ANALISA SETTING GROUND FAULT RELAY (GFR) TERHADAP SISTEM PENTANAHAN NETRAL PENYULANG PANDEANLAMPER 06 JTM 20 KV SEMARANG

dokumen-dokumen yang mirip
KEMENTRIAN PENDIDIKAN DAN KEBUDAYAAN UNIVERSITAS BRAWIJAYA FAKULTAS TEKNIK JURUSAN TEKNIK ELEKTRO

Analisa Koordinasi Over Current Relay Dan Ground Fault Relay Di Sistem Proteksi Feeder Gardu Induk 20 kv Jababeka

KOORDINASI SISTEM PROTEKSI OCR DAN GFR TRAFO 60 MVA GI 150 KV JAJAR TUGAS AKHIR

STUDI PENGARUH SETTING RELE PENGAMAN UNTUK MEMINIMALKAN GANGGUAN SYMPATHETIC TRIP PADA PENYULANG BUNISARI - SUWUNG

2.2.6 Daerah Proteksi (Protective Zone) Bagian-bagian Sistem Pengaman Rele a. Jenis-jenis Rele b.

Analisa Relai Arus Lebih Dan Relai Gangguan Tanah Pada Penyulang LM5 Di Gardu Induk Lamhotma

BAB II TINJAUAN PUSTAKA

BAB IV ANALISIA DAN PEMBAHASAN. 4.1 Koordinasi Proteksi Pada Gardu Induk Wonosobo. Gardu induk Wonosobo mempunyai pengaman berupa OCR (Over Current

BAB V PENUTUP 5.1 Simpulan Saran DAFTAR PUSTAKA LAMPIRAN LAMPIRAN

14 Teknologi Elektro, Vol. 16, No. 02, Mei - Agustus Z 2eq = Impedansi eqivalen urutan negatif

DAFTAR ISI LEMBAR PENGESAHAN PEMBIMBING LEMBAR PERNYATAAN KEASLIAN LEMBAR PENGESAHAN PENGUJI HALAMAN PERSEMBAHAN HALAMAN MOTTO KATA PENGANTAR

EVALUASI SETTING RELAY ARUS LEBIH DAN SETTING RELAY GANGGUAN TANAH PADA GARDU INDUK 150KV BAWEN

POLITEKNIK NEGERI SRIWIJAYA BAB I PENDAHULUAN

Analisa Koordinasi Relay Proteksi Dengan Recloser Pada Penyulang Purbalingga 05 Di PT. PLN (Persero) Rayon Purbalingga

STUDI ANALISIS SETTING BACKUP PROTEKSI PADA SUTT 150 KV GI KAPAL GI PEMECUTAN KELOD AKIBAT UPRATING DAN PENAMBAHAN SALURAN

Dielektrika, [P-ISSN ] [E-ISSN X] 77 Vol. 4, No. 2 : 77-84, Agustus 2017

EVALUASI SETTING RELAY PROTEKSI DAN DROP VOLTAGE PADA GARDU INDUK SRONDOL SEMARANG MENGGUNAKAN ETAP 7.5

KOORDINASI RELAY ARUS LEBIH DAN RECLOSER PADA TRAFO 60 MVA GARDU INDUK PANDEAN LAMPER SEMARANG DENGAN SIMULASI ETAP

BAB I PENDAHULUAN. Pada sistem penyaluran tenaga listrik, kita menginginkan agar pemadaman tidak

Jl. Prof. Sudharto, Tembalang, Semarang, Indonesia Abstrak

STUDI KOORDINASI PERALATAN PROTEKSI OCR & GFR PADA PENYULANG TIBUBENENG

SIMULASI OVER CURRENT RELAY (OCR) MENGGUNAKAN KARATERISTIK STANDAR INVERSE SEBAGAI PROTEKSI TRAFO DAYA 30 MVA ABSTRAK

Studi Analisis Koordinasi Over Current Relay (OCR) dan Ground Fault Relay (GFR) pada Recloser di Saluran Penyulang Penebel

