PENERAPAN OLS UNTUK MEMINIMALISIR PEMADAMAN MELUAS AKIBAT OVERLOAD PADA SATU PENGHANTAR 1. Anung 2. Achirul Ramadhani
|
|
- Sudirman Kusumo
- 6 tahun lalu
- Tontonan:
Transkripsi
1 PENERAPAN OLS UNTUK MEMINIMALISIR PEMADAMAN MELUAS AKIBAT OVERLOAD PADA SATU PENGHANTAR 1. Anung 2. Achirul Ramadhani Program Studi Teknik Elektro, Sekolah Tinggi Teknologi Mandala Jl.Soekarno Hatta No.597 Bandung, Jawa Barat ABSTRACT Economic growth is directly proportional to the electrical power system availability requirements. The consequence of the addition of electric power, necessary to increase the capacity (uprating) and the addition of new installations to meet the demands / needs of the electric power. But adding additional capacity or new installation is not easy, given the various constraints and no small investment. In the Java-Bali power system, there are some particular subsystem Cibatu distribution equipment installation (transformer / IBT and conductor) with the condition that no longer meet the criteria for N-1 or in other words, the assignment has been above 60%. This means that if one of the IBT or impaired conductor / conductor trip the IBT or the other will experience more load / Overload (above the nominal rating). To avoid that implemented an operating strategy, namely Overload Sheding Strategy (OLS). This strategy aims to secure the equipment from the loading more and avoid the risk of widespread blackouts in a way that partially extinguish automatically load with a load arranged. Overload Shedding Scheme (OLS) using overload relay (Over Load Relay) which, in principle, to detect the presence of more current flowing in the transformer / IBT and the Transmission. Over Load Shedding (OLS) at setting 1.1 x Nominal currents lower than the setting Overcurrent relays (OCR) to 1.2 x Current Nominal setting but with different time characteristics, which overcurrent relays (OCR) works with the characteristics Inverse standard (SI) and Over Load Shedding relays work with definite characteristics. With the target at GI Rengasdengklok one transformer 60 MVA so that before the ols is installed the load is off MW and after the installed OLS load is off MW. Keywords : Transformator, Transmision, N-1, OLS, OCR ABSTRAK Pertumbuhan ekonomi berbanding lurus dengan kebutuhan ketersediaan sistem tenaga listrik. Konsekuensi dari Penambahan daya listrik, perlu dilakukan penambahan kapasitas (uprating) maupun penambahan instalasi baru untuk memenuhi permintaan/kebutuhan daya listrik tersebut. Namun penambahan kapasitas maupun penambahan instalasi baru tidaklah mudah, mengingat berbagai kendala dan investasi yang tidak sedikit. Di sistem tenaga listrik Jawa Bali, khususnya subsistem Cibatu 3-4 terdapat beberapa peralatan instalasi penyaluran (trafo/ibt maupun penghantar) dengan kondisi yang sudah tidak memenuhi kriteria N-1 atau dengan kata lain pembebanannya sudah diatas 60%. Artinya bila salah satu IBT atau penghantar tersebut mengalami gangguan/trip maka IBT atau penghantar yang satunya akan mengalami pembebanan lebih/overload (diatas rating nominalnya). Untuk mengindari hal tersebut diterapkan suatu strategi operasi, yaitu Strategi Overload Sheding (OLS). Strategi ini bertujuan untuk mengamankan peralatan dari pembebanan lebih serta menghindari resiko pemadaman yang luas dengan cara memadamkan sebagian beban secara otomatis dengan beban yang diatur sedemikian rupa. Skema Overload Shedding (OLS) menggunakan relai beban lebih (Over Load Relai) yang pada prinsipnya mendeteksi adanya arus lebih yang mengalir pada Transformator/IBT maupun Transmisi tersebut. Over Load Shedding (OLS) di setting 1,1 x Arus Nominal yang lebih rendah dari setting relai Arus Lebih (OCR) dengan setting 1,2 x Arus Nominal tetapi dengan karakteristik waktu yang berbeda, dimana relai arus lebih
2 (OCR) bekerja dengan karakteristik Standar Inverse (SI) dan relai Over Load Shedding bekerja dengan karakteristik Definite. Dengan target di GI Rengasdengklok trafo satu 60 MVA sehingga sebelum ols terpasang beban padam 63,18 MW dan sesudah terpasang OLS beban padam 18,84 MW. Kata Kunci : Trafo, Penghantar, N-1, OLS, OCR I. PENDAHULUAN Pertumbuhan ekonomi berbanding lurus dengan kebutuhan ketersediaan sistem tenaga listrik. Konsekuensi dari Penambahan daya listrik, perlu dilakukan penambahan kapasitas (uprating) maupun penambahan instalasi baru untuk memenuhi permintaan/kebutuhan daya listrik tersebut. Namun penambahan kapasitas maupun penambahan instalasi baru tidaklah mudah, mengingat berbagai kendala dan investasi yang tidak sedikit. Di sistem tenaga listrik Jawa Bali khususnya Jawa Barat, penghantar 70 kv Kosambi Baru Rengasdengklok yang pernah mengalami overload, sehingga mengakibatkan hilang tegangan dan padam total di sisi GI Rengasdengklok pada tahun 2014, dikarenakan masih terdapat peralatan instalasi penyaluran (penghantar) dengan kondisi yang sudah tidak memenuhi kriteria N-1 (kondisi normal dua penghantar dikurangin satu) atau dengan kata lain pembebanannya sudah diatas 60%. Artinya bila salah satu penghantar tersebut mengalami gangguan/trip maka penghantar yang satunya akan mengalami pembebanan lebih/overload (diatas rating nominalnya). Maka dari itu, untuk mengindari terjadinya pemadaman total yang mengakibatkan tidak tersalurkannya energi listrik dalam jumlah besar, perlu diterapkan suatu strategi operasi, yaitu dengan penerapan relay Overload Sheding (OLS). Strategi ini bertujuan untuk mengamankan peralatan dari pembebanan lebih serta menghindari atau meminimalisir resiko pemadaman yang luas dengan cara memadamkan sebagian beban secara otomatis dengan beban yang diatur sedemikian rupa, II. TINJAUAN PUSTAKA Sistem Tenaga Listrik Sistem Tenaga Listrik adalah suatu sistem yang terdiri dari beberapa komponen berupa pembangkitan, transmisi, distribusi dan beban yang saling berhubungan dan berkerja sama untuk melayani kebutuhan tenaga listrik bagi pelanggan sesuai kebutuhan. Secara garis besar Sistem Tenaga Listrik dapat digambarkan dengan skema di bawah ini. [1] Gambar 2.1 Sistem Tenaga Listrik Sistem Transmisi Gambar 2.2 Sistem Transmisi Bagian dari sistem tenaga listrik yang berupa sejumlah konduktor yang dipasang membentang sepanjang jarak antara pusat pembangkit sampai pusat beban. Fungsinya untuk mengirimkan energi listrik dari pusat pembangkit ke pusat beban. [1] Macam-macam Saluran Transmisi: Saluran udara: Kawat atau kondutor telanjang (tanpa isolasi) yang digantung dengan ketinggian tertentu pada tower dengan menggunakan isolator. Saluran bawah tanah: kabel atau konduktor berisolasi yang ditanam dalam tanah dengan kedalaman tertentu.
