PENGARUH BEBAN TIDAK SEIMBANG TERHADAP EFISIENSI TRANSFORMATOR TIGA FASA PADA HUBUNGAN OPEN-DELTA
|
|
- Hartanti Salim
- 9 tahun lalu
- Tontonan:
Transkripsi
1 PENGARUH BEBAN TIDAK SEIMBANG TERHADAP EFISIENSI TRANSFORMATOR TIGA FASA PADA HUBUNGAN OPEN-DELTA Sumantri, Titiek Suheta 1, dan Joao Filomeno Dos Santos Teknik-Elektro ITATS 1, Jl. Arief Rahman Hakim No. 100 Surabaya 1 : sondysuheta@yahoo.com ABSTRACT Dd0 transformer with a capacity of 2000 KVA mensupplay power distribution system in Timor Leste. But as often happens more load on the transformer and the limitations of the service, the result is often damaged transformer. Usually the damage occurs on one phase at a transformer, so it will cause a total blackout. This is due to the limited stock available transformer there is very limited, so to overcome this, then the transformer in circuit Open - Delta in order to keep functioning. Transformer is connected Open - Delta then the power is supplied by only 66.7%, so the settings are in the division of the burden on consumers, by way of rolling blackouts while waiting for the procurement of a new transformer. Keywords: Open - Delta, Dd0 transformers, Power. ABSTRAK Trafo Dd0 dengan kapasitas 2000 KVA mensupplai sistem distribusi daya listrik di Timor Leste. Namun karena sering kali terjadi beban lebih pada trafo dan keterbatasan pelayanannya,maka mengakibatkan trafo sering rusak. Biasanya kerusakan terjadi pada salah satu fasa pada trafo, sehingga akan menyebabkan terjadinya pemadaman total. Hal ini disebabkan karena keterbatasan stok trafo yang tersedia disana yang sangat terbatas, sehingga untuk mengatasi hal tersebut, maka pada trafo di hubung Open Delta agar tetap berfungsi. Trafo terhubung Open Delta maka daya yang disuplai hanya sebesar 66,7%, sehingga dilakukan pengaturan dalam pembagian beban pada konsumen, yaitu dengan cara pemadaman bergilir sambil menunggu pengadaan trafo baru. Kata kunci: Open Delta, Trafo Dd0, Daya. PENDAHULUAN Sumber energi listrik yang ada di PLN TIMOR LESTE merupakan pembangkit Listrik Tenaga Diesel (PLTD) dengan trafo distribusi 2000 KVA. Permasalahan yang sering terjadi di TIMOR LESTE adalah dampak dari gangguan alam (sambaran petir) yang sering terjadi, sehingga menimbulkan lonjakan tegangan yang sangat tinggi pada sistem, akibatnya akan terjadi kerusakan pada bagian dari sistem distribusi tenaga listrik. Dan juga kurang kesadaran dari masyarakat yang tidak bertanggung jawab dengan melakukan penyambungan listrik melebihi kapasitas trafo yang terpasang, sehingga daya listrik yang dipakai tidak dapat dikontrol secara maximal dan juga tidak adanya keseimbangan beban antara fasa di sistem distribusi tenaga listrik, dimana salah satu fasanya terputus, sehingga akan menyebabkan pemadaman total. Untuk mengantisipasi hal tersebut maka trafo dihubung Open Delta agar trafo tetap bekerja walaupun tidak 100 %,namun demikian trafo tetap mensuplay energi listrik walaupun harus dilakukan pemadaman bergilir.
2 105 Jurnal IPTEK Vol 17 No.2 Desember 201 TINJAUAN PUSTAKA Tiga transformator berfasa satu dapat dihubungkan untuk membentuk bank- fasa (susunan fasa = bank phase) dengan satu cara maupun dengan berbagai cara menghubungkan belitan transformator. Pada tiga buah transformator satu fasa yang dipakai sebagai transformator tiga fasa setiap kumparan primer dari satu transformator dijodohkan dengan kumparan sekundernya. Hendaknya dicatat bahwa pada transformator tiga fasa ini besar tegangan antara fasa (V L-L ) dan daya transformator (kva) tidak tergantung dari hubungan belitannya,namun untuk tegangan fasa ke netral (V L-N ) serta arus dari masing-masing transformator tergantung pada hubungan belitannya [1]. Ada beberapa hubungan belitan yang terdapat pada transformator tiga fasa ini. Hubungan antara Δ-Y biasanya digunakan untuk menurunkan tegangan, dari tegangan tinggi ke tegangan menengah atau tegangan rendah. Satu diantara alasannya karena dengan menggunakan hubungan belitan ini untuk membumikan dari sisi tegangan tinggi telah tersedia saluran netral. Dapat dibuktikan bahwa hubungan belitan ini adalah hubungan yang paling banyak digunakan dilapangan[2]. Sebaliknya hubungan Y-Δ biasa digunakan untuk menaikan tegangan dari tegangan rendah ke tegangan menengah, atau dari tegangan menengah ke tegangan tinggi. hal ini juga bertujuan sama, agar pada sisi tegangan tingginya apabila dikebumikan telah tersedia saluran netral [],[4]. Hubungan delta - delta adalah satu jenis hubungan bilitan yang istimewa keuntungannya yaitu salah satu kaki transformator dapat dipindahkan apabila terjadi kerusakan atau apabila diadakan perawatan, sedangkan dua fasa yang tertinggal dapat terus beroperasi sebagai bank- fasa dengan ranting kva yang turun sampai dengan 66,7% dari bank yang asli [5]. METODE Bahan Penelitian Trafo 2000 KVA dengan frekuensi 50 Hz, phase, high voltage V, low voltage 400 V, Current HV 57 A, Current LV 2886 A, Impedance 7%, Type of cooling ONAN, Vektor group Dd0 dan temp oil/winding 60/65 C 0. Alat Penelitian Alat yang digunakan Digital multimeter conzerv untuk melihat perubahan beban pada trafo. Lokasi Penelitian Lokasi adalah PLN nasional Timor Leste, Dili. Metode Metode yang digunakan dalam penelitian ini adalah dengan menggunakan rumus trafo hubungan open delta. HASIL DAN PEMBAHASAN Pada beban normal besar daya tiap fasa (R,S,T) [2] : P = V L x I P x Cos θ (1)
3 Sumantri, T. Suheta & J.F.D. Santos. Pengaruh Beban Tidak Seimbang I P = P x VL x Cos 0 (2) = 2000x10 x220x0.8 I P = 787,8A Daya per fase untuk beban normal besarnya sama yaitu : Fase R,S,T: P = I P x V P x Cos θ () = x 220 x 0.8 = W = KW Jadi daya total untuk fasa dalam keadan normal adalah : 2000 KW Namun pada keadan beban tidak seimbang dan over load, trafo akan break down dan membuat salah satu fasa dari trafo tersebut rusak, sehingga trafo dihubung Open Delta seperti Gambar 1 dibawah ini. HUBUNGAN OPEN - DELTA U R V 220 V 440 V S W 220 V T 0 N Gambar 1. Hubungan Open Delta [6]. Daya yang dihasilkan perfase dalam keadaan Open Delta adalah sebagai berikut: besar daya Fase R = Fase S, P = I P x V P x Cos θ = x 220 x 0.8 = W = KW sedangkan daya pada Fase T : P = I P x V P x Cos θ = x 0 x 0.8 = 0 V
4 107 Jurnal IPTEK Vol 17 No.2 Desember 201 Jadi daya total dalam keadan hubungan Open Delta : = 1.4W = 1.4 KW Efisiensi trafo dalam hubungan Open - Delta [6] : η = Pout x 100% (4) P in 1.4 = 2000 = 66.7% x 100% Jadi daya trafo yang dihasilkan pada hubungan Open Delta adalah sebesar 66.7% dari daya total trafo tersebut, sehingga penyeimbangan beban sangat diperlukakan untuk menjaga trafo tetap bekerja. Gambar 2. Hubungan daya terhadap efisiensi [6]. Pada grafik hubungan daya terhadap efisiensi ditunjukkan bahwa,dengan kapasitas trafo sebesar 2000 kva didapatkan efisiensi trafo dalam hubungan open-delta sebesar 66.7%.