Analisis Sympathetic Trip pada Penyulang Ungasan dan Bali Resort, Bali

LAPORAN TUGAS AKHIR. Oleh: ANGKI PUTRA KURNIAWAN NIM :

Analisis Sympathetic Trip pada Penyulang Ungasan dan Bali Resort, Bali

Gambar 2.1 Skema Sistem Tenaga Listrik (3)

EVALUASI KOORDINASI RELE PENGAMAN PADA JARINGAN DISTRIBUSI 20 KV DI GARDU INDUK GARUDA SAKTI, PANAM-PEKANBARU

BAB II TINJAUAN PUSTAKA. c. Memperkecil bahaya bagi manusia yang ditimbulkan oleh listrik.

KOORDINASI RELAY PENGAMAN DAN LOAD FLOW ANALYSIS MENGGUNAKAN SIMULASI ETAP 7.0 PT. KRAKATAU STEEL (PERSERO) TBK

STUDI PENENTUAN KAPASITAS PEMUTUS TENAGA SISI 20 KV PADA GARDU INDUK SEKAYU

Ground Fault Relay and Restricted Earth Faulth Relay

FEEDER PROTECTION. Penyaji : Ir. Yanuar Hakim, MSc.

KOORDINASI SETTING RELAI ARUS LEBIH PADA INCOMING 2 KUDUS TERHADAP OUTGOING KUDUS 5 DAN 6 YANG MENGGUNAKAN JARINGAN DOUBLE CIRCUIT DI GI 150 KV KUDUS

ANALISIS KOORDINASI RELE PENGAMAN FEEDER WBO04 SISTEM KELISTRIKAN PT. PLN (PERSERO) RAYON WONOSOBO

KOORDINASI RELE ARUS LEBIH DI GARDU INDUK BUKIT SIGUNTANG DENGAN SIMULASI (ETAP 6.00)

ANALISA SETTING RELAI PENGAMAN AKIBAT REKONFIGURASI PADA PENYULANG BLAHBATUH

ANALISA SETTING GROUND FAULT RELAY(GFR) TERHADAP SISTEM PENTANAHAN NETRAL PENYULANG PANDEANLAMPER 06 JTM 20 KV SEMARANG TUGAS AKHIR

20 Teknologi Elektro, Vol. 16, No. 02, Mei - Agustus I Gede Krisnayoga Kusuma 1, I Gede Dyana Arjana 2, I Wayan Arta Wijaya 3

Analisis Koordinasi Sistem Pengaman Incoming dan Penyulang Transformator 3 di GI Sukolilo Surabaya

STUDI PERENCANAAN KOORDINASI RELE PROTEKSI PADA SALURAN UDARA TEGANGAN TINGGI GARDU INDUK GAMBIR LAMA - PULOMAS SKRIPSI

Analisa Setting Rele Arus Lebih dan Rele Gangguan Tanah pada Penyulang Topan Gardu Induk Teluk Betung

Analisis Sistem Pengaman Arus Lebih pada Penyulang Abang Akibat Beroperasinya PLTS pada Saluran Distribusi Tegangan Listrik 20 Kv di Karangasem

STUDI SETTINGAN DISTANCE RELAY PADA SALURAN TRANSMISI 150 KV DI GI PAYAKUMBUH MENGGUNAKAN SOFTWARE MATLAB

ANALISIS RESETTING RECLOSER PADA SALURAN WLI 06 TRAFO 30 MVA 150 KV GARDU INDUK WELERI KENDAL DENGAN SIMULASI ETAP

BAB III METODE PENELITIAN. Universitas Lampung dan PT. PLN (Persero) Cabang Tanjung Karang pada. bulan Maret 2013 sampai dengan selesai.