3 Saluran bawah laut: kabel atau konduktor berisolasi yang diletakkan di dasar laut. Saluran transmisi biasanya digunakan untuk mengirimkan daya listrik untuk jarak yang relatif jauh. Dari ketiga jenis saluran transmisi, paling banyak digunakan adalah saluran udara, karena lebih ekonomis. Biaya pembangunan saluran udara relatif lebih ringan dibandingkan dengan jenis yang lain, karena menggunakan penghantar yang telanjang atau tidak berisolasi, sedang jenis yang lain harus menggunakan penghantar berisolasi. Gardu Induk Gambar 2.3 Sistem Tenaga Listrik di Gardu Induk Gardu induk merupakan bagian dari sistem tenaga listrik yang berupa sejumlah peralatan pemutus/penghubung aliran arus dan trafo penaik/penurun tegangan yang dipasang di antara dua komponen sistem tenaga listrik lainnya. Gardu induk berfungsi untuk memutus/menghubungkan aliran arus listrik dan menyesuaikan level tegangan sistem-sistem yang dihubungkan. [1] Pengertian Dasar Proteksi Sistem proteksi adalah pengaman listrik pada sistem tenaga listrik yang terpasang pada sistem distribusi tenaga listrik, trafo tenaga, transmisi tenaga listrik dan generator listrik yang dipergunakan untuk mengamankan sistem tenaga listrik dari gangguan listrik atau beban lebih, dengan cara memisahkan bagian sistem tenaga listrik yang terganggu. Sehingga sistem kelistrikan yang tidak terganggu dapat terus bekerja (mengalirkan arus kebeban atau konsumen). Jadi pada hakekatnya pengaman pada system tenaga listrik yaitu mengamankan seluruh sistem tenaga listrik supaya kehandalan tetap terjaga. [2] Sistem Proteksi dan Kontrol Penghantar SUTT Sistem proteksi bay penghantar adalah suatu sistem yang yang berfungsi untuk mengamankan/mengisolir penghantar (saluran udara/saluran kabel) tegangan tinggi atau tegangan ekstra tinggi dari gangguan temporer dan gangguan permanen yang terjadi pada penghantar tersebut. [3] III. METODE PENELITIAN Desain Penelitian Desain penelitian menurut Sedarmayanti dan Hidayat (2011:206) adalah semua proses yang diperlukan dalam perencanaan dan pelaksanaan penelitian.[6] Menurut Sugiyono (2003:11) penelitian berdasarkan tingkat eksplanasinya (tingkat kejelasan) dapat digolongkan sebagai berikut: Asosiatif Penelitian asosiatif dapat dibangun oleh suatu teori yangberfungsiuntuk menjelaskan,meramalkan, dan mengontrol suatu gejala[1], yaitu dengan cara memprediksi hitungan beban (Megawatt) pada waktu sebelum - sebelumnya di masing masing trafo distribusi Gardu Induk Rengasdengklok. Komparatif Penelitian komparatif yaitu suatu penelitian yang bersifat membandingkan fluktuasi beban (Megawatt) pada waktu yang berbeda, saat beban (Megawatt) puncak/tinggi dan beban (Megawatt) rendahdi Gardu Induk Rengasdengklok. Deskriptif Penelitian deskriptif merupakan penelitian yang dilakukan untuk mengetahui nilai variabel, yaitu dengan cara menghubungi langsung operator Gardu Induk untuk menanyakan suatu nilai beban (Megawatt) trafoataupun dengan cara otomatis dari nilai SCADA (Supervisory Control Data Acquisition). Sedangkan jenis penelitian menurut Sugiyono, (2003:14) terdiri dari:
4 Penelitian kuantitatif, adalah penelitian dengan memperoleh data yang berbentuk angka atau data kualitatif yang diangkakan[5], yaitu pengambilan nilai dalam bentuk beban (Megawatt) dengan menggunakanscada (Supervisory Control Data Acquisition) yang merupakan suatu sistem kendali industri Gambar 4.1 Skema target OLS berbasis komputer yang dipakai untuk pengontrolan suatu proses. Penelitian kualitatif merupakan suatu penelitian yang bertujuan memahami kondisi realitas pertumbuhan beban (Megawatt) di Gardu Induk Rengasdengklok yang sudah melebihi kapasitas penghantar 70 KV Gardu Induk Kosambi Baru Rengasdengklok saat beban puncak yang dapat mengakibatkan pemadaman meluas akibat overload pada saat operasi satu penghantar. IV.HASIL PENELITIAN DAN PEMBAHASAN Skema target OLS Menurut Buku Pedoman Defence Scheme Jawa Bali Over Load Shedding (OLS) yaitu skema pengaman system untuk mengamankan operasional instalasi penyaluran (penghantar/trafo) yang sudah tidak memenuhi kapasitas akibat kelebihan beban konsumen dengan cara melepas sebagian beban konsumen yang ada di sisi terima instalasi tersebut. Skema pengaman ini biasanya dibuat menjadi beberapa tahap untuk meminimalkan besar beban konsumen yang dilepaskan. 4.2 Setting relay Tabel 4.1 Setting OCR dan O OCR : Iset (pri) = 1,2 x 440 A = 528 Ampere Iset (sek) = 528 x 1 500/5 = 528 x = 5,28 Ampere t= 0,25 SI Karekteristik relay = Standard Inverse 5 500/5 OLS : Iset (pri) = 1,1 x 440 A = 484 Ampere Iset (sek) = 484 x 1 500/5 = 4,84 Ampere t= 6,5 detik Karekteristik relay = Definite = 484 x Tabel 4.2 Perhitunganwaktu OCR 5 500/5 Dari tabel 4.2 pada setting relay OCR dijelaskan bahwa semakin besar arus maka semakin cepat waktu[7]. Untuk mencari setting waktu digunakan persamaan 4.1 sebagai berikut : Gambar 4.1 Skema target OLS t= T..(4.1) K (I Is)α - 1
5 Dimana : t = Waktu kerja relay T = Setting waktu pada relay K = Faktor I = Arus kerja relay Is = Arus setting relay α = Faktor kali t= 0,25 T = 42.8 detik (550/528) t= 0,25 T = 29.7 detik (560/528) t= 0,25 T = 22.8 detik (570/528) t= 0,25 T = 18.6 detik (580/528) t= 0,25 T = 15.7 detik (590/528) t= 0,25 T = 13.6 detik (600/528) Gambar 4.2 Perbandingan karakteristik relay Dari grafik diatas, dapat diketahui bahwa pada karakteristik definite time relay akan memberikan perintah pada PMT pada saat terjadi gangguan hubung singkat atau besarnya arus gangguan melampaui settingnya (Is) dan jangka waktu kerja relay mulai pick up sampai kerja relay diperpanjang dengan waktu tertentu tidak tergantung 51 besar nyaarus yang mengerjakan relay. Sedangkan pada karakteristik inverse time relay, relay akan bekerja dengan waktu tunda yang tergantung dari besarnya arus secara terbalik, semakin besar arus maka makin kecil waktu tundanya. Sebelum terpasang relay OLS Pada tanggal 21Juli 2014 pukul 18:55 WIB terjadi trip pada penghantar 1 70 kv Gardu Induk Kosambi Baru - Rengasdengklok sehingga mengakibatkan over load pada penghantar 2,yang mengakibatkan Gardu Induk Rengasdengklok mengalami hilang tegangan. Dengan data berupa tabel seperti berikut : Tabel 4.3 Data tabel beban pada saat gangguan t= 0,25 T = 12.1 detik (610/528) t= 0,25 T = 10.8 detik (620/528) t= 0,25 T = 9.8 detik (630/528) Dari tabel 4.3 menunjukan fluktuasi beban perjam di hari senin. Pada pukul 19:00 WIB beban pada Trafo 1, Trafo 2, Trafo 3 & Trafo 4 menunjukan angka Nol yang berarti sedang mengalami gangguan padam total atau hilang tegangan. Berikut tampilan dalam bentuk grafik :
6 Gambar 4.3 Grafik beban sebelum ols terpasang Dari tabel 4.4 menunjukan fluktuasi beban perjam di hari senin. Pada pukul 18:00 WIB beban pada Trafo 1 menunjukan angka Nol yang berarti sedang mengalami gangguan padam, sedangkan Trafo 2, Trafo 3 & Trafo 4 masih menunjukan nilai beban. Berikut tampilan dalam bentuk grafik : Gambar 4.4 Gardu Induk Rengasdengklok hilang tegangan Gambar 4.5 Grafik beban sesudah ols terpasang Sesudah terpasang relay OLS Dan setelah dilakukan pemasangan relai over shadding pada Gardu Induk Rengasdengklok dengan mengurangi beban Trafo 1 30 MVA di dapat hasil bahwa pemasangan relai over shadding bisa mengatasi overload pada penghantar Gardu Induk Kosambi baru Rengasdengklok.Dengan data tanggal 9 Februari 2015 pukul 17:47 WIB berupa tabel seperti berikut : Tabel 4.4 Data tabel beban trafo setelang dipasang Relay Gambar 4.6 Gardu Induk Regasdengklok Trip Trafo satu Energi tak tersalurkan Dari data yang sudah diperoleh maka dapat dihitung perbandingan energi yang tak tersalurkan saat OLS yang sudah terpasang dan belum terpasang.