5 Sumantri, T. Suheta & J.F.D. Santos. Pengaruh Beban Tidak Seimbang KESIMPULAN Berdasarkan pembahasan diatas maka dapat disimpulkan bahwa : 1. Jadi dengan sering terjadinya pembebanan lebih dan tidak seimbang pada trafo di Timor Leste maka akan menyebabkan trafo mengalami kerusakan. Karena persediaan trafo di sana terbatas maka untuk mengatasi pelayanan energi listrik di Timor Leste maka pihak PLN melakukan hubugan Open Delta pada trafo yang mengalami kerusakan tersebut. 2. Jika kondisi trafo yang terhubung Open Delta, maka efisiensi daya yang dihasilkan akan mengalami penurunan sebesar 66.7% dari daya total trafo. Jadi dengan besar daya tersebut, maka pelayanan energi listrik pada konsumen tidak maksimal dalam hal ini pihak PLN akan melakukan pembagian atau pengaturan beban dengan cara pemadaman bergilir. Dengan cara seperti itu diharapkan dapat mengatasi masalah pemadaman total sambil menunggu pengadaan trafo baru. DAFTAR PUSTAKA [1]. Djulil, A. & Fali, O Kekuatan dan rugi-rugi dielektrik minyak transformator yang dipengaruhi oleh kontaminasi air dan kenaikan temperatur, Seminar Nasional Teknik Elektro. [2]. Hutauruk, T.S Pengetanahan Netral Sistem Tenaga dan Pentanahan Peralatan, Jakarta, Erlangga. []. IEC Power Transformer, IEC 76/1976. [4]. Kadir, A Transformator, Edisi 2, Jakarta, Universitas Indonesia. [5]. Stevenson & Wiliam, D Analisa Sistem Tenaga Listrik, edisi 4, Jakarta, Erlangga. [6]. Soemarwanto Teknik Tenaga Listrik, Edisi 1, Malang, Universitas Brawijaya.
PENGARUH HARMONISA PADA GARDU TRAFO TIANG DAYA 200 KVA DI PT PLN (Persero) APJ SURABAYA UTARA
PENGARUH HARMONISA PADA GARDU TRAFO TIANG DAYA 200 KVA DI PT PLN (Persero) APJ SURABAYA UTARA Titiek Suheta Teknik Elektro, Fakultas Teknologi Industri, Institut Teknologi Adhi Tama Surabaya sondysuheta@yahoo.com
Lebih terperinciPENGARUH HARMONISA PADA GARDU TRAFO TIANG DAYA 200 KVA DI PT PLN (Persero) APJ SURABAYA UTARA
PENGARUH HARMONISA PADA GARDU TRAFO TIANG DAYA 200 KVA DI PT PLN (Persero) APJ SURABAYA UTARA Titiek Suheta Teknik Elektro, Fakultas Teknologi Industri, Institut Teknologi Adhi Tama Surabaya sondysuheta@yahoo.com
Lebih terperinciAKIBAT KETIDAKSEIMBANGAN BEBAN TERHADAP ARUS NETRAL DAN LOSSES PADA TRANSFORMATOR DISTRIBUSI
AKIBAT KETIDAKEIMBANGAN BEBAN TERHADAP ARU NETRAL DAN LOE PADA TRANFORMATOR DITRIBUI Moh. Dahlan 1 email : dahlan_kds@yahoo.com surat_dahlan@yahoo.com IN : 1979-6870 ABTRAK Ketidakseimbangan beban pada
Lebih terperinciPENGARUH KETIDAKSEIMBANGAN BEBAN TRANSFORMATOR KERING BHT02 RSG GA SIWABESSY TERHADAP ARUS NETRAL DAN RUGI-RUGI
PENGARUH KETIDAKSEIMBANGAN BEBAN TRANSFORMATOR KERING BHT02 RSG GA SIWABESSY TERHADAP ARUS NETRAL DAN RUGI-RUGI Koes Indrakoesoema, Yayan Andryanto, M Taufiq Pusat Reaktor Serba Guna GA Siwabessy, Puspiptek,
Lebih terperinciDosen Pembimbing II. Ir. Sjamsjul Anam, MT
ANALISIS KUALITAS DAYA DAN CARA PENINGKATANNYA PADA JARINGAN DISTRIBUSI TEGANGAN MENENGAH DAN RENDAH EDTL TIMOR LESTE DI SISTEM PLTD KABUPATEN BAUCAU REINALDO GUTERRES DA CRUZ - 2208100627 Bidang Studi
Lebih terperinciBAB I PENDAHULUAN. yang dipakai adalah tegangan dan arus bolak-balik ( AC). Sedangkan tegangan dan arus
BAB I PENDAHULUAN I.1. LATAR BELAKANG MASALAH Dalam istilah elektro, transformator adalah suatu alat yang dapat mengubah energi listrik menjadi energi listrik dengan frekuensi yang sama. Perubahan energi
Lebih terperinciSTUDI PENGARUH HARMONISA PADA GARDU TRAFO TIANG DAYA 200 KVA DI PT PLN (Persero) APJ SURABAYA UTARA
STUDI PENGARUH HARMONISA PADA GARDU TRAFO TIANG DAYA 200 KVA DI PT PLN (Persero) APJ SURABAYA UTARA Titiek Suheta,Abdullah Farid Jurusan Teknik Elektro,Fakultas Teknologi Industri Institut Teknologi Adhi
Lebih terperinciPENGARUH KETIDAKSEIMBANGAN BEBAN TERHADAP ARUS NETRAL DAN LOSSES PADA TRAFO DISTRIBUSI
PENGARUH KETDAKEMBANGAN BEBAN TERHADAP ARU NETRAL DAN LOE PADA TRAFO DTRBU Arief Budi Laksono 1 1) Dosen Fakultas Teknik Prodi Elektro Universitas slam Lamongan Abstrak Ketidakseimbangan beban pada suatu
Lebih terperinciBAB IV PEMBAHASAN KONSTRUKSI CORE PADA TRANSFORMATOR. DISTRIBUSI 20/0,4 kv, 315 kva. (Aplikasi Di PT Trafoindo Prima Perkasa)
BAB IV PEMBAHASAN KONSTRUKSI CORE PADA TRANSFORMATOR DISTRIBUSI 20/0,4 kv, 315 kva (Aplikasi Di PT Trafoindo Prima Perkasa) 4.1. Penentuan dimensi core Transformator Distribusi 20 / 0,4 kv dengan Konstruksi
Lebih terperinciDAFTAR ISI... DAFTAR ISI DAFTAR GAMBAR.. DAFTAR TABEL... DAFTAR LAMPIRAN...
