSIENT 61

Penentuan Setting Rele Arus Lebih Generator dan Rele Diferensial Transformator Unit 4 PLTA Cirata II

Perhitungan Setting Rele OCR dan GFR pada Sistem Interkoneksi Diesel Generator di Perusahaan X

III PENGUMPULAN DAN PENGOLAHAN DATA

EVALUASI DISTRIBUSI TEGANGAN RENDAH PADA GARDU DISTRIBUSI PT. PLN (PERSERO) RAYON MARIANA

BAB II TINJAUAN PUSTAKA

BAB II LANDASAN TEORI

ABSTRAK. Universitas Kristen Maranatha

LAPORAN AKHIR GANGGUAN OVERLOAD PADA GARDU DISTRBUSI ASRAMA KIWAL

Transkripsi:

PENGARUH BEBAN TIDAK SEIMBANG TERHADAP EFISIENSI TRANSFORMATOR TIGA FASA PADA HUBUNGAN OPEN-DELTA Sumantri, Titiek Suheta 1, dan Joao Filomeno Dos Santos Teknik-Elektro ITATS 1, Jl. Arief Rahman Hakim No. 100 Surabaya Email 1 : sondysuheta@yahoo.com ABSTRACT Dd0 transformer with a capacity of 2000 KVA mensupplay power distribution system in Timor Leste. But as often happens more load on the transformer and the limitations of the service, the result is often damaged transformer. Usually the damage occurs on one phase at a transformer, so it will cause a total blackout. This is due to the limited stock available transformer there is very limited, so to overcome this, then the transformer in circuit Open - Delta in order to keep functioning. Transformer is connected Open - Delta then the power is supplied by only 66.7%, so the settings are in the division of the burden on consumers, by way of rolling blackouts while waiting for the procurement of a new transformer. Keywords: Open - Delta, Dd0 transformers, Power. ABSTRAK Trafo Dd0 dengan kapasitas 2000 KVA mensupplai sistem distribusi daya listrik di Timor Leste. Namun karena sering kali terjadi beban lebih pada trafo dan keterbatasan pelayanannya,maka mengakibatkan trafo sering rusak. Biasanya kerusakan terjadi pada salah satu fasa pada trafo, sehingga akan menyebabkan terjadinya pemadaman total. Hal ini disebabkan karena keterbatasan stok trafo yang tersedia disana yang sangat terbatas, sehingga untuk mengatasi hal tersebut, maka pada trafo di hubung Open Delta agar tetap berfungsi. Trafo terhubung Open Delta maka daya yang disuplai hanya sebesar 66,7%, sehingga dilakukan pengaturan dalam pembagian beban pada konsumen, yaitu dengan cara pemadaman bergilir sambil menunggu pengadaan trafo baru. Kata kunci: Open Delta, Trafo Dd0, Daya. PENDAHULUAN Sumber energi listrik yang ada di PLN TIMOR LESTE merupakan pembangkit Listrik Tenaga Diesel (PLTD) dengan trafo distribusi 2000 KVA. Permasalahan yang sering terjadi di TIMOR LESTE adalah dampak dari gangguan alam (sambaran petir) yang sering terjadi, sehingga menimbulkan lonjakan tegangan yang sangat tinggi pada sistem, akibatnya akan terjadi kerusakan pada bagian dari sistem distribusi tenaga listrik. Dan juga kurang kesadaran dari masyarakat yang tidak bertanggung jawab dengan melakukan penyambungan listrik melebihi kapasitas trafo yang terpasang, sehingga daya listrik yang dipakai tidak dapat dikontrol secara maximal dan juga tidak adanya keseimbangan beban antara fasa di sistem distribusi tenaga listrik, dimana salah satu fasanya terputus, sehingga akan menyebabkan pemadaman total. Untuk mengantisipasi hal tersebut maka trafo dihubung Open Delta agar trafo tetap bekerja walaupun tidak 100 %,namun demikian trafo tetap mensuplay energi listrik walaupun harus dilakukan pemadaman bergilir.

105 Jurnal IPTEK Vol 17 No.2 Desember 201 TINJAUAN PUSTAKA Tiga transformator berfasa satu dapat dihubungkan untuk membentuk bank- fasa (susunan fasa = bank phase) dengan satu cara maupun dengan berbagai cara menghubungkan belitan transformator. Pada tiga buah transformator satu fasa yang dipakai sebagai transformator tiga fasa setiap kumparan primer dari satu transformator dijodohkan dengan kumparan sekundernya. Hendaknya dicatat bahwa pada transformator tiga fasa ini besar tegangan antara fasa (V L-L ) dan daya transformator (kva) tidak tergantung dari hubungan belitannya,namun untuk tegangan fasa ke netral (V L-N ) serta arus dari masing-masing transformator tergantung pada hubungan belitannya [1]. Ada beberapa hubungan belitan yang terdapat pada transformator tiga fasa ini. Hubungan antara Δ-Y biasanya digunakan untuk menurunkan tegangan, dari tegangan tinggi ke tegangan menengah atau tegangan rendah. Satu diantara alasannya karena dengan menggunakan hubungan belitan ini untuk membumikan dari sisi tegangan tinggi telah tersedia saluran netral. Dapat dibuktikan bahwa hubungan belitan ini adalah hubungan yang paling banyak digunakan dilapangan[2]. Sebaliknya hubungan Y-Δ biasa digunakan untuk menaikan tegangan dari tegangan rendah ke tegangan menengah, atau dari tegangan menengah ke tegangan tinggi. hal ini juga bertujuan sama, agar pada sisi tegangan tingginya apabila dikebumikan telah tersedia saluran netral [],[4]. Hubungan delta - delta adalah satu jenis hubungan bilitan yang istimewa keuntungannya yaitu salah satu kaki transformator dapat dipindahkan apabila terjadi kerusakan atau apabila diadakan perawatan, sedangkan dua fasa yang tertinggal dapat terus beroperasi sebagai bank- fasa dengan ranting kva yang turun sampai dengan 66,7% dari bank yang asli [5]. METODE Bahan Penelitian Trafo 2000 KVA dengan frekuensi 50 Hz, phase, high voltage 20.000 V, low voltage 400 V, Current HV 57 A, Current LV 2886 A, Impedance 7%, Type of cooling ONAN, Vektor group Dd0 dan temp oil/winding 60/65 C 0. Alat Penelitian Alat yang digunakan Digital multimeter conzerv untuk melihat perubahan beban pada trafo. Lokasi Penelitian Lokasi adalah PLN nasional Timor Leste, Dili. Metode Metode yang digunakan dalam penelitian ini adalah dengan menggunakan rumus trafo hubungan open delta. HASIL DAN PEMBAHASAN Pada beban normal besar daya tiap fasa (R,S,T) [2] : P = V L x I P x Cos θ (1)