7 ENS (Energy Not Serve) Energi yang tak tersalurkan : Sebelum OLS terpasang Diketahui : Beban Trafo 1 = 18,33 MW Trafo 2 = 12,17 MW Trafo 3 = 17,48 MW Trafo 4 = 15,2 MW Total = = 63,18 MW = 63,18 MW x = Watt Tegangan = 20 kv = 20 kv x 1000 = Volt P I = = 3.V.cos φ w = = 2148,2 Ampere 1.73 x v x 0,85 10 t = 10 menit = = 0,16 60 kwh = I x V x cos φ x 3 x t = 2148,2 ampere x 20 kv x 0,85 x = 1,7320 x 0,16 Jam = 10120,2 kwh Jika 1 kwh = Rp.1034 = 10120,2 kwh x Rp = Rp ,8 Sesudah OLS Terpasang Diketahui : Beban Trafo 1 = 18,84 MW =18,84MWx MW = Watt Tegangan = 20 kv x 1000= Volt I = P 3.V.cos φ w = 1,73x20.000v x0,85 = 640,59 Ampere 10 t= 10 menit = = 0,16 Jam 60 kwh = I x V x Cos φ x 3 x t = 640,59 ampere x 20 kv x 0.85 x 1,7320 x 0,16 jam = 3017,84 kwh Jika 1 kwh = Rp = 3017,84 kwh x Rp.1034 = Rp ,56 Saving : =Rp ,8 Rp ,56 = Rp ,24 V. SIMPULAN DAN SARAN Simpulan Kemampuan I nominal penghantar GI Kosambi baru Rengsdengklok yaitu 440 A, sehingga untuk setting relay OLS 1,1 x I nominal penghantar (440 A) = 484 A dan OCR 1,2 x I nominal penghantar (440 A) = 528 A. agar penyaluran tenaga listrik pada penghantar lebih optimal. Penerapan starategi Overload shedding (OLS) diperlukan untuk mengamankan peralatan listrik baik trafo maupun penghantar (yang dioperasikan paralel) dari pembebanan lebih, sebelum OLS terpasang beban padam 63,18 MW dan setelah terpasang OLS 18,84 MW. Saran Di data ulang untuk setiap beban yang mengalir pada penghantar yang sudah melebihi kapasitas agar bisa segera dipasang rele pengaman OLS.
8 Uprating kapasitas penghantar yang bebannya melebihi kapasitas DAFTAR PUSTAKA Hasan Basri, Ir., 2003 Proteksi Sistem Tenaga Listrik (Jakarta :Fakultas Teknologi Industri Institut Sains dan Teknologi Nasional) Sarimun, Wahyudi, N, MT dan Kadarisman Pribadi, Ir., 2005 Pengaman Sistem (Jakarta : STT- PLN) Hendra, Marta Yudha Rele Proteksi. Sriwijaya: Ar Raihan. Sedarmayanti,Syarifudin Hidayat Metodologi Penelitian. Bandung : CV. Mandar Maju. Sugiyono Metode Penelitian Kualitatif, kualitatif dan R&D. Bandung: Alfabeta. Moleong, Lexy J Metode Penelitian Kualitatif. Bandung: PT. Remaja Rosdakaya. A.R van C. Warrington. Protective Relays. STT Mandala. Chapman & Hall APB JABAR, PLN Buku Pedoman Defence Scheme Jawa Bali. Bandung: PT PLN ( Persero
ABSTRAK Kata Kunci :
ABSTRAK Transformator 3 pada GI Pesanggaran mendapat penambahan 4 blok pembangkit dengan daya maksimum sebesar 60 MW daya dari keempat blok pembangkit tersebut digunakan untuk mensuplai beban penyulang
Lebih terperinciBAB V PENUTUP 5.1 Simpulan Saran DAFTAR PUSTAKA LAMPIRAN LAMPIRAN
DAFTAR ISI HALAMAN SAMPUL DALAM... i PRASYARAT GELAR... ii LEMBAR PERNYATAAN ORISINALITAS... iii LEMBAR PERSETUJUAN PEMBIMBING... iv UCAPAN TERIMAKASIH... v ABSTRAK... vii ABSTRACT... viii DAFTAR ISI...
Lebih terperinciBAB II TINJAUAN PUSTAKA
BAB II TINJAUAN PUSTAKA 2.1. Sistem Distribusi 1 Bagian dari sistem tenaga listrik yang paling dekat dengan pelanggan adalah sistem distribusi. Sistem distribusi adalah bagian sistem tenaga listrik yang
Lebih terperinciBAB II TINJAUAN PUSTAKA. c. Memperkecil bahaya bagi manusia yang ditimbulkan oleh listrik.
6 BAB II TINJAUAN PUSTAKA 2.1 Sistem Proteksi Sistem proteksi merupakan sistem pengaman yang terpasang pada sistem distribusi tenaga listrik, trafo tenaga transmisi tenaga listrik dan generator listrik.
Lebih terperinci2.2.6 Daerah Proteksi (Protective Zone) Bagian-bagian Sistem Pengaman Rele a. Jenis-jenis Rele b.
DAFTAR ISI JUDUL SAMPUL DALAM... ii LEMBAR PERNYATAAN ORISINALITAS... iii LEMBAR PERSYARATAN GELAR... iv LEMBAR PENGESAHAN... v UCAPAN TERIMA KASIH... vi ABSTRAK... viii ABSTRACT... ix DAFTAR ISI... x
Lebih terperinciBAB I PENDAHULUAN. Pada sistem penyaluran tenaga listrik, kita menginginkan agar pemadaman tidak
BAB I PENDAHULUAN 1-1. Latar Belakang Masalah Pada sistem penyaluran tenaga listrik, kita menginginkan agar pemadaman tidak sering terjadi, karena hal ini akan mengganggu suatu proses produksi yang terjadi
Lebih terperinciAnalisa Koordinasi Over Current Relay Dan Ground Fault Relay Di Sistem Proteksi Feeder Gardu Induk 20 kv Jababeka
Analisa Koordinasi Over Current Relay Dan Ground Fault Relay Di Sistem Proteksi Feeder Gardu Induk 20 kv Jababeka Erwin Dermawan 1, Dimas Nugroho 2 1) 2) Jurusan Teknik Elektro Fakultas Teknik Universitas
Lebih terperinciBAB II LANDASAN TEORI
BAB II LANDASAN TEORI 2.1 Pengertian Saluran Transmisi Sistem transmisi adalah suatu sistem penyaluran energi listrik dari satu tempat ke tempat lain, seperti dari stasiun pembangkit ke substation ( gardu
Lebih terperinciTUGAS AKHIR. Diajukan guna melengkapi sebagian syarat dalam mencapai gelar Sarjana Strata Satu (S1) Disusun Oleh :
TUGAS AKHIR Strategi Over Load Shedding (OLS) Dalam Meminimalkan Pemadaman Penyaluran Tenaga Listrik Di Wilayah Sub Sistem Cibatu Pada Saluran Udara Tegangan Tinggi (SUTT) 150 kv Mekarsari Diajukan guna
Lebih terperinciBAB IV SISTEM PROTEKSI GENERATOR DENGAN RELAY ARUS LEBIH (OCR)
27 BAB IV SISTEM PROTEKSI GENERATOR DENGAN RELAY ARUS LEBIH (OCR) 4.1 Umum Sistem proteksi merupakan salah satu komponen penting dalam system tenaga listrik secara keseluruhan yang tujuannya untuk menjaga
Lebih terperinciGround Fault Relay and Restricted Earth Faulth Relay
Ground Fault Relay and Restricted Earth Faulth Relay Seperti telah disebutkan sebelumnya, maka tentang relay akan dilanjutkan dengan beberapa tipe relay. Dan kali ini yang ingin dibahas adalah dua tipe
Lebih terperinciGambar 2.1 Skema Sistem Tenaga Listrik (3)
BAB II TINJAUAN PUSTAKA 2.1 Teori Umum Secara umum suatu sistem tenaga listrik terdiri dari tiga bagian utama, yaitu, pusat pembangkitan listrik, saluran transmisi dan sistem distribusi. Perlu dikemukakan