DAFTAR ISI LEMBAR JUDUL LEMBAR PERNYATAAN ORISINALITAS.. LEMBAR PRASYARAT GELAR SARJANA... LEMBAR PENGESAHAN... KATA PENGANTAR... ABSTRAK.. ABSTRACT... DAFTAR ISI... DAFTAR GAMBAR.. DAFTAR TABEL... DAFTAR
Lebih terperinciANALISA BERBAGAI HUBUNGAN BELITAN TRANSFORMATOR 3 PHASA DALAM KEADAAN BEBAN LEBIH (APLIKASI PADA LABORATORIUM KONVERSI ENERGI LISTRIK FT.
ANALISA BERBAGAI HUBUNGAN BELITAN TRANSFORMATOR 3 PHASA DALAM KEADAAN BEBAN LEBIH (APLIKASI PADA LABORATORIUM KONVERSI ENERGI LISTRIK FT. USU) Zul Fahmi Dhuha (1), Syamsul Amien (2) Konsentrasi Teknik
Lebih terperinciJurnal Teknologi Elektro, Universitas Mercu Buana ISSN: ANALISIS VECTOR GROUP PADA HUBUNGAN PARALEL TRANSFORMATOR UNIT GARDU BERGERAK
ANALISIS VECTOR GROUP PADA HUBUNGAN PARALEL TRANSFORMATOR UNIT GARDU BERGERAK Budi Yanto Husodo ¹, Firmansyah² Program Studi Teknik Elektro, Fakultas Teknik Universitas Mercu Buana, Jakarta, Indonesia
Lebih terperinciOPTIMASI PENYEIMBANGAN BEBAN PADA TRAFO DISTRIBUSI TERHADAP SUSUT ENERGI (APLIKASI FEEDER SIKAKAP)
OPTIMASI PENYEIMBANGAN BEBAN PADA TRAFO DISTRIBUSI TERHADAP SUSUT ENERGI (APLIKASI FEEDER SIKAKAP) Oleh : Antonov 1), Doni Aprinaldo 2) 1) Studi Teknik Elektro Fakultas Teknologi Industri Institut Teknologi
Lebih terperinciABSTRAK Kata Kunci :
ABSTRAK Transformator 3 pada GI Pesanggaran mendapat penambahan 4 blok pembangkit dengan daya maksimum sebesar 60 MW daya dari keempat blok pembangkit tersebut digunakan untuk mensuplai beban penyulang
Lebih terperinciESTIMASI UMUR PAKAI DAN RUGI DAYA TRANSFORMATOR. The Estimated Age of Use and Loss Power Transformer
Techno, ISSN 1410-8607 Volume 15 No. 2, Oktober 2014 Hal. 50 55 ESTIMASI UMUR PAKAI DAN RUGI DAYA TRANSFORMATOR The Estimated Age of Use and Loss Power Transformer Winarso Program Studi Teknik Elektro,
Lebih terperinciANALISIS KINERJA TRANSFORMATOR TIGA BELITAN SEBAGAI GENERATOR STEP-UP TRANSFORMER
Harrij Mukti K, Analisis Kinerja Transformator, Hal 71-82 ANALISIS KINERJA TRANSFORMATOR TIGA BELITAN SEBAGAI GENERATOR STEP-UP TRANSFORMER Harrij Mukti K 6 Pada pusat pembangkit tenaga listrik, generator
Lebih terperinciANALISIS GANGGUAN HUBUNG SINGKAT TRAFO TENAGA 60 MVA SHORT CIRCUIT ANALYSIS OF POWER TRANSFORMER 60 MVA
Techno, ISSN 1410-8607 Volume 16 No. 2, Oktober 2015 Hal. 125 130 ANALISIS GANGGUAN HUBUNG SINGKAT TRAFO TENAGA 60 MVA SHORT CIRCUIT ANALYSIS OF POWER TRANSFORMER 60 MVA Eka Purwito dan Fitrizawati* Program
Lebih terperinciANALISIS TEORITIS PENEMPATAN TRANSFORMATOR DISTRIBUSI MENURUT JATUH TEGANGAN DI PENYULANG BAGONG PADA GARDU INDUK NGAGEL
Analisis Teoritis Penempatan Transformator Distribusi Menurut Jatuh Tegangan Di Penyulang Bagong ANALISIS TEORITIS PENEMPATAN TRANSFORMATOR DISTRIBUSI MENURUT JATUH TEGANGAN DI PENYULANG BAGONG PADA GARDU
Lebih terperinciANALISA PENGARUH BEBAN TIDAK SEIMBANG TERHADAP RUGI DAYA LISTRIK PADA JARINGAN DISTRIBUSI SEKUNDER HASBULAH
ANALISA PENGARUH BEBAN TIDAK SEIMBANG TERHADAP RUGI DAYA LISTRIK PADA JARINGAN DISTRIBUSI SEKUNDER HASBULAH Jurusan Teknik Elektro, Program Studi Teknik Listrik Politeknik Negeri Sriwijaya Email: hasbulahhasan@gmail.com
Lebih terperinciSINGUDA ENSIKOM VOL. 7 NO. 3/ Juni 2014
ANALISIS PERBANDINGAN PENGARUH BEBAN SEIMBANG DAN TIDAK SEIMBANG TERHADAP REGULASI TEGANGAN DAN EFISIENSI PADA BERBAGAI HUBUNGAN BELITAN TRANSFORMATOR TIGA FASA Yuliana Tanjung [1], A. Rachman Hasibuan
Lebih terperinciBAB III PERANCANGAN ALAT
BAB III PERANCANGAN ALAT 3.1 Flow Chart Pengujian Deskripsi sistem rancang rangkaian untuk pengujian transformator ini digambarkan dalam flowchart sebagai berikut : Mulai Peralatan Uji Merakit Peralatan
Lebih terperinciEVALUASI SISTEM PENTANAHAN TRANSFORMATOR DAYA 60 MVA PLTGU INDRALAYA
Jurnal Desiminasi Teknologi, Volume 2, No. 1, Januari 2014 EVALUASI SISTEM PENTANAHAN TRANSFORMATOR DAYA 60 MVA PLTGU INDRALAYA Oleh : Manogu Simangunsong [1], Yuslan Basir [2], Helmi [3], Hazairin Samaulah
Lebih terperinciANALISIS JATUH TEGANGAN DAN RUGI DAYA PADA JARINGAN TEGANGAN RENDAH MENGGUNAKAN SOFTWARE ETAP
ANALISIS JATUH TEGANGAN DAN RUGI DAYA PADA JARINGAN TEGANGAN RENDAH MENGGUNAKAN SOFTWARE ETAP 12.6.0 Fani Istiana Handayani * ), Yuningtyastuti, and Agung Nugroho Jurusan Teknik Elektro, Fakultas Teknik,
Lebih terperinciStudi Koordinasi Proteksi Sistem Kelistrikan di Project Pakistan Deep Water Container Port
PROCEEDING TUGAS AKHIR, (2014) 1-6 1 Studi Koordinasi Proteksi Sistem Kelistrikan di Project Pakistan Deep Water Container Port Adam Anas Makruf, Margo Pujiantara 1), Feby Agung Pamuji 2) Jurusan Teknik
Lebih terperinciPENGARUH ARUS NETRAL TERHADAP RUGI-RUGI BEBAN PADA TRANSFORMATOR DISTRIBUSI PLN RAYON JOHOR MEDAN
PENGARUH ARUS NETRAL TERHADAP RUGI-RUGI BEBAN PADA TRANSFORMATOR DISTRIBUSI PLN RAYON JOHOR MEDAN Rendy F Sibarani, Ir. Syamsul Amien, MS Konsentrasi Teknik Energi Listrik, Departemen Teknik Elektro Fakultas
Lebih terperinciDAFTAR ISI SAMPUL DALAM...