BAB IV PEMBAHASAN. Gardu Induk Godean berada di jalan Godean Yogyakarta, ditinjau dari

2014 ANALISIS KOORDINASI SETTING OVER CURRENT RELAY

ANALISA PENYETELAN RELAI GANGGUAN TANAH (GFR) PADA PENYULANG TRAFO 2 30 MVA 70/20 KV DI PT. PLN (PERSERO) GARDU INDUK BOOM BARU PALEMBANG

Studi dan Evaluasi Setting Relai Arus Lebih pada Transformator Daya di Gardu Induk Garuda Sakti Pekanbaru

ANALISA KOORDINASI OCR - RECLOSER PENYULANG KALIWUNGU 03

ANALISA KOORDINASI RECLOSER DAN OCR (OVER CURRENT RELAY) UNTUK GANGGUAN HUBUNG SINGKAT PADA PENYULANG 3 DISTRIBUSI 20 KV GI JAJAR

BAB 3 RELE PROTEKSI PADA SALURAN UDARA TEGANGAN TINGGI

ABSTRAK Kata Kunci :

DAFTAR ISI LEMBAR PERNYATAAN KEASLIAN HALAMAN PERSEMBAHAN HALAMAN MOTTO KATA PENGANTAR ABSTRAK DAFTAR GAMBAR DAFTAR TABEL BAB I PENDAHULUAN 1

ANALISIS PERBAIKAN DROP VOLTAGE

Perhitungan Setting Rele OCR dan GFR pada Sistem Interkoneksi Diesel Generator di Perusahaan X

dalam sistem sendirinya dan gangguan dari luar. Penyebab gangguan dari dalam

KAJIAN PROTEKSI MOTOR 200 KW,6000 V, 50 HZ DENGAN SEPAM SERI M41

Sidang Tugas Akhir (Genap ) Teknik Sistem Tenaga Jurusan Teknik Elektro ITS

BAB II GARDU INDUK 2.1 PENGERTIAN DAN FUNGSI DARI GARDU INDUK. Gambar 2.1 Gardu Induk

PERANCANGAN KOORDINASI RELAI ARUS LEBIH PADA GARDU INDUK DENGAN JARINGAN DISTRIBUSI SPINDLE

BAB I PENDAHULUAN. kemajuan teknologi kelistrikan yang menyentuh kehidupan sehari-hari maupun

Vol.17 No.2. Agustus 2015 Jurnal Momentum ISSN : X

PENYETELAN RELAY ARUS LEBIH PADA TRANSFORMATOR DAYA 60 MVA DI GARDU INDUK BUKIT ASAM PT. PLN (PERSERO)

Setting Relai Gangguan Tanah (Gfr) Outgoing Gh Tanjung Pati Feeder Taram Pt. Pln (Persero) Rayon Lima Puluh Kota

ANALISIS ARUS GANGGUAN HUBUNG SINGKAT PADA PENYULANG 20 KV DENGAN OVER CURRENT RELAY (OCR) DAN GROUND FAULT RELAY (GFR)

ANALISIS PENYEBAB KEGAGALAN KERJA SISTEM PROTEKSI PADA GARDU AB

TUGAS AKHIR. SETTING KOORDINASI OVER CURRENT RELAY PADA TRAFO 60 MVA 150/20 kv DAN PENYULANG 20 kv

1 BAB II TINJAUAN PUSTAKA

Makalah Seminar Tugas Akhir. Judul

ANALISA KOORDINASI RECLOSER DAN OCR (OVER CURRENT RELAY) UNTUK HUBUNG SINGKAT PADA PENYULANG 9 DISTRIBUSI 20 KV GI BAWEN

Kata kunci : Gangguan, Sistem Proteksi, Relai.