Sumantri, T. Suheta & J.F.D. Santos. Pengaruh Beban Tidak Seimbang... 106 I P = P x VL x Cos 0 (2) = 2000x10 x220x0.8 I P = 787,8A Daya per fase untuk beban normal besarnya sama yaitu : Fase R,S,T: P = I P x V P x Cos θ () = 787.8 x 220 x 0.8 = 666666.7 W = 666.7 KW Jadi daya total untuk fasa dalam keadan normal adalah : 2000 KW Namun pada keadan beban tidak seimbang dan over load, trafo akan break down dan membuat salah satu fasa dari trafo tersebut rusak, sehingga trafo dihubung Open Delta seperti Gambar 1 dibawah ini. HUBUNGAN OPEN - DELTA U R V 220 V 440 V S W 220 V T 0 N Gambar 1. Hubungan Open Delta [6]. Daya yang dihasilkan perfase dalam keadaan Open Delta adalah sebagai berikut: besar daya Fase R = Fase S, P = I P x V P x Cos θ = 787.8 x 220 x 0.8 = 666666.7 W = 666.7 KW sedangkan daya pada Fase T : P = I P x V P x Cos θ = 787.8 x 0 x 0.8 = 0 V

107 Jurnal IPTEK Vol 17 No.2 Desember 201 Jadi daya total dalam keadan hubungan Open Delta : 666666.7 + 666666.7 + 0 = 1.4W = 1.4 KW Efisiensi trafo dalam hubungan Open - Delta [6] : η = Pout x 100% (4) P in 1.4 = 2000 = 66.7% x 100% Jadi daya trafo yang dihasilkan pada hubungan Open Delta adalah sebesar 66.7% dari daya total trafo tersebut, sehingga penyeimbangan beban sangat diperlukakan untuk menjaga trafo tetap bekerja. Gambar 2. Hubungan daya terhadap efisiensi [6]. Pada grafik hubungan daya terhadap efisiensi ditunjukkan bahwa,dengan kapasitas trafo sebesar 2000 kva didapatkan efisiensi trafo dalam hubungan open-delta sebesar 66.7%.

Sumantri, T. Suheta & J.F.D. Santos. Pengaruh Beban Tidak Seimbang... 108 KESIMPULAN Berdasarkan pembahasan diatas maka dapat disimpulkan bahwa : 1. Jadi dengan sering terjadinya pembebanan lebih dan tidak seimbang pada trafo di Timor Leste maka akan menyebabkan trafo mengalami kerusakan. Karena persediaan trafo di sana terbatas maka untuk mengatasi pelayanan energi listrik di Timor Leste maka pihak PLN melakukan hubugan Open Delta pada trafo yang mengalami kerusakan tersebut. 2. Jika kondisi trafo yang terhubung Open Delta, maka efisiensi daya yang dihasilkan akan mengalami penurunan sebesar 66.7% dari daya total trafo. Jadi dengan besar daya tersebut, maka pelayanan energi listrik pada konsumen tidak maksimal dalam hal ini pihak PLN akan melakukan pembagian atau pengaturan beban dengan cara pemadaman bergilir. Dengan cara seperti itu diharapkan dapat mengatasi masalah pemadaman total sambil menunggu pengadaan trafo baru. DAFTAR PUSTAKA [1]. Djulil, A. & Fali, O. 200. Kekuatan dan rugi-rugi dielektrik minyak transformator yang dipengaruhi oleh kontaminasi air dan kenaikan temperatur, Seminar Nasional Teknik Elektro. [2]. Hutauruk, T.S. 1987. Pengetanahan Netral Sistem Tenaga dan Pentanahan Peralatan, Jakarta, Erlangga. []. IEC. 1976. Power Transformer, IEC 76/1976. [4]. Kadir, A. 1981. Transformator, Edisi 2, Jakarta, Universitas Indonesia. [5]. Stevenson & Wiliam, D. 1996. Analisa Sistem Tenaga Listrik, edisi 4, Jakarta, Erlangga. [6]. Soemarwanto. 1988. Teknik Tenaga Listrik, Edisi 1, Malang, Universitas Brawijaya.