DAFTAR ISI SAMPUL DALAM... i PRASYARAT GELAR... ii LEMBAR PERNYATAAN ORISINALITAS... iii LEMBAR PENGESAHAN... iv UCAPAN TERIMAKASIH... v ABSTRAK... vii ABSTRACT... viii DAFTAR ISI... ix DAFTAR GAMBAR...
Lebih terperinciBAB II TINJAUAN PUSTAKA
BAB II TINJAUAN PUSTAKA 2.1.Transformator distribusi Transformator distribusi yang sering digunakan adalah jenis transformator step up down 20/0,4 kv dengan tegangan fasa sistem JTR adalah 380 Volt karena
Lebih terperinciBAB II DASAR TEORI. melalui gandengan magnet dan prinsip induksi elektromagnetik [1].
BAB II DASAR TEORI 2.1 Umum Transformator merupakan suatu alat listrik statis yang dapat memindahkan dan mengubah energi listrik dari satu rangkaian listrik ke rangkaian listrik lainnya melalui gandengan
Lebih terperinciMesin Arus Bolak Balik
Teknik Elektro-ITS Surabaya share.its.ac.id 1 Mesin Arus Bolak balik TE091403 Institut Teknologi Sepuluh Nopember August, 2012 Teknik Elektro-ITS Surabaya share.its.ac.id ACARA PERKULIAHAN DAN KOMPETENSI
Lebih terperinciBAB II LANDASAN TEORI ANALISA HUBUNG SINGKAT DAN MOTOR STARTING
BAB II LANDASAN TEORI ANALISA HUBUNG SINGKAT DAN MOTOR STARTING 2.1 Jenis Gangguan Hubung Singkat Ada beberapa jenis gangguan hubung singkat dalam sistem tenaga listrik antara lain hubung singkat 3 phasa,
Lebih terperinciRANCANG BANGUN KAPASITOR BANK UNTUK EFISIENSI DAYA LISTRIK PADA INDUSTRI KECIL
RANCANG BANGUN KAPASITOR BANK UNTUK EFISIENSI DAYA LISTRIK PADA INDUSTRI KECIL Jurusan Teknik Elektro, Fakultas Teknik, Universitas Negeri Semarang Email: henryananta@gmail.com Abstrak. Penelitian ini
Lebih terperinciPEMELIHARAAN TRANSFORMATOR DISTRIBUSI 20 KV / 220 V di PLN AREA LUBUK PAKAM
PEMELIHARAAN TRANSFORMATOR DISTRIBUSI 20 KV / 220 V di PLN AREA LUBUK PAKAM LAPORAN TUGAS AKHIR Diajukan untuk Memenuhi Sebagian Persyaratan dalam Menyelesaikan Program Pendidikan Diploma III PROGRAM STUDI
Lebih terperinciANALISIS JATUH TEGANGAN DAN RUGI DAYA PADA JARINGAN TEGANGAN RENDAH MENGGUNAKAN SOFTWARE ETAP
ANALISIS JATUH TEGANGAN DAN RUGI DAYA PADA JARINGAN TEGANGAN RENDAH MENGGUNAKAN SOFTWARE ETAP 12.6.0 Fani Istiana Handayani * ), Yuningtyastuti, Agung Nugroho Jurusan Teknik Elektro, Fakultas Teknik, Universitas
Lebih terperinciBAB II JARINGAN DISTRIBUSI TENAGA LISTRIK. karena terdiri atas komponen peralatan atau mesin listrik seperti generator,
BAB II JARINGAN DISTRIBUSI TENAGA LISTRIK II.1. Sistem Tenaga Listrik Struktur tenaga listrik atau sistem tenaga listrik sangat besar dan kompleks karena terdiri atas komponen peralatan atau mesin listrik
Lebih terperinci47 JURNAL MATRIX, VOL. 7, NO. 2, JULI 1971
47 JURNAL MATRIX, VOL. 7, NO. 2, JULI 1971 ANALISIS PENGARUH REKONFIGURASI GROUNDING KABEL POWER 20 kv TERHADAP ERROR RATIO CURRENT TRANSFORMERS PELANGGAN TEGANGAN MENENGAH DI HOTEL GOLDEN TULIP SEMINYAK
Lebih terperinciDAFTAR ISI JUDUL... LEMBAR PRASYARAT GELAR... LEMBAR PERNYATAAN ORISINALITAS... LEMBAR PENGESAHAN... UCAPAN TERIMAKASIH... ABSTRAK...
DAFTAR ISI JUDUL... LEMBAR PRASYARAT GELAR... LEMBAR PERNYATAAN ORISINALITAS... LEMBAR PENGESAHAN... UCAPAN TERIMAKASIH... ABSTRAK... ABSRACT... DAFTAR ISI... DAFTAR TABEL... DAFTAR GAMBAR... DAFTAR LAMPIRAN...