BAB III GANGGUAN PADA JARINGAN LISTRIK TEGANGAN MENENGAH DAN SISTEM PROTEKSINYA

ANALISA SETTING RELE ARUS LEBIH PADA PENYULANG KURMA DI GARDU INDUK BOOM BARU PT. PLN (PERSERO)

Analisa Perhitungan dan Pengaturan Relai Arus Lebih dan Relai Gangguan Tanah pada Kubikel Cakra 20 KV Di PT XYZ

BAB II TINJAUAN PUSTAKA

ANALISA KOORDINASI PERALATAN PENGAMAN JARINGAN PENYULANG KALIWUNGU 03 SECARA INDEPENDEN SERTA PELIMPAHAN BEBAN DARI PENYULANG WELERI

Analisis Rele Pengaman Peralatan dan Line Transmisi Switchyard GITET Baru 500kV PT PLN (PERSERO) di Kediri

BAB I PENDAHULUAN 1.1 Latar Belakang

BAB I PENDAHULUAN Latar Belakang

REKONFIGURASI JARINGAN DISTRIBUSI TEGANGAN 20 KV PADA FEEDER PANDEAN LAMPER 5 RAYON SEMARANG TIMUR

ANALISA SETTING RELAY GANGGUAN TANAH PADA PENYULANG 20 kv di GARDU INDUK SEDUDUK PUTIH

PERHITUNGAN SETTING RELE ARUS LEBIH PADA TRAFO SISI 20KV DI GARDU INDUK BUKIT ASAM LAPORAN AKHIR

ANALISIS KOORDINASI PROTEKSI PADA PT.PLN (PERSERO) GARDU INDUK WONOSOBO MENGGUNAKAN SOFTWARE APLIKASI ETAP TUGAS AKHIR

ANALISA PERBANDINGAN RELE GANGGUAN TANAH (GFR) PADA GARDU INDUK TALANG RATU

Analisis Gangguan Hubung Singkat untuk Penentuan Breaking Capacity Pada Penyulang Kutai, Ludruk, dan Reog di GIS Gambir Lama

BAB III METODE PENELITIAN

Perencanaan Koordinasi Rele Pengaman Pada Sistem Kelistrikan Di PT. Wilmar Gresik Akibat Penambahan Daya

Kata kunci hubung singkat, recloser, rele arus lebih

Kata kunci : jaringan distribusi spindle; koordinasi proteksi; rele arus lebih

Koordinasi Rele Pada Jaringan Transmisi 150 kv

STUDI KEANDALAN DISTANCE RELAY JARINGAN 150 kv GI TELLO - GI PARE-PARE

EVALUASI SETTING RELAY OCR, GFR DAN RECLOSER PASCA REKONFIGURASI JARINGAN DISTRIBUSI PADA TRAFO 2 GARDU INDUK SRONDOL SEMARANG MENGGUNAKAN ETAP 12.6.

Analisis Koordinasi Sistem Pengaman Incoming dan Penyulang Transformator 3 di GI Sukolilo Surabaya

BAB III METODOLOGI. 3.2 Tahap Pelaksanaan Penyusunan Laporan Akhir

Analisis Koordinasi Rele Arus Lebih Pda Incoming dan Penyulang 20 kv Gardu Induk Sengkaling Menggunakan Pola Non Kaskade

BAB I PENDAHULUAN Latar Belakang

STUDI KOORDINASI RELE PENGAMAN PADA SISTEM BUSBAR DI GARDU INDUK KAPAL

Analisis Setting Relay Proteksi Pengaman Arus Lebih Pada Generator (Studi Kasus di PLTU 2X300 MW Cilacap)

Transkripsi:

ANALISA SETTING GROUND FAULT RELAY (GFR) TERHADAP SISTEM PENTANAHAN NETRAL PENYULANG PANDEANLAMPER 06 JTM 20 KV SEMARANG Muhammad Iqbal, Moh Toni Prasetyo, Luqman Assaffat 1) 1) Jurusan Teknik Elektro Fakultas Teknik Universitas Muhammadiyah Semarang Jl. Kasipah no 10-12 Semarang Indonesia e-mail : Iqbalkharisma30@gmail.com ABSTRACT The operation of the distribution system has major problems in overcoming interference. In its development, electric power systems increasingly large currents cause electrical interference that may occur the greater. Therefore, they invented a system called neutral grounding.there is no ideal grounding neutral earthing throughout the distribution network Semarang cause neutral grounding resistance value. Neutral resistance values may cause a decrease in current flowing to ground disturbance that affects the sensitivity GFR (Ground Foult Relay) installed. Because of that, necessary to analyze the GFR setting the main feeder neutral earthing systems JTM 20 kv feeders Semarang by taking samples Pandealamper 06 to determine the condition of setting GFR installed in accordance with the neutral earthing systems.results of the calculation of the noise current by entering the value of resistance neutral earthing exiting GFR values obtained ideal setting on the feeder Pandeanlamper 06 is not much different from the existing GFR setting value. Values of 0.27 Ω neutral earthing (existing) did not significantly influence the sensitivity GFR of the feeder PDL 06.GFR remained detect interference and work in accordance with the characteristic curve GFR.Based on the analysis, GFR mounted setting was appropriate and able to provide security in Pandeanlamper feeder 06.. Keywords: Neutral Grounding, GFR, Main Feeder 1. PENDAHULUAN Pengoperasian sistem distribusi mempunyai masalah utama dalam mengatasi gangguan. Dalam perkembangannya,sistem tenaga listrik yang semakin besar menyebabkan arus gangguan listrik yang mungkin terjadi semakin besar. Oleh sebab itu dibuatlah suatu sistem yang disebut pentanahan netral. Adanya Ketidakidealan pentanahan netral sepanjang jaringan distribusi Semarang menyebabkan nilai tahanan pentanahan netral. Nilai tahanan netral tersebut dapat menyebabkan penurunan arus gangguan ke tanah yang mengalir sehingga berdampak pada sensitivitas GFR yang dipasang Marsudi, (Djiteng, 2006). Oleh karena itu perlu dilakukan peninjauan pentanahan netral sistem distribusi wilayah Semarang dengan memasukkan nilai tahanan pentanahan netral yang sesungguhnya guna memastikan setting GFR penyulang utama yang dipasang mampu mengatasi semua gangguan yang mungkin terjadi di sistem tanpa membahayakan keselamatan makhluk Analisa Setting Ground Fault... 1

hidup yang ada di sekitar dan tanpa merusak peralatan yang terpasang di sistem (Tobing B, 2003). Adapun penyulang PDL06 dipilih untuk mewakili penyulang lain di wilayah distribusi Semarang 2. RUMUSAN MASALAH Dengan adanya Ketidakidealan pentanahan netral sepanjang jaringan distribusi Semarang yang dapat mempengaruhi sensitivitas Ground Foult Relay (GFR) yang terpasang pada penyulang utama PDL06 maka diperlukan analisa terhadap setting GFR yang terpasang sesuai dengan sistem pentanahan netral dan mampu memberikan pengamanan pada penyulang PDL06 (Suhadi, dkk. 2008). 3. METODE PENELITIAN DIAGRAM ALIR PENELITIAN Mulai Studi pustaka Identifikasi dan pengumpulan data: 1. Konfigurasi jaringan 2. Pentanahan netral sistem distribusi 3. Setting GFR PMT dan PBO Perhitungan Setting GFR pada sistem distribusi Analisa pengaruh pentanahan netral sistem terhadap Setting GFR PMT&PBO Kesesuaian pentanahan netral sistem terhadap GFR Ya Kesimpulan Tidak Rekomendasi Selesai Gambar 1 Diagram alir proses penelitian 4. HASIL DAN PEMBAHASAN Pentanahan netral sistem distribusi penyulang PDL06 menggunakan metode pentanahan langsung sepanjang jaringan, dimana nilai pentanahan netral tidak murni nol melainkan sebesar 0,27 Ω. Pada penyulang utama JTM 20 kv Pandeanlamper 06 terdapat dua relai GFR yaitu relai GFR PMT (Pemutus Tenaga) dan GFR PBO (Penutup Balik Otomatis). Koordinasi antara rele gangguan tanah PMT dan PBO dilakukan secara time and current grading. Masing-masing rele dilengkapi dengan fasilitas penyetelan waktu kerja (Time Multiplier Setting/ TMS) dan penyetelan arus kerja minimum. Adapun setting karakteristik kurva waktu yang diterapkan pada GFR PMT dan PBO penyulang PDL06 adalah Standard Inverse. I. Perhitungan Setting GFR PMT dan PBO pada Penyulang PDL06 a. Setting GFR PMT Setting arus GFR (Is GFR) PMT pada penyulang PDL06 sebesar 180A. Setting waktu tunda GFR PMT penyulang PDL06 menggunakan karakteristik Standard Inverse dan TMS 0,24 (Ravindranath, B; Chander, M. 1983). 2 Muhammad Iqbal, Moh Toni Prasetyo, Luqman Assaffat