Lebih terperinciBAB II GARDU INDUK 2.1 PENGERTIAN DAN FUNGSI DARI GARDU INDUK. Gambar 2.1 Gardu Induk
BAB II GARDU INDUK 2.1 PENGERTIAN DAN FUNGSI DARI GARDU INDUK Gardu Induk merupakan suatu instalasi listrik yang terdiri atas beberapa perlengkapan dan peralatan listrik dan menjadi penghubung listrik
Lebih terperinciPERHITUNGAN SETTING RELE ARUS LEBIH PADA TRAFO SISI 20KV DI GARDU INDUK BUKIT ASAM LAPORAN AKHIR
PERHITUNGAN SETTING RELE ARUS LEBIH PADA TRAFO SISI 20KV DI GARDU INDUK BUKIT ASAM LAPORAN AKHIR Dibuat Untuk Memenuhi Syarat Menyelesaikan Pendidikan Diploma III Pada Jurusan Teknik Elektro Program Studi
Lebih terperinciANALISIS PENYEBAB KEGAGALAN KERJA SISTEM PROTEKSI PADA GARDU AB
ANALISIS PENYEBAB KEGAGALAN KERJA SISTEM PROTEKSI PADA GARDU AB 252 Oleh Vigor Zius Muarayadi (41413110039) Jurusan Teknik Elektro, Fakultas Teknik, Universitas Mercu Buana Sistem proteksi jaringan tenaga
Lebih terperinciSTUDI ANALISIS SETTING BACKUP PROTEKSI PADA SUTT 150 KV GI KAPAL GI PEMECUTAN KELOD AKIBAT UPRATING DAN PENAMBAHAN SALURAN
STUDI ANALISIS SETTING BACKUP PROTEKSI PADA SUTT 150 KV GI KAPAL GI PEMECUTAN KELOD AKIBAT UPRATING DAN PENAMBAHAN SALURAN I Putu Dimas Darma Laksana 1, I Gede Dyana Arjana 2, Cok Gede Indra Partha 3 1,2,3
Lebih terperinciANALISA SETTING RELAI PENGAMAN AKIBAT REKONFIGURASI PADA PENYULANG BLAHBATUH
ANALISA SETTING RELAI PENGAMAN AKIBAT REKONFIGURASI PADA PENYULANG BLAHBATUH I K.Windu Iswara 1, G. Dyana Arjana 2, W. Arta Wijaya 3 1,2,3 Jurusan Teknik Elektro, Fakultas Teknik Universitas Udayana, Denpasar
Lebih terperinciANALISIS PENGARUH GANGGUAN BEBAN LEBIH PADA INTER BUS TRANSFORMER (IBT) TERHADAP KINERJA OVER LOAD SHEDDING (OLS) DI SUBSISTEM KRIAN-GRESIK
nalisis Pengaruh Beban Lebih Pada IBT Terhadap Kinerja OLS Di Subsistem -Gresik NLISIS PENGRUH GNGGUN BEBN LEBIH PD INTER BUS TRNSFORMER (IBT) TERHDP KINERJ OVER LOD SHEDDING (OLS) DI SUBSISTEM KRIN-GRESIK
Lebih terperinciBAB II LANDASAN TEORI
BAB II LANDASAN TEORI 2.1 Proses Penyaluran Tenaga Listrik Ke Konsumen Didalam dunia kelistrikan sering timbul persoalan teknis, dimana tenaga listrik dibangkitkan pada tempat-tempat tertentu, sedangkan
Lebih terperinciAnalisa Relai Arus Lebih Dan Relai Gangguan Tanah Pada Penyulang LM5 Di Gardu Induk Lamhotma
Yusmartato,Yusniati, Analisa Arus... ISSN : 2502 3624 Analisa Arus Lebih Dan Gangguan Tanah Pada Penyulang LM5 Di Gardu Induk Lamhotma Yusmartato,Yusniati Jurusan Teknik Elektro, Fakultas Teknik, Universitas
Lebih terperinciANALISIS ARUS GANGGUAN HUBUNG SINGKAT PADA PENYULANG 20 KV DENGAN OVER CURRENT RELAY (OCR) DAN GROUND FAULT RELAY (GFR)
JURNAL LOGIC. VOL. 16. NO.1. MARET 2016 46 ANALISIS ARUS GANGGUAN HUBUNG SINGKAT PADA PENYULANG 20 KV DENGAN OVER CURRENT RELAY (OCR) DAN GROUND FAULT RELAY (GFR) I Gusti Putu Arka, Nyoman Mudiana, dan
Lebih terperinciIII PENGUMPULAN DAN PENGOLAHAN DATA
III PENGUMPULAN DAN PENGOLAHAN DATA 3.1. Umum Berdasarkan standard operasi PT. PLN (Persero), setiap pelanggan energi listrik dengan daya kontrak di atas 197 kva dilayani melalui jaringan tegangan menengah
Lebih terperinciANALISA SETTING GROUND FAULT RELAY (GFR) TERHADAP SISTEM PENTANAHAN NETRAL PENYULANG PANDEANLAMPER 06 JTM 20 KV SEMARANG
ANALISA SETTING GROUND FAULT RELAY (GFR) TERHADAP SISTEM PENTANAHAN NETRAL PENYULANG PANDEANLAMPER 06 JTM 20 KV SEMARANG Muhammad Iqbal, Moh Toni Prasetyo, Luqman Assaffat 1) 1) Jurusan Teknik Elektro
Lebih terperinciPENYETELAN RELAY ARUS LEBIH PADA TRANSFORMATOR DAYA 60 MVA DI GARDU INDUK BUKIT ASAM PT. PLN (PERSERO)
PENYETELAN RELAY ARUS LEBIH PADA TRANSFORMATOR DAYA 60 MVA DI GARDU INDUK BUKIT ASAM PT. PLN (PERSERO) LAPORAN AKHIR Disusun Untuk Memenuhi Syarat Menyelesaikan Pendidikan Diploma III Pada Jurusan Teknik
Lebih terperinciKEMENTRIAN PENDIDIKAN DAN KEBUDAYAAN UNIVERSITAS BRAWIJAYA FAKULTAS TEKNIK JURUSAN TEKNIK ELEKTRO
KEMENTRIAN PENDIDIKAN DAN KEBUDAYAAN UNIVERSITAS BRAWIJAYA FAKULTAS TEKNIK JURUSAN TEKNIK ELEKTRO Jalan MT Haryono 167 Telp& Fax. 0341 554166 Malang 65145 KODE PJ-01 PENGESAHAN PUBLIKASI HASIL PENELITIAN
Lebih terperinciSIMULASI OVER CURRENT RELAY (OCR) MENGGUNAKAN KARATERISTIK STANDAR INVERSE SEBAGAI PROTEKSI TRAFO DAYA 30 MVA ABSTRAK
Simulasi Over Current Relay (OCR) Menggunakan Karateristik Standar Invers. Selamat Meliala SIMULASI OVER CURRENT RELAY (OCR) MENGGUNAKAN KARATERISTIK STANDAR INVERSE SEBAGAI PROTEKSI TRAFO DAYA 30 MVA
Lebih terperinciKOORDINASI SISTEM PROTEKSI OCR DAN GFR TRAFO 60 MVA GI 150 KV JAJAR TUGAS AKHIR
KOORDINASI SISTEM PROTEKSI OCR DAN GFR TRAFO 60 MVA GI 150 KV JAJAR TUGAS AKHIR Diajukan Untuk Memenuhi Tugas dan Syarat-syarat Guna Memperoleh Gelar Sarjana Teknik Jurusan Studi Elektro pada Fakultas
Lebih terperinciBAB 1 PENDAHULUAN. Tahun-tahun belakangan ini, terjadi peningkatan penggunaan komponen
1 BAB 1 PENDAHULUAN 1.1. Latar Belakang Masalah Tahun-tahun belakangan ini, terjadi peningkatan penggunaan komponen elektronika daya baik sebagai beban maupun sebagai alat kontrol yang mengakibatkan bentuk
Lebih terperinciBAB II TINJAUAN PUSTAKA
BAB II TINJAUAN PUSTAKA 2.1 Umum Secara umum suatu sistem tenaga listrik terdiri dari tiga bagian utama, yaitu, pusat pembangkitan listrik, saluran transmisi dan sistem distribusi. Perlu dikemukakan bahwa
Lebih terperinciBAB III LANDASAN TEORI
15 BAB III LANDASAN TEORI Tenaga listrik dibangkitkan dalam Pusat-pusat Listrik seperti PLTA, PLTU, PLTG, PLTP dan PLTD kemudian disalurkan melalui saluran transmisi yang sebelumnya terlebih dahulu dinaikkan
Lebih terperinciANALISA PERHITUNGAN SETTING RELE ARUS LEBIH SEBAGAI PROTEKSI PADA PENYULANG DI GARDU INDUK SUNGAI JUARO PALEMBANG