Lebih terperinciBAB III METODOLOGI DAN PENGUMPULAN DATA
BAB III METODOLOGI DAN PENGUMPULAN DATA 3.1 Bendungan Gambar 3.1 Ilustrasi PLTMH cinta mekar (sumber,ibeka, 2007) PLTMH Cinta Mekar memanfaatkan aliran air irigasi dari sungai Ciasem yang berhulu di Gunung
Lebih terperinciANALISIS KETIDAKSEIMBANGAN BEBAN TRAFO 1 GI SRONDOL TERHADAP RUGI-RUGI AKIBAT ARUS NETRAL DAN SUHU TRAFO MENGGUNAKAN ETAP
ANALISIS KETIDAKSEIMBANGAN BEBAN TRAFO 1 GI SRONDOL TERHADAP RUGI-RUGI AKIBAT ARUS NETRAL DAN SUHU TRAFO MENGGUNAKAN ETAP 12.6.0 Dennis Satria Wahyu Jayabadi *), Bambang Winardi, and Mochammad Facta Departemen
Lebih terperinciBAB III METODE PENENTUAN VECTOR GROUP
BAB III METODE PENENTUAN VECTOR GROUP 3.1 Pengujian Vector Group Transformator Salah satu pengujian yang dilakukan pada transformator adalah pengujian vector group transformator. Pengujian vector group
Lebih terperinciKata kunci : Hubung Singkat 3 Fasa, Kedip Tegangan, Dynamic Voltage Restorer, Simulink Matlab.
ABSTRAK Banyaknya gangguan yang timbul dalam pendistribusian energi listrik dapat mengakibatkan menurunnya kualitas daya listrik. Salah satu gangguan yang timbul dalam pendistribusian tenaga listrik yaitu
Lebih terperinciBAB II LANDASAN TEORI
BAB II LANDASAN TEORI 2.1. Sistem Distribusi Tenaga Listrik Sistem tenaga listrik adalah kumpulan atau gabungan dari komponenkomponen atau alat-alat listrik seperti generator, transformator, saluran transmisi,
Lebih terperinciABSTRAK. Kata kunci : Arus Transien, Ketahanan Transformator, Jenis Beban. ABSTRACT. Keywords : Transient Current, Transformer withstand, load type.
Jurnal Reka Elkomika 2337-439X Januari 2013 Jurnal Online Institut Teknologi Nasional Teknik Elektro Itenas Vol.1 No.1 Analisis Arus Transien Transformator Setelah Penyambungan Beban Gedung Serbaguna PT
Lebih terperinciD. Relay Arus Lebih Berarah E. Koordinasi Proteksi Distribusi Tenaga Listrik BAB V PENUTUP A. KESIMPULAN B. SARAN...
DAFTAR ISI HALAMAN JUDUL... i HALAMAN PENGESAHAN... ii HALAMAN PERNYATAAN... v MOTTO... vi HALAMAN PERSEMBAHAN... vii KATA PENGANTAR... viii DAFTAR ISI... x DAFTAR GAMBAR... xii DAFTAR TABEL... xiv INTISARI...
Lebih terperinciKata Kunci : Transformator Distribusi, Ketidakseimbangan Beban, Arus Netral, Rugi-rugi, Efisiensi
Rizky Syahputra Srg., Raja Harahap, Perhitungan Arus... SSN : 59 1099 (Online) SSN : 50 3 (Cetak) Perhitungan Arus Netral, Rugi-Rugi, dan Efisiensi Transformator Distribusi 3 Fasa 0 KV/00V Di PT. PLN (Persero)
Lebih terperinciBAB II EKSPERIMEN 2 RANGKAIAN TIGA FASA SERTA HUBUNGAN Y (BINTANG) DAN DELTA ( )
BAB II EKSPERIMEN 2 RANGKAIAN TIGA FASA SERTA HUBUNGAN (BINTANG) DAN DELTA ( ) I. Tujuan Untuk mempelajari hubungan arus dan tegangan pada hubungan dan delta pada rangkaian tiga fasa. II. Alat dan Bahan
Lebih terperinci2.2.6 Daerah Proteksi (Protective Zone) Bagian-bagian Sistem Pengaman Rele a. Jenis-jenis Rele b.
DAFTAR ISI JUDUL SAMPUL DALAM... ii LEMBAR PERNYATAAN ORISINALITAS... iii LEMBAR PERSYARATAN GELAR... iv LEMBAR PENGESAHAN... v UCAPAN TERIMA KASIH... vi ABSTRAK... viii ABSTRACT... ix DAFTAR ISI... x
Lebih terperinciBAB V PENUTUP 5.1 Simpulan Saran DAFTAR PUSTAKA LAMPIRAN LAMPIRAN
DAFTAR ISI HALAMAN SAMPUL DALAM... i PRASYARAT GELAR... ii LEMBAR PERNYATAAN ORISINALITAS... iii LEMBAR PERSETUJUAN PEMBIMBING... iv UCAPAN TERIMAKASIH... v ABSTRAK... vii ABSTRACT... viii DAFTAR ISI...
Lebih terperinciSTUDI PENGARUH KETIDAKSEIMBANGAN PEMBEBANAN TRANSFORMATOR DISTRIBUSI 20 KV PT PLN (PERSERO) CABANG PONTIANAK
STUDI PENGARUH KETIDAKSEIMBANGAN PEMBEBANAN TRANSFORMATOR DISTRIBUSI 20 KV PT PLN (PERSERO) CABANG PONTIANAK Edy Julianto D0110707 Fakultas teknik, Jurusan Teknik Elektro, Universitas Tanjungpura Email
Lebih terperinciANALISIS SISTEM JARINGAN DISTRIBUSI TEGANGAN RENDAH DI KECAMATAN BENTENG KAB. KEPULAUAN SELAYAR TAHUN 2010
ANALISIS SISTEM JARINGAN DISTRIBUSI TEGANGAN RENDAH DI KECAMATAN BENTENG KAB. KEPULAUAN SELAYAR TAHUN 010 Sriwati, A. Arif Bijaksana Dosen Program Studi Teknik Elektro Universitas Islam Makassar ABASTRAK
Lebih terperinciBAB I PENDAHULUAN. atau penurunan tegangan yang diakibatkan pusat-pusat pembangkit tenaga listrik
BAB I PENDAHULUAN I.1. Latar Belakang Salah satu masalah yang terdapat dalam sistim tenaga listrik adalah perubahan atau penurunan tegangan yang diakibatkan pusat-pusat pembangkit tenaga listrik berada
Lebih terperinciANALISA RUGI-RUGI PADA GARDU 20/0.4 KV
ANALISA RUGI-RUGI PADA GARDU 20/0.4 KV Oleh Endi Sopyandi Dasar Teori Dalam penyaluran daya listrik banyak digunakan transformator berkapasitas besar dan juga bertegangantinggi. Dengan transformator tegangan
Lebih terperinciPengaruh Ketidakseimbangan Beban Terhadap Arus Netral dan Losses pada Trafo Distribusi
Jurnal Teknik Elektro Vol. 6, No. 1, Maret 2006: 68-7 engaruh Ketidakseimbangan Beban Terhadap Arus Netral dan Losses pada Trafo Distribusi Julius entosa etiadji 1, Tabrani Machmudsyah 2, Yanuar snanto