360 540 720 900 1080 1260 1440 1620 1800 1980 Media Elektrika, Vol. 9, No. 1, Juni 2016 ISSN 1979-7451 Rumus waktu tunda GFR PMT penyulang PDL06 sebagai berikut: Time to trip (td) = 0,14 [ I hs Iset ] 0,02 1 0,24 0,14 Time to trip (td) = [ I 0,02 0,1 hs ] 1 I set 3,00 2,50 2,00 1,50 1,00 0,50 0,00 1,2 1 0,8 0,6 0,4 0,2 Gambar 2. Kurva koordinasi karakteristik kerja GFR dari PMT Selain disetting untuk bekerja dengan tunda waktu Standard Inverse, GFR PMT penyulang PDL06 juga dikombinasikan untuk bekerja seketika atau tanpa tunda waktu. Adapun setting arus instantaneous (Iins) GFR PMT penyulang PDL06 sebesar 7 x Iset GFR = 1260A. b. Setting GFR PBO Setting arus GFR (Is GFR) PBO pada penyulang PDL06 sebesar 110A. Setting waktu tunda GFR PBO penyulang PDL06 menggunakan karakteristik Standard Inverse dan TMS 0,1. dapat diketahui rumus waktu tunda GFR PBO penyulang PDL06 sebagai berikut: 0 Gambar 3. Kurva koordinasi karakteristik kerja GFR dari PBO Selain disetting untuk bekerja dengan tunda waktu Standard Inverse, GFR PBO penyulang PDL06 juga dikombinasikan untuk bekerja seketika atau tanpa tunda waktu. Adapun setting arus instantaneous (Iins) GFR PBO penyulang PDL06 sebesar 8 x Iset GFR = 880 A. II. Kurva Koordinasi Karakteristik Kerja GFR PMT dan PBO GFR PBO berfungsi sebagai rele utama yang mengamankan bagian hilir penyulang utama dari gangguan tanah. Sedangkan GFR PMT berfungsi sebagai rele utama yang mengamankan bagian hulu penyulang utama sekaligus sebagai rele back-up bagian hilir penyulang utama. Dari Analisa Setting Ground Fault... 3

Waktu kerja (detik) Media Elektrika, Vol. 9, No. 1, Juni 2016 ISSN 1979-7451 Gambar 3 terlihat bahwa terjadi koordinasi antara kerja GFR PMT dan PBO melalui setting arus dan setting waktu kerja (TMS). Setting TMS GFR PMT yang lebih tinggi dari GFR PBO menyebabkan GFR PMT tidak trip bersama-sama dengan GFR PBO apabila terjadi gangguan di bagian hilir dimana nilai arus gangguan tidak terlalu besar. Sistem pengaman gangguan tanah pun menjadi selektif dan dapat membatasi luas daerah yang padam akibat gangguan. Selain itu GFR juga disetting untuk bekerja seketika untuk mengatasi arus gangguan ke tanah yang bernilai sangat besar penghantar maupun peralatan tidak rusak ketika gangguan terjadi. 100,00 10,00 Kurva koordinasi GFR PMT dan PBO Rele gangguan tanah PMT Rele gangguan tanah PBO Gambar 4. Kurva koordinasi karakteristik kerja GFR dari PMT dan PBO 4. KESIMPULAN 1. Pentanahan netral sistem distribusi penyulang PDL06 menggunakan metode pentanahan langsung sepanjang jaringan, dimana nilai pentanahan netral tidak murni nol melainkan sebesar 0,27 Ω. 2. Nilai pentanahan netral sebesar 0,27 Ω (kondisi existing) tidak berpengaruh signifikan terhadap sensitivitas GFR pada penyulang PDL 06. GFR tetap mendeteksi gangguan dan bekerja sesuai dengan kurva karakteristik kerja GFR. 3. Setting GFR yang dipasang (existing) sudah tepat dan mampu memberikan pengamanan pada penyulang utama PDL06. 1,00 5. DAFTAR PUSTAKA 0,10 0,01 100 1000 10000 100000 Arus gangguan (A) Aslimeri, dkk. 2008, Teknik Transmisi Tenaga Listrik Jilid 2 untuk SMK. Jakarta: Direktorat Pembinaan Sekolah Menengah Kejuruan, Direktorat Jenderal Manajemen 4 Muhammad Iqbal, Moh Toni Prasetyo, Luqman Assaffat