ANALISA PERHITUNGAN SETTING RELE ARUS LEBIH SEBAGAI PROTEKSI PADA PENYULANG DI GARDU INDUK SUNGAI JUARO PALEMBANG LAPORAN AKHIR Disusun Untuk Memenuhi Syarat Menyelesaikan Pendidikan Diploma III Pada Jurusan
Lebih terperinciANALISA PENYETELAN RELAI GANGGUAN TANAH (GFR) PADA PENYULANG TRAFO 2 30 MVA 70/20 KV DI PT. PLN (PERSERO) GARDU INDUK BOOM BARU PALEMBANG
ANALISA PENYETELAN RELAI GANGGUAN TANAH (GFR) PADA PENYULANG TRAFO 2 30 MVA 70/20 KV DI PT. PLN (PERSERO) GARDU INDUK BOOM BARU PALEMBANG LAPORAN AKHIR Dibuat Untuk Memenuhi Persyaratan Menyelesaikan Pendidikan
Lebih terperinciPENERAPAN PELEPASAN BEBAN LEBIH (OLS) PADA TRANSFORMATOR DAYA 30 MVA 70/20 kv DI GARDU INDUK BOOM BARU PT. PLN (PERSERO)
PENERAPAN PELEPASAN BEBAN LEBIH (OLS) PADA TRANSFORMATOR DAYA 30 MVA 70/20 kv DI GARDU INDUK BOOM BARU PT. PLN (PERSERO) LAPORAN AKHIR Dibuat Untuk Memenuhi Syarat Menyelesaikan Pendidikan Diploma III
Lebih terperinciBAB II LANDASAN TEORI 2.1 Sistem Distribusi Tenaga Listrik
BAB II LANDASAN TEORI 2.1 Sistem Distribusi Tenaga Listrik Energi listrik disalurkan melalui penyulang-penyulang yang berupa saluran udara atau saluran kabel tanah. Pada penyulang distribusi ini terdapat
Lebih terperinciKata kunci hubung singkat, recloser, rele arus lebih
ANALSS KOORDNAS RELE ARUS LEBH DAN PENUTUP BALK OTOMATS (RECLOSER) PADA PENYULANG JUNREJO kv GARDU NDUK SENGKALNG AKBAT GANGGUAN ARUS HUBUNG SNGKAT Mega Firdausi N¹, Hery Purnomo, r., M.T.², Teguh Utomo,
Lebih terperinciANALISIS GANGGUAN HUBUNG SINGKAT TRAFO TENAGA 60 MVA SHORT CIRCUIT ANALYSIS OF POWER TRANSFORMER 60 MVA
Techno, ISSN 1410-8607 Volume 16 No. 2, Oktober 2015 Hal. 125 130 ANALISIS GANGGUAN HUBUNG SINGKAT TRAFO TENAGA 60 MVA SHORT CIRCUIT ANALYSIS OF POWER TRANSFORMER 60 MVA Eka Purwito dan Fitrizawati* Program
Lebih terperinciBAB I PENDAHULUAN. A. Latar Belakang Masalah
BAB I PENDAHULUAN A. Latar Belakang Masalah Sistem transmisi memegang peranan yang sangat penting dalam proses penyaluran daya. Oleh karena itu pengaman pada saluran transmisi perlu mendapat perhatian
Lebih terperinciBAB III SISTEM PROTEKSI DENGAN RELAI JARAK. terutama untuk masyarakat yang tinggal di kota-kota besar. Kebutuhan tenaga
BAB III SISTEM PROTEKSI DENGAN RELAI JARAK 3.1. Umum Tenaga listrik merupakan suatu kebutuhan pokok dalam kehidupan manusia, terutama untuk masyarakat yang tinggal di kota-kota besar. Kebutuhan tenaga
Lebih terperinciTUGAS AKHIR ANALISA DAN SOLUSI KEGAGALAN SISTEM PROTEKSI ARUS LEBIH PADA GARDU DISTRIBUSI JTU5 FEEDER ARSITEK
TUGAS AKHIR ANALISA DAN SOLUSI KEGAGALAN SISTEM PROTEKSI ARUS LEBIH PADA GARDU DISTRIBUSI JTU5 FEEDER ARSITEK Diajukan guna melengkapi sebagian syarat dalam mencapai gelar Sarjana Strata Satu (S1) Disusun
Lebih terperinciPenentuan Kapasitas CB Dengan Analisa Hubung Singkat Pada Jaringan 70 kv Sistem Minahasa
1 Penentuan Kapasitas CB Dengan Analisa Hubung Singkat Pada Jaringan 70 kv Sistem Minahasa Filia Majesty Posundu, Lily S. Patras, ST., MT., Ir. Fielman Lisi, MT., dan Maickel Tuegeh, ST., MT. Jurusan Teknik
Lebih terperinciEVALUASI KERJA AUTO RECLOSE RELAY TERHADAP PMT APLIKASI AUTO RECLOSE RELAY PADA TRANSMISI 150 KV MANINJAU PADANG LUAR
EVALUASI KERJA AUTO RECLOSE RELAY TERHADAP PMT APLIKASI AUTO RECLOSE RELAY PADA TRANSMISI 150 KV MANINJAU PADANG LUAR Edo Trionovendri (1), Ir. Cahayahati, M.T (2), Ir. Ija Darmana, M.T (3) (1) Mahasiswa
Lebih terperinciBAB IV ANALISA DAN PEMBAHASAN
BAB IV ANALISA DAN PEMBAHASAN 4.1 Studi Kasus Gambar 4.1 Ilustrasi studi kasus Pada tahun 2014 telah terjadi gangguan di sisi pelanggan gardu JTU5 yang menyebabkan proteksi feeder Arsitek GI Maximangando
Lebih terperinciJl. Prof. Sudharto, Tembalang, Semarang, Indonesia Abstrak
Makalah Seminar Kerja Praktek PRINSIP KERJA DAN DASAR RELE ARUS LEBIH PADA PT PLN (PERSERO) PENYALURAN DAN PUSAT PENGATURAN BEBAN REGION JAWA TENGAH DAN DIY Fa ano Hia. 1, Ir. Agung Warsito, DHET. 2 1
Lebih terperinciKOORDINASI RELE ARUS LEBIH DI GARDU INDUK BUKIT SIGUNTANG DENGAN SIMULASI (ETAP 6.00)
JURNAL MEDIA TEKNIK VOL. 8, NO.3: 2011 KOORDINASI RELE ARUS LEBIH DI GARDU INDUK BUKIT SIGUNTANG DENGAN SIMULASI (ETAP 6.00) KASMIR Staf Pengajar Program Studi Teknik Listrik Politeknik Negeri Sriwijaya
Lebih terperinciAnalisis Setting Relay Proteksi Pengaman Arus Lebih Pada Generator (Studi Kasus di PLTU 2X300 MW Cilacap)
Analisis Setting Relay Proteksi Pengaman Arus Lebih Pada Generator (Studi Kasus di PLTU 2X300 MW Cilacap) Fitrizawati 1, Siswanto Nurhadiyono 2, Nur Efendi 3 1,2,3 Program Studi Teknik Elektro Sekolah
Lebih terperinci14 Teknologi Elektro, Vol. 16, No. 02, Mei - Agustus Z 2eq = Impedansi eqivalen urutan negatif
Teknologi Elektro, Vol. 16, No. 02, Mei - Agustus 2017 13 Studi Analisis Kapasitas Pengaman Kopel dalam Mensuplai Daya di Bandara Internasional Ngurah Rai Saat Hilangnya Suplai Daya Dari Gayatri atau Bandara
Lebih terperinciANALISA SISTEM PENGAMAN TRAFO DAYA 60 MVA MENGGUNAKAN RELE ARUS LEBIH DI GARDU INDUK TALANG KELAPA PT. PLN (PERSERO)
ANALISA SISTEM PENGAMAN TRAFO DAYA 60 MVA MENGGUNAKAN RELE ARUS LEBIH DI GARDU INDUK TALANG KELAPA PT. PLN (PERSERO) LAPORAN AKHIR Dibuat untuk Memenuhi Syarat Menyelesaikan Pendidikan Diploma III Jurusan
Lebih terperinciPoliteknik Negeri Sriwijaya BAB II TINJAUAN PUSTAKA
BAB II TINJAUAN PUSTAKA 2.1 Gardu Induk Gardu induk adalah sub sistem dari sistem penyaluran (tranmisi) tenaga listrik, atau merupakan satu kesatuan dari sistem penyaluran, gardu induk memiliki peran yang
Lebih terperinciBAB I PENDAHULUAN. menyalurkan tenaga listrik dari sumber daya listrik besar sampai ke konsumen.