Lebih terperinciBAB I PENDAHULUAN. 1.1 Latar Belakang Masalah
BAB I PENDAHULUAN 1.1 Latar Belakang Masalah Trafo Distribusi merupakan suatu komponen yang sangat penting dalam penyaluran tenaga listrik dari gardu distribusi ke konsumen. Trafo Distribusi dapat dipasang
Lebih terperinciBAB II LANDASAN TEORI
BAB II LANDASAN TEORI Pada bab ini akan dijelaskan tentang gangguan pada sistem tenaga listrik, sistem proteksi tenaga listrik, dan metoda proteksi pada transformator daya. 2.1 Gangguan dalam Sistem Tenaga
Lebih terperinciBAB III LANDASAN TEORI
15 BAB III LANDASAN TEORI Tenaga listrik dibangkitkan dalam Pusat-pusat Listrik seperti PLTA, PLTU, PLTG, PLTP dan PLTD kemudian disalurkan melalui saluran transmisi yang sebelumnya terlebih dahulu dinaikkan
Lebih terperinciBAB II TINJAUAN PUSTAKA. yang lain, melalui suatu gandengan magnet dan berdasarkan prinsip induksi
BAB II TINJAUAN PUSTAKA 2.1 Transformator Transformator adalah suatu alat listrik yang dapat memindahkan dan mengubah energi listrik dari satu atau lebih rangkaian listrik ke rangkaian listrik yang lain,
Lebih terperinciBAB II TINJAUAN PUSTAKA. Gambar 2.1 Tiga Bagian Utama Sistem Tenaga Listrik untuk Menuju Konsumen
BAB II TINJAUAN PUSTAKA 2.1 Sistem Distribusi Pada dasarnya, definisi dari sebuah sistem tenaga listrik mencakup tiga bagian penting, yaitu pembangkitan, transmisi, dan distribusi, seperti dapat terlihat
Lebih terperinciAnalisis Unjuk Kerja Tiga Unit Inter Bus Transformers 500 MVA 500/150/66 kv di GITET Kediri
ELPOSYS Jurnal Sistem Kelistrikan Vol. 03 No.1, ISSN: 2355 9195, E-ISSN: 2356-0533 Analisis Unjuk Kerja Tiga Unit Inter Bus Transformers 500 MVA 500/150/66 kv di GITET Kediri Aan M. Ilham *a), Rachmat
Lebih terperinciANALISA PROTEKSI TRANSFORMATOR 150 kv DENGAN MENGGUNAKAN RELE DIFERENSIAL DI PLTG PAYA PASIR
ANALISA PROTEKSI TRANSFORMATOR 150 kv DENGAN MENGGUNAKAN RELE DIFERENSIAL DI PLTG PAYA PASIR LAPORAN TUGAS AKHIR Ditulis Untuk Memenuhi Syarat Menyelesaikan Pendidikan Diploma III PROGRAM STUDI TEKNIK
Lebih terperinciBAB II SALURAN DISTRIBUSI
BAB II SALURAN DISTRIBUSI 2.1 Umum Jaringan distribusi adalah salah satu bagian dari sistem penyaluran tenaga listrik dari pembangkit listrik ke konsumen. Secara umum, sistem penyaluran tenaga listrik
Lebih terperinciBAB II PRINSIP DASAR TRANSFORMATOR
BAB II PRINSIP DASAR TRANSFORMATOR 2.1 UMUM Transformator (trafo ) merupakan piranti yang mengubah energi listrik dari suatu level tegangan AC lain melalui gandengan magnet berdasarkan prinsip induksi
Lebih terperinciAnalisis Kualitas Minyak Transformator Daya 25 KVA Berdasarkan Data Citra Kamera Termal dan Data Hasil Uji Gas Chromatograph
JURNAL TEKNIK POMITS Vol. 1, No. 1, (2012) 1-6 1 Analisis Kualitas Minyak Transformator Daya 25 KVA Berdasarkan Data Citra Kamera Termal dan Data Hasil Uji Gas Chromatograph Subkhi Abdul Aziz, Vita Lystianingrum
Lebih terperinciABSTRAK. Kata Kunci : Perumahan Nuansa Kori Jimbaran, drop tegangan, JTR. vii
ABSTRAK Perumahan Nuansa Kori Jimbaran disuplai oleh salah satu trafo distribusi KA1441 melalui Penyulang Jimbaran. Trafo KA1441 berlokasi di Perumahan Nuansa Kori Jimbaran dengan kapasitas 250 KVA yang
Lebih terperinciMonitoring Kondisi Transformator Daya Secara Online Berbasis Analisis Data Suhu, Tegangan, dan Arus pada Transformator Distribusi
JURNA L TEKNIK POMITS Vo l. 1, No. 1, (2012) 1-6 1 Monitoring Kondisi Transformator Daya Secara Online Berbasis Analisis Data Suhu, Tegangan, dan Arus pada Transformator Distribusi Bryan Rahardy, Dr. Eng.
Lebih terperinciSTUDI PENGGUNAAN SISTEM PENDINGIN UDARA TEKAN UNTUK MENINGKATKAN EFISIENSI TRANSFORMATOR PADA BEBAN LEBIH
STUDI PENGGUNAAN SISTEM PENDINGIN UDARA TEKAN UNTUK MENINGKATKAN EFISIENSI TRANSFORMATOR PADA BEBAN LEBIH (Aplikasi pada PLTU Labuhan Angin, Sibolga) Yohannes Anugrah, Eddy Warman Konsentrasi Teknik Energi
Lebih terperinciRudi Salman Staf Pengajar Program Studi Teknik Elektro Universitas Negeri Medan
Analisis Penempatan Transformator Distribusi Berdasarkan Jatuh Tegangan Rudi Salman Staf Pengajar Program Studi Teknik Elektro Universitas Negeri Medan rudisalman.unimed@gmail.com Abstract Distribution
Lebih terperinciANALISIS KETIDAKSEIMBANGAN BEBAN PADA JARINGAN DISTRIBUSI SEKUNDER GARDU DISTRIBUSI DS 0587 DI PT. PLN (Persero) DISTRIBUSI BALI RAYON DENPASAR
SKRIPSI ANALISIS KETIDAKSEIMBANGAN BEBAN PADA JARINGAN DISTRIBUSI SEKUNDER GARDU DISTRIBUSI DS 0587 DI PT. PLN (Persero) DISTRIBUSI BALI RAYON DENPASAR WAHYU SUSONGKO NIM. 0819451020 JURUSAN TEKNIK ELEKTRO
Lebih terperinciPengujian Transformator
Pengujian Transformator Pengujian transformator dilaksanakan menurut SPLN 50-1982 dengan melalui tiga macam pengujian, sebagaimana diuraikan juga dalam IEC 76 (1976), yaitu : - Pengujian Rutin Pengujian
Lebih terperinciBACK UP SISTEM KELISTRIKAN PLTGU PT. INDONESIA POWER UBP SEMARANG DENGAN START UP DIESEL GENERATOR 6,3KV DAN 400V