Pendidikan Dasar dan Menengah, Departemen Pendidikan Nasional. Marsudi, Djiteng. 2006, Operasi Sistem Tenaga Listrik. Semarang: Penerbit Graha Ilmu. Perdana, W. C. 2008, Evaluasi Koordinasi Pengaman Feeder 20 kv Pandeanlamper 01 GI Pandeanlamper PT. PLN (Persero) APJ Semarang. Skripsi S1, Jurusan Teknik Elektro dan Teknologi Informasi FT UNIMUS. Tidak Dipublikasikan. Ravindranath, B; Chander, M. 1983, Power Sistem Protection and Switchgear. New Delhi: Wiley Eastern Limited. Sulasno, Ir. 2001, Analisis Sistem Tenaga Listrik. Semarang : Badan Penerbit Universitas Diponegoro. Suhadi, dkk. 2008, Teknik Distribusi Tenaga Listrik Jilid 1 untuk SMK. Jakarta: Direktorat Pembinaan Sekolah Menengah Kejuruan, Direktorat Jenderal Manajemen Pendidikan Dasar dan Menengah, Departemen Pendidikan Nasional. Suhadi, dkk. 2008, Teknik Distribusi Tenaga Listrik Jilid 3 untuk SMK. Jakarta: Direktorat Pembinaan Sekolah Menengah Kejuruan, Direktorat Jenderal Manajemen Pendidikan Dasar dan Menengah, Departemen Pendidikan Nasional. PT.PLN (Persero) P3B dan PT PLN UDIKLAT SEMARANG, 2010, Buku Teori Pelatihan O&M Relai Proteksi Gardu Induk, Jakarta:PT PLN Persero. Tobing, Bonggas L (2003), Peralatan Tegangan Tinggi. Jakarta : PT. Gramedia Pustaka Utama. Wahyudi, dkk. 2008. Workshop Operasi dan Pemeliharaan Distribusi. Jakarta: PT. PLN Pusdiklat. --------- (2008), Laporan Pekerjaan Pemeliharaan 1 Tahunan Trafo dan Bay Trafo III 60 MVA di Gardu Induk Pandeanlamper tanggal 22 Juli 2011. Semarang : PT. PLN (Persero) UPT Semarang. --------- SPLN 64 : 1985, Petunjuk Pemilihan dan Penggunaan Pelebur pada Sistem Distribusi Tegangan Menengah. Jakarta : PT. PLN (Persero) --------- SPLN 12 : 1978, Pedoman Penerapan Sistem Distribusi 20 kv, Fasa-Tiga, 4-Kawat. Jakarta : PT. PLN (Persero) --------- SPLN 2 : 1978, Pentanahan Netral Sistem Transmisi, Sub-transmisi dan Distribusi beserta Pengamanannya. Jakarta : PT. PLN (Persero) Analisa Setting Ground Fault... 5

6 Muhammad Iqbal, Moh Toni Prasetyo, Luqman Assaffat