BAB I PENDAHULUAN 1.1 Latar Belakang Di dalam penggunaan daya listrik, mutlak dibutuhkan sistem distribusi. Sistem distribusi merupakan bagian dari sistem tenaga listrik yang berguna untuk menyalurkan
Lebih terperinciAnalisis Sistem Koordinasi OCR pada Gardu Induk Sukolilo
Analisis Sistem Koordinasi OCR pada Gardu Induk Sukolilo ANALISIS SISTEM KOORDINASI OVER CURRENT RELAY (OCR) PADA GARDU INDUK (GI) 150 kv SUKOLILO Fendy Gilang Hernantyo S1 Teknik Elektro, Fakultas Teknik,
Lebih terperinciBAB III PENGAMANAN TRANSFORMATOR TENAGA
41 BAB III PENGAMANAN TRANSFORMATOR TENAGA 3.1 Pengamanan Terhadap Transformator Tenaga Sistem pengaman tenaga listrik merupakan sistem pengaman pada peralatan - peralatan yang terpasang pada sistem tenaga
Lebih terperinciSTUDI PERENCANAAN KOORDINASI RELE PROTEKSI PADA SALURAN UDARA TEGANGAN TINGGI GARDU INDUK GAMBIR LAMA - PULOMAS SKRIPSI
STUDI PERENCANAAN KOORDINASI RELE PROTEKSI PADA SALURAN UDARA TEGANGAN TINGGI GARDU INDUK GAMBIR LAMA - PULOMAS SKRIPSI Oleh ADRIAL MARDENSYAH 04 03 03 004 7 DEPARTEMEN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS
Lebih terperinciBAB IV ANALISIA DAN PEMBAHASAN. 4.1 Koordinasi Proteksi Pada Gardu Induk Wonosobo. Gardu induk Wonosobo mempunyai pengaman berupa OCR (Over Current
BAB IV ANALISIA DAN PEMBAHASAN 4.1 Koordinasi Proteksi Pada Gardu Induk Wonosobo Gardu induk Wonosobo mempunyai pengaman berupa OCR (Over Current Relay) dan Recloser yang dipasang pada gardu induk atau
Lebih terperinciSTUDI PENGARUH SETTING RELE PENGAMAN UNTUK MEMINIMALKAN GANGGUAN SYMPATHETIC TRIP PADA PENYULANG BUNISARI - SUWUNG
Teknologi Elektro, Vol. 15, No.2, Juli - Desember 2016 53 STUDI PENGARUH SETTING RELE PENGAMAN UNTUK MEMINIMALKAN GANGGUAN SYMPATHETIC TRIP PADA PENYULANG BUNISARI - SUWUNG I Komang Anom Astana Ady 1,
Lebih terperinciBAB II TINJAUAN PUSTAKA
5 BAB II TINJAUAN PUSTAKA 2.1 Dasar-Dasar Sistem Proteksi 1 Sistem proteksi adalah pengaman listrik pada sistem tenaga listrik yang terpasang pada : sistem distribusi tenaga listrik, trafo tenaga, transmisi
Lebih terperinciBAB I PENDAHULUAN 1.1 Latar Belakang
BAB I PENDAHULUAN 1.1 Latar Belakang Sistem transmisi memegang peranan yang sangat penting dalam proses penyaluran daya listrik. Oleh karena itu pengaman pada saluran transmisi perlu mendapat perhatian
Lebih terperinciBAB II TINJAUAN PUSTAKA
BAB II TINJAUAN PUSTAKA 2.1 Dasar Dasar Sistem Proteksi Suatu sistem t`enaga listrik dibagi ke dalam seksi-seksi yang dibatasi oleh PMT. Tiap seksi memiliki relai pengaman dan memiliki daerah pengamanan
Lebih terperinciAnalisis Sistem Pengaman Arus Lebih pada Penyulang Abang Akibat Beroperasinya PLTS pada Saluran Distribusi Tegangan Listrik 20 Kv di Karangasem
Teknologi Elektro, Vol. 16, 1, Januari-April 2017 61 Analisis Sistem Pengaman Arus Lebih pada Penyulang Abang Akibat Beroperasinya PLTS pada Saluran Distribusi Tegangan Listrik 20 Kv di Karangasem Made
Lebih terperinciBAB II LANDASAN TEORI
BAB II LANDASAN TEORI 2.1 Gardu Distribusi Gardu distribusi adalah suatu bangunan gardu listrik yang terdiri dari instalasi PHB-TM (Perlengkapan Hubung Bagi Tegangan Menengah), TD (Transformator Distribusi),
Lebih terperinciBAB III GANGGUAN PADA JARINGAN LISTRIK TEGANGAN MENENGAH DAN SISTEM PROTEKSINYA
BAB GANGGUAN PADA JARNGAN LSTRK TEGANGAN MENENGAH DAN SSTEM PROTEKSNYA 3.1 Gangguan Pada Jaringan Distribusi Penyebab utama terjadinya pemutusan saluran distribusi tenaga listrik adalah gangguan pada sistem
Lebih terperinciBAB II TINJAUAN PUSTAKA. terhadap kondisi abnormal pada operasi sistem. Fungsi pengaman tenaga listrik antara lain:
5 BAB II TINJAUAN PUSTAKA 2.1 Sistem Pengaman 2.1.1 Pengertian Pengaman Sistem pengaman tenaga listrik merupakan sistem pengaman pada peralatan yang terpasang pada sistem tenaga listrik seperti generator,
Lebih terperinciJurusan Teknik Elektro Fakultas Teknologi Industri Institut Teknologi Sepuluh Nopember Surabaya
Jurusan Teknik Elektro Fakultas Teknologi Industri Institut Teknologi Sepuluh Nopember Surabaya Tujuan Melakukan analisis terhadap sistem pengaman tenaga listrik di PT.PLN (PERSERO) Melakukan evaluasi
Lebih terperinciI GEDE AGUS YOGA ARMIKA
SKRIPSI STUDI ANALISIS KAPASITAS PENGAMAN KOPEL DALAM MENSUPLAI DAYA DI BANDARA INTERNASIONAL NGURAH RAI SAAT HILANGNYA SUPLAI DAYA DARI PENYULANG GAYATRI ATAU PENYULANG BANDARA I GEDE AGUS YOGA ARMIKA
Lebih terperinciAnalisis Koordinasi Sistem Pengaman Incoming dan Penyulang Transformator 3 di GI Sukolilo Surabaya