BACK UP SISTEM KELISTRIKAN PLTGU PT. INDONESIA POWER UBP SEMARANG DENGAN START UP DIESEL GENERATOR 6,3KV DAN 400V Alga Bagas Setiawan 1, Ir. Agung Nugroho, Mkom 2. 1 Mahasiswa dan 2 Dosen Jurusan Teknik
Lebih terperinciKata Kunci Pentanahan, Gardu Induk, Arus Gangguan Ketanah, Tegangan Sentuh, Tegangan Langkah, Tahanan Pengetanahan. I. PENDAHULUAN
PERANCANGAN SISTEM PENGETANAHAN PERALATAN DI GARDU INDUK PLTU IPP (INDEPENDENT POWER PRODUCER) KALTIM 3 Jovie Trias Agung N¹, Drs. Ir. Moch. Dhofir, MT.², Ir. Soemarwanto, M.T.³ ¹Mahasiswa Teknik Elektro,
Lebih terperinciBAB IV DATA DAN PEMBAHASAN. Pengumpulan data dilaksanakan di PT Pertamina (Persero) Refinery
BAB IV DATA DAN PEMBAHASAN 4.1 Pengumpulan Data Pengumpulan data dilaksanakan di PT Pertamina (Persero) Refinery Unit V Balikpapan selama 2 bulan mulai tanggal 1 November 2016 sampai tanggal 30 Desember
Lebih terperinciANALISA PENYETELAN RELAI GANGGUAN TANAH (GFR) PADA PENYULANG TRAFO 2 30 MVA 70/20 KV DI PT. PLN (PERSERO) GARDU INDUK BOOM BARU PALEMBANG
ANALISA PENYETELAN RELAI GANGGUAN TANAH (GFR) PADA PENYULANG TRAFO 2 30 MVA 70/20 KV DI PT. PLN (PERSERO) GARDU INDUK BOOM BARU PALEMBANG LAPORAN AKHIR Dibuat Untuk Memenuhi Persyaratan Menyelesaikan Pendidikan
Lebih terperinciTransformator : peralatan listrik elektromagnetik statis yang berfungsi untuk memindahkan dan mengubah daya listrik dari suatu rangkaian listrik ke ra
TRANSFORMATOR Transformator : peralatan listrik elektromagnetik statis yang berfungsi untuk memindahkan dan mengubah daya listrik dari suatu rangkaian listrik ke rangkaian listrik lainnya,dengan frekuensi
Lebih terperinciSTUDI SUSUT UMUR TRANSFORMATOR DISTRIBUSI 20 kv AKIBAT PEMBEBANAN LEBIH DI PT.PLN (PERSERO) KOTA PONTIANAK
STUDI SUSUT UMUR TRANSFORMATOR DISTRIBUSI 20 kv AKIBAT PEMBEBANAN LEBIH DI PT.PLN (PERSERO) KOTA PONTIANAK Parlindungan Gultom 1), Ir. Danial, MT. 2), Managam Rajagukguk, ST, MT. 3) 1,2,3) Program Studi
Lebih terperinciPerencanaan Kebutuhan Distribusi Sekunder Perumahan RSS Manulai II
10 Jurnal Rekayasa Elektrika Vol. 10,. 1, April 2012 Perencanaan Kebutuhan Distribusi Sekunder Perumahan RSS Manulai II Evtaleny R. Mauboy dan Wellem F. Galla Jurusan Teknik Elektro, Universitas Nusa Cendana
Lebih terperinciTotal Loss Energy Efisiensi Transformator Kualitas Daya Listrik (Power Quality) Harmonisa
DAFTAR ISI JUDUL... i LEMBAR PERNYATAAN ORISINALITAS... ii LEMBAR PRASYARAT GELAR SARJANA... iii LEMBAR PENGESAHAN... iv UCAPAN TERIMAKASIH... v ABSTRAK... vii ABSTRACT... viii DAFTAR ISI... ix DAFTAR
Lebih terperinciPENGARUH KETIDAKSEIMBANGAN BEBAN PADA TRAFO DISTRIBUSI DI PT. PLN (PERSERO) WS2JB AREA PALEMBANG RAYON KAYU AGUNG. LAPORAN AKHIR.
PENGARUH KETIDAKSEIMBANGAN BEBAN PADA TRAFO DISTRIBUSI DI PT. PLN (PERSERO) WS2JB AREA PALEMBANG RAYON KAYU AGUNG. LAPORAN AKHIR Laporan akhir ini disusun untuk memenuhi salah satu syarat Menyelesaikan
Lebih terperinciREKONDISI TRANSFORMATOR UNTUK MENGATASI MENURUNNYA KEMAMPUAN ISOLASI PADA TRANSFORMATOR DISTRIBUSI 20 kv
REKONDISI TRANSFORMATOR UNTUK MENGATASI MENURUNNYA KEMAMPUAN ISOLASI PADA TRANSFORMATOR DISTRIBUSI 20 kv (Transformer Recondition in order to overcome Reduction of Insulation Performance in Distribution
Lebih terperinciANALISA KEDIP TEGANGAN PADA SISTEM DISTRIBUSI TENAGA LISTRIK 20 KV AKIBAT HUBUNG SINGKAT PADA PENYULANG PEDAN 1 KLATEN
ANALISA KEDIP TEGANGAN PADA SISTEM DISTRIBUSI TENAGA LISTRIK 20 KV AKIBAT HUBUNG SINGKAT PADA PENYULANG PEDAN 1 KLATEN Disusun sebagai salah satu syarat menyelesaikan Program Studi Strata I pada Jurusan
Lebih terperinciProsiding Seminar Nasional Aplikasi Sains & Teknologi (SNAST) 2014 ISSN: X Yogyakarta, 15 November 2014
FUNGSI MINYAK ISOLASI PADA TRANSFORMATOR YANG BERKAPASITAS BESAR H. Sabari 1,H. Suhardi 2 12 Program Studi T. Elektro,Politeknik Harapan Bersama Tegal E-mail : hajisabari@gmail.com, suhardith@gmail.com
Lebih terperinciLatihan Soal dan Quiz II
Modul ke: Latihan Soal dan Quiz II Modul ini menjelaskan latihan soal tranformator dan quiz II Fakultas TEKNIK Ima Rochimawati, ST. MT Program Studi Teknik Elektro www.mercubuana.ac.id Latihan Soal : 1.
Lebih terperinciWATAK HARMONIK PADA INVERTER TIGA FASA TAK BERBEBAN
WATAK HARMONIK PADA INVERTER TIGA FASA TAK BERBEBAN Wahri Sunanda 1, Yuli Asmi Rahman 2 1 Teknik Elektro Fakultas Teknik Universitas Bangka Belitung 2 Teknik Elektro Fakultas Teknik Universitas Tadulako
Lebih terperinciANALISIS KEDIP TEGANGAN AKIBAT GANGGUAN HUBUNG SINGKAT PADA PENYULANG ABANG DI KARANGASEM
ANALISIS KEDIP TEGANGAN AKIBAT GANGGUAN HUBUNG SINGKAT PADA PENYULANG ABANG DI KARANGASEM I Made Yoga Dwipayana 1, I Wayan Rinas 2, I Made Suartika 3 Jurusan Teknik Elektro dan Komputer, Fakultas Teknik,
Lebih terperinciJurnal Media Elektro, Vol. 1, No. 3, April 2013 ISSN
Analisis Jatuh Pada Penyulang 20 kv Berdasarkan pada Perubahan Beban (Studi Kasus Penyulang Penfui dan Penyulang Oebobo PT. PLN Persero Rayon Kupang) Agusthinus S. Sampeallo, Wellem F. Galla, Rendi A.
