Analisis Pengaruh Pemasangan Dynamic Voltage Restorer (DVR) terhadap Kedip Tegangan akibat Gangguan Hubung Singkat 3 Fasa pada Penyulang Kampus
|
|
- Ari Sanjaya
- 6 tahun lalu
- Tontonan:
Transkripsi
1 106 Teknologi Elektro, Vol. 16, No.03,September -Desember 2017 Analisis Pengaruh Pemasangan Dynamic Voltage Restorer () terhadap Kedip Tegangan akibat Gangguan Hubung Singkat 3 Fasa pada Penyulang Kampus I Gusti Agung Alit Teja Kusuma Putra 1, I Wayan Rinas 2, Yanu Prapto Sudarmojo 3 Abstract One of the disturbances that arise in the distribution of electric power is a 3 phase short circuit. 3-phase short circuit occurring in the distribution of electrical energy is not only causing a large fault currents on phases are impaired but also cause voltage sag on the distribution system. In general, voltage sag interference could result in damage/failure of equipment and disruption of network security equipment performance. This study analyzed the effect of the installation of Dynamic Voltage Restorer () on the voltage sag in the Kampus Feeder, using MATLAB-Simulink software, with a 3- phase short circuit and 5 to load variations is the percentage of load of 50%, 55%, 60%, 65%, and 70% of the total power distribution transformers to determine the effect of the installation on each load. Based on the analysis the greater percentage of the load voltage sag disorder is also getting bigger, causing fundamental voltage on each phase decreases. The voltage drop can be recovered by the by supplying the voltage at each voltage-dropping phase. supply voltage up to 1 pu on each phase. At a load percentage of 50% the supplies a voltage of 0.29 pu in phase A, 0.24 pu at phase B and 0.29 pu at phase C. Intisari Salah satu gangguan yang timbul dalam pendistribusian tenaga listrik adalah gangguan hubung singkat 3 fasa. Gangguan hubung singkat 3 fasa yang terjadi dalam pendistribusian energi listrik tidak hanya menyebabkan timbulnya arus gangguan yang besar pada fasa-fasa yang mengalami gangguan akan tetapi juga menyebabkan kedip tegangan pada sistem distribusi. Secara umum gangguan kedip tegangan dapat mengakibatkan kerusakan/ kegagalan peralatan dan terganggunya kinerja peralatan pengaman jaringan. Penelitian ini menganalisis pengaruh pemasangan Dynamic Voltage Restorer () terhadap kedip tegangan di Penyulang Kampus, menggunakan software MATLAB-Simulink, dengan gangguan hubung singkat 3 fasa dan 5 variasi beban yaitu dengan persentase beban 50%, 55%, 60%, 65%, dan 70% dari total daya trafo distribusi untuk mengetahui pengaruh pemasangan pada setiap beban. Berdasarkan hasil analisis semakin besar persentase beban maka gangguan kedip tegangan juga semakin besar sehingga menyebabkan tegangan fundamental pada setiap fasa menurun. Penurunan tegangan dapat dipulihkan oleh dengan menyuplai tegangan pada setiap fasa yang mengalami penurunan tegangan. menyuplai tegangan hingga menjadi 1 pu pada setiap fasa. Pada 1 Mahasiswa, Jurusan Teknik Elektro dan Komputer Fakultas Teknik Universitas Udayana, Jln. Cempaka, Dalung, Kuta Utara, Badung INDONESIA (tlp: ; gungalitteja23@gmail.com) 2,