Analisis Koordinasi Sistem Pengaman Incoming dan Penyulang Transformator 3 di GI Sukolilo Surabaya Eka Setya Laksana Fakultas Teknologi Industri, Jurusan Teknik Elektro Institut Teknologi Sepuluh Nopember
Lebih terperinciBAB I PENDAHULUAN Latar Belakang
BAB I PENDAHULUAN 1.1. Latar Belakang Dewasa ini, dimana listrik sudah berkembang menjadi salah satu kebutuhan primer masyarakat dan menuntut PT.PLN (Persero) untuk dapat memenuhi kebutuhan terhadap listrik
Lebih terperinciANALISA SETTING RELE ARUS LEBIH PADA PENYULANG KURMA DI GARDU INDUK BOOM BARU PT. PLN (PERSERO)
ANALISA SETTING RELE ARUS LEBIH PADA PENYULANG KURMA DI GARDU INDUK BOOM BARU PT. PLN (PERSERO) LAPORAN AKHIR Dibuat Untuk Memenuhi Persyaratan Menyelesaikan Pendidikan Diploma III Pada Jurusan Teknik
Lebih terperinciSTUDI PENGARUH UPRATING SALURAN TRANSMISI TEGANGAN TINGGI 150 kv TERHADAP SETTING RELE JARAK ANTARA GI KAPAL GI PADANG SAMBIAN GI PESANGGARAN
STUDI PENGARUH UPRATING SALURAN TRANSMISI TEGANGAN TINGGI 150 kv TERHADAP SETTING RELE JARAK ANTARA GI KAPAL GI PADANG SAMBIAN GI PESANGGARAN Supriana S.K. 1, Dyana Arjana, I.G. 2, Amrita, A.A.N. 3 1,2,3
Lebih terperinciANALISIS TEORITIS PENEMPATAN TRANSFORMATOR DISTRIBUSI MENURUT JATUH TEGANGAN DI PENYULANG BAGONG PADA GARDU INDUK NGAGEL
Analisis Teoritis Penempatan Transformator Distribusi Menurut Jatuh Tegangan Di Penyulang Bagong ANALISIS TEORITIS PENEMPATAN TRANSFORMATOR DISTRIBUSI MENURUT JATUH TEGANGAN DI PENYULANG BAGONG PADA GARDU
Lebih terperinciBAB III SISTEM PROTEKSI JARINGAN DISTRIBUSI
BAB III SISTEM PROTEKSI JARINGAN DISTRIBUSI 3.1 Umum Sebaik apapun suatu sistem tenaga dirancang, gangguan pasti akan terjadi pada sistem tenaga tersebut. Gangguan ini dapat merusak peralatan sistem tenaga
Lebih terperinciANALISIS SETTING RELE OGS SEBAGAI SISTEM PENGAMAN TRANSFORMATOR 3 UNTUK MENJAGA KONTINYUITAS ALIRAN DAYA DI GARDU INDUK PESANGGARAN
E-Journal SPEKTRUM Vol. 4, No. 2 Desember 2017 ANALISIS SETTING RELE OGS SEBAGAI SISTEM PENGAMAN TRANSFORMATOR 3 UNTUK MENJAGA KONTINYUITAS ALIRAN DAYA DI GARDU INDUK PESANGGARAN I Wayan Alit Wigunawan
Lebih terperinciANALISIS PERENCANAAN KETERJAMINAN ALIRAN DAYA DAN BIAYA PRODUKSI PLN SUB REGION BALI TAHUN TESIS
ANALISIS PERENCANAAN KETERJAMINAN ALIRAN DAYA DAN BIAYA PRODUKSI PLN SUB REGION BALI TAHUN 2008-2017 TESIS Oleh: ADI PURWANTO 06 06 00 30 64 PROGRAM STUDI TEKNIK ELEKTRO PROGRAM PASCASARJANA BIDANG ILMU
Lebih terperinci1 BAB II TINJAUAN PUSTAKA
1 BAB II TINJAUAN PUSTAKA 1.1 Teori Umum Proteksi adalah pengaman listrik pada sistem tenaga listrik yang terpasang pada sistem distribusi tenaga listrik. Tujuan utama dari suatu sistem tenaga listrik
Lebih terperinciBAB 2 TINJAUAN PUSTAKA
BAB 2 TINJAUAN PUSTAKA 2.1 Distributed Generation Distributed Generation adalah sebuah pembangkit tenaga listrik yang bertujuan menyediakan sebuah sumber daya aktif yang terhubung langsung dengan jaringan
Lebih terperinciPENGGUNAAN RELE DIFFERENSIAL PADA TRANSFORMATOR DAYA 20 MVA DI GARDU INDUK SUNGAI JUARO
PENGGUNAAN RELE DIFFERENSIAL PADA TRANSFORMATOR DAYA 20 MVA DI GARDU INDUK SUNGAI JUARO LAPORAN AKHIR Dibuat Untuk Memenuhi Syarat Menyelesaikan Pendidikan Diploma III Pada Jurusan Teknik Elektro Program
Lebih terperinciKOORDINASI RELAY PENGAMAN DAN LOAD FLOW ANALYSIS MENGGUNAKAN SIMULASI ETAP 7.0 PT. KRAKATAU STEEL (PERSERO) TBK
Makalah Seminar Kerja Praktek KOORDINASI RELAY PENGAMAN DAN LOAD FLOW ANALYSIS MENGGUNAKAN SIMULASI ETAP 7.0 PT. KRAKATAU STEEL (PERSERO) TBK Oktarico Susilatama PP 1, Ir. Agung Warsito, DHET 2 1 Mahasiswa
Lebih terperinciSTUDI KOORDINASI RELE PENGAMAN PADA SISTEM BUSBAR DI GARDU INDUK KAPAL
SKRIPSI STUDI KOORDINASI RELE PENGAMAN PADA SISTEM BUSBAR DI GARDU INDUK KAPAL I GUSTI NGURAH AGUNG BUDI HARTA YOGA JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS UDAYANA BUKIT JIMBARAN 2015 SKRIPSI
Lebih terperinciBAB IV ANALISA GANGGUAN DAN IMPLEMENTASI RELAI OGS
BAB IV ANALISA GANGGUAN DAN IMPLEMENTASI RELAI OGS 4.1 Gangguan Transmisi Suralaya Balaraja Pada Pembangkit PLTU Suralaya terhubung dengan sistem 500KV pernah mengalami gangguan CT (Current Transformer)
Lebih terperinciBAB II LANDASAN TEORI
BAB II LANDASAN TEORI 2.1 Dasar Koordinasi Proteksi Pada Sistem Kelistrikan Keandalan dan kemampuan suatu sistem tenaga listrik dalam melayani konsumen sangat tergantung pada sistem proteksi yang digunakan.
Lebih terperinciBAB I PENDAHULUAN. menyalurkan energi listrik dengan gangguan pemadaman yang minimal.