Lebih terperinciOPTIMALISASI PEMBEBANAN TRANSFORMATOR DISTRIBUSI DENGAN PENYEIMBANGAN BEBAN
PROSIDING 0 13 HASIL PENELITIAN FAKULTAS TEKNIK OPTIMALISASI PEMBEBANAN TRANSFORMATOR DISTRIBUSI DENGAN PENYEIMBANGAN BEBAN Jurusan Teknik Elektro Fakultas Teknik Universitas Hasanuddin Jl. Perintis Kemerdekaan
Lebih terperinciPROSEDUR PENGUJIAN TAHANAN ISOLASI TRAFO
PROSEDUR PENGUJIAN TAHANAN ISOLASI TRAFO 1. Tujuan Percobaan : Untuk mengetahui kondisi isolasi trafo 3 fasa Untuk mengetahui apakah ada bagian yang hubung singkat atau tidak 2. Alat dan Bahan : Trafo
Lebih terperinciBAB III SPESIFIKASI TRANSFORMATOR DAN SWITCH GEAR
38 BAB III SPESIFIKASI TRANSFORMATOR DAN SWITCH GEAR 3.1 Unit Station Transformator (UST) Sistem PLTU memerlukan sejumlah peralatan bantu seperti pompa, fan dan sebagainya untuk dapat membangkitkan tenaga
Lebih terperinciBAB III. Transformator
BAB III Transformator Transformator merupakan suatu alat listrik yang mengubah tegangan arus bolak-balik dari satu tingkat ke tingkat yang lain melalui suatu gandengan magnet dan berdasarkan prinsipprinsip
Lebih terperinciANALISIS KEDIP TEGANGAN AKIBAT GANGGUAN HUBUNG SINGKAT PADA PENYULANG ABANG DI KARANGASEM
SKRIPSI ANALISIS KEDIP TEGANGAN AKIBAT GANGGUAN HUBUNG SINGKAT PADA PENYULANG ABANG DI KARANGASEM I MADE YOGA DWIPAYANA JURUSAN TEKNIK ELEKTRO DAN KOMPUTER FAKULTAS TEKNIK UNIVERSITAS UDAYANA BUKIT JIMBARAN
Lebih terperinciBAB II TRANSFORMATOR. elektromagnet. Pada umumnya transformator terdiri atas sebuah inti yang terbuat
BAB II TRANSFORMATOR 2.1 UMUM Transformator merupakan suatu alat listrik yang dapat memindahkan dan mengubah energi listrik dari satu atau lebih rangkain listrik ke rangkaian listrik lainnya melalui suatu
Lebih terperinciPERANCANGAN PROTOTIPE REAL TIME MONITORING BEBAN TRANSFORMATOR DISTRIBUSI 20 KV BERBASIS MIKROKONTROLER
JETri, Vol. 15, No. 1, Agustus 2017, Hlm. 55-64, P-ISSN 1412-0372, E-ISSN 2541-089X PERANCANGAN PROTOTIPE REAL TIME MONITORING BEBAN TRANSFORMATOR DISTRIBUSI 20 KV BERBASIS MIKROKONTROLER Lia Frisila dan
Lebih terperinciKONDISI TRANSIENT 61
KONDISI TRANSIENT 61 NAMEPLATE GENERATOR GENERATOR SET SALES MODEL RATING 1000 KVA 800 KW 0.8 COSΦ 50 HZ CONTINUOUS XXX PRIME STANDBY STANDBY GENERATOR DATA 3 PHASE 12 WIRE XXX WYE DELTA CONNECTION XXX
Lebih terperinciPenentuan Setting Rele Arus Lebih Generator dan Rele Diferensial Transformator Unit 4 PLTA Cirata II
Jurnal Reka Elkomika 2337-439X Februari 2013 Jurnal Online Institut Teknologi Nasional Teknik Elektro Itenas Vol.1 No.2 Penentuan Setting Rele Arus Lebih Generator dan Rele Diferensial Transformator Unit
Lebih terperinciPerhitungan Setting Rele OCR dan GFR pada Sistem Interkoneksi Diesel Generator di Perusahaan X
Jurnal Reka Elkomika 2337-439X Januari 2013 Jurnal Online Institut Teknologi Nasional Teknik Elektro Itenas Vol.1 No.1 Perhitungan Setting Rele OCR dan GFR pada Sistem Interkoneksi Diesel Generator di
Lebih terperinciIII PENGUMPULAN DAN PENGOLAHAN DATA
III PENGUMPULAN DAN PENGOLAHAN DATA 3.1. Umum Berdasarkan standard operasi PT. PLN (Persero), setiap pelanggan energi listrik dengan daya kontrak di atas 197 kva dilayani melalui jaringan tegangan menengah
Lebih terperinciEVALUASI DISTRIBUSI TEGANGAN RENDAH PADA GARDU DISTRIBUSI PT. PLN (PERSERO) RAYON MARIANA
EVALUASI DISTRIBUSI TEGANGAN RENDAH PADA GARDU DISTRIBUSI PT. PLN (PERSERO) RAYON MARIANA LAPORAN AKHIR Dibuat Untuk Memenuhi Syarat Menyelesaikan Pendidikan Diploma III Pada Jurusan Teknik Elektro Program
Lebih terperinciBAB II TINJAUAN PUSTAKA
BAB II TINJAUAN PUSTAKA 2.1 Umum Suatu sistem tenaga listrik dikatakan ideal jika bentuk gelombang arus yang dihasilkan dan bentuk gelombang tegangan yang disaluran ke konsumen adalah gelombang sinus murni.
Lebih terperinciBAB II LANDASAN TEORI
BAB II LANDASAN TEORI 2.1 Definisi Transformator Transformator atau transformer atau trafo adalah suatu peralatan listrik elektromagnetik statis yang berfungsi untuk memindah dan mengubah energi listrik
Lebih terperinciABSTRAK. Universitas Kristen Maranatha
ABSTRAK Sebuah transformator dapat dibebani secara terus menerus sesuai dengan kemampuan nominalnya. Pada prakteknya sangat jarang terjadi pembebanan sebuah transformator secara terus menerus pada nominalnya.
Lebih terperinciLAPORAN AKHIR GANGGUAN OVERLOAD PADA GARDU DISTRBUSI ASRAMA KIWAL
LAPORAN AKHIR GANGGUAN OVERLOAD PADA GARDU DISTRBUSI ASRAMA KIWAL Oleh : SEMUEL MASRI PONGKORUNG NIM : 13021003 Dosen Pembimbing Reiner Ruben Philipus Soenpiet, SST NIP. 1961019 199103 2 001 KEMENTERIAN
Lebih terperinci