BAB I PENDAHULUAN 1.1 LATAR BELAKANG Kebutuhan energi listrik terus meningkat dari tahun ke tahun. Hal ini tentu saja menuntut PLN guna meningkatkan pasokan tenaga listrik. Di dalam penyaluran energi listrik,
Lebih terperinciESTIMASI PEMBEBANAN TRANSFORMATOR GARDU INDUK 150 KV
ISSN: 085 645 99 ESTIMASI PEMBEBANAN TRANSFORMATOR GARDU INDUK 150 KV Elias K. Bawan 1, DiahSuwarti W. 1 Staf Pengajar Teknik Elektro Universitas Negeri Papua elias_kondorura@yahoo.com Jurusan Teknik Elektro
Lebih terperinciBAB III GANGGUAN SIMPATETIK TRIP PADA GARDU INDUK PUNCAK ARDI MULIA. Simpatetik Trip adalah sebuah kejadian yang sering terjadi pada sebuah gardu
BAB III GANGGUAN SIMPATETIK TRIP PADA GARDU INDUK PUNCAK ARDI MULIA 3.1. Pengertian Simpatetik Trip adalah sebuah kejadian yang sering terjadi pada sebuah gardu induk, dimana pemutus tenaga dari penyulang-penyulang
Lebih terperinciSukamerindu, Switchyard Musi dan Switchyard Tess (Bengkulu). I.PENDAHULUAN 1.1 Latar Belakang
Makalah Seminar Kerja Praktek PENERAPAN RELAY OLS PADA TRAFO TD 3 # 30 MVA G SUKAMERNDU BENGKULU DENGAN SENSNG ARUS PRMER 70KV UNTUK MENTRPKAN PENYULANG 20 KV Rio Parohon T. Tambunan (L2F 009 024) Email:
Lebih terperinciBAB III SISTEM KELISTRIKAN DAN PROTEKSI
BAB III SISTEM KELISTRIKAN DAN PROTEKSI 3.1 Generator dan Transformator Unit Generator Suatu alat listrik yang merubah energi gerak berupa putaran dari turbin yang dipasang seporos dengan generator, kemudian
Lebih terperinciBAB II LANDASAN TEORI
BAB II LANDASAN TEORI 2.1. Relai Proteksi Relai proteksi atau relai pengaman adalah susunan peralatan yang berfungsi untuk mendeteksi atau merasakan adanya gangguan atau mulai merasakan adanya ketidak
Lebih terperinciAnalisa Stabilitas Transien dan Koordinasi Proteksi pada PT. Linde Indonesia Gresik Akibat Penambahan Beban Kompresor 4 x 300 kw
Analisa Stabilitas Transien dan Koordinasi Proteksi pada PT. Linde Indonesia Gresik Akibat Penambahan Beban Kompresor 4 x 300 kw Nama : Frandy Istiadi NRP : 2209 106 089 Pembimbing : 1. Dr. Ir. Margo Pujiantara,
Lebih terperinciPOLITEKNIK NEGERI SRIWIJAYA BAB I PENDAHULUAN
BAB I PENDAHULUAN 1.1 Latar Belakang Dalam operasi pelayanan penyediaan energi listrik khususnya di GI Bungaran, sistem tenaga listrik dapat mengalami berbagai macam gangguan, misal gangguan dari hubung
Lebih terperinciAnalisa Koordinasi Rele Pengaman Transformator Pada Sistem Jaringan Kelistrikan di PLTD Buntok
Analisa Koordinasi Rele Pengaman Transformator Pada Sistem Jaringan Kelistrikan di PLTD Buntok Yusuf Ismail Nakhoda, Awan Uji Krismanto, dan Maskur Usmanto Jurusan Teknik Elektro, Institut Teknologi Nasional
Lebih terperincidalam sistem sendirinya dan gangguan dari luar. Penyebab gangguan dari dalam
6 Penyebab gangguan pada sistem distribusi dapat berasal dari gangguan dalam sistem sendirinya dan gangguan dari luar. Penyebab gangguan dari dalam antara lain: 1 Tegangan lebih dan arus tak normal 2.
Lebih terperinciBAB III GANGGUAN PADA JARINGAN LISTRIK TEGANGAN MENENGAH
BAB III GANGGUAN PADA JARINGAN LISTRIK TEGANGAN MENENGAH 3.1 KOMPONEN KOMPONEN SIMETRIS Tiga fasor tak seimbang dari sistem fasa tiga dapat diuraikan menjadi tiga sistem fasor yang seimbang. Himpunan seimbang
Lebih terperinciBAB III LANDASAN TEORI
BAB III LANDASAN TEORI 3.1 Sistem Distribusi Tenaga Listrik Sistem Tenaga Listrik adalah sistem penyediaan tenaga listrik yang terdiri dari beberapa pembangkit atau pusat listrik terhubung satu dengan
Lebih terperinciBAB III METODOLOGI PENELITIAN
BAB III METODOLOGI PENELITIAN 3.1 Desain Penelitian Berdasarkan data PLN APB Jawa Barat tahun 2014, subsistem Cirata 150 kv disuplai oleh dua unit IBT 500 MVA pada tegangan 500/150 kv di Gardu Induk Tegangan
Lebih terperinciMakalah Seminar Tugas Akhir. Judul
1 Judul ANALISA PENGGUNAAN ECLOSE 3 PHASA 20 KV UNTUK PENGAMAN AUS LEBIH PADA SUTM 20 KV SISTEM 3 PHASA 4 KAWAT DI PT. PLN (PESEO) APJ SEMAANG Disusun oleh : Kunto Herwin Bono NIM : L2F 303513 Jurusan
Lebih terperinciAnalisa Setting Rele Arus Lebih dan Rele Gangguan Tanah pada Penyulang Topan Gardu Induk Teluk Betung
ELECTRICIAN Jurnal Rekayasa dan Teknologi Elektro Analisa Setting Rele Arus Lebih dan Rele Gangguan Tanah pada Penyulang Topan Gardu Induk Teluk Betung Ade Wahyu Hidayat Herri Gusmedi Lukmanul Hakim Dikpride
Lebih terperinciPEMASANGAN KAPASITOR BANK UNTUK PERBAIKAN FAKTOR DAYA PADA PANEL UTAMA LISTRIK GEDUNG FAKULTAS TEKNIK UNIVERSITAS IBN KHALDUN BOGOR
PEMASANGAN KAPASITOR BANK UNTUK PERBAIKAN FAKTOR DAYA PADA PANEL UTAMA LISTRIK GEDUNG FAKULTAS TEKNIK UNIVERSITAS IBN KHALDUN BOGOR M. Hariansyah 1, Joni Setiawan 2 1 Dosen Tetap Program Studi Teknik Elektro
Lebih terperinciKAJIAN PROTEKSI MOTOR 200 KW,6000 V, 50 HZ DENGAN SEPAM SERI M41
Jurnal ELTEK, Vol 12 Nomor 01, April 2014 ISSN 1693-4024 KAJIAN PROTEKSI MOTOR 200 KW,6000 V, 50 HZ DENGAN SEPAM 1000+ SERI M41 Heri Sungkowo 1 Abstrak SEPAM (System Electronic Protection Automation Measurement)1000+
Lebih terperinciBAB II DASAR TEORI. Sistem proteksi adalah sistem yang memisahkan bagian sistem yang. b. Melepaskan bagian sistem yang terganggu (fault clearing)
BAB II DASAR TEORI 2.1 Sistem Proteksi Panel Tegangan Menegah Sistem proteksi adalah sistem yang memisahkan bagian sistem yang terganggu sehingga bagian sistem lain dapat terus beroperasi dengan cara sebagai
Lebih terperinciJurnal Teknik Elektro ISSN
STUDI ANALISIS PERBANDINGAN RUGI DAYA PADA TITIK SAMBUNG PIERCHING CONNECTOR DENGAN LINE TAP CONNECTOR PADA JARINGAN TEGANGAN RENDAH 220 V DI PT. PLN (PERSERO) RAYON LAMONGAN Ulul Ilmi *), Arief Budi Laksono
Lebih terperinciBAB II LANDASAN TEORI
BAB II LANDASAN TEORI 2.1. Sistem Jaringan Distribusi Sistem Tenaga listrik di Indonesia tersebar dibeberapa tempat, maka dalam penyaluran tenaga listrik dari tempat yang dibangkitkan sampai ke tempat
Lebih terperinciAnalisa Penggunaan Recloser Untuk Pengaman Arus Lebih Pada Jaringan Distribusi 20 kv Gardu Induk Garuda Sakti
Analisa Penggunaan Recloser Untuk Pengaman Arus Lebih Pada Jaringan Distribusi 20 kv Gardu Induk Garuda Sakti Ario Putra*, Firdaus** Jurusan Teknik Elektro Fakultas Teknik Universitas Riau Kampus Bina
Lebih terperinciSIMULASI PROTEKSI DAERAH TERBATAS DENGAN MENGGUNAKAN RELAI OMRON MY4N-J12V DC SEBAGAI PENGAMAN TEGANGAN EKSTRA TINGGI DI GARDU INDUK
Simulasi Proteksi Daerah Terbatas... (Setiono dan Arum) SIMULASI PROTEKSI DAERAH TERBATAS DENGAN MENGGUNAKAN RELAI OMRON MY4N-J12V DC SEBAGAI PENGAMAN TEGANGAN EKSTRA TINGGI DI GARDU INDUK Iman Setiono
Lebih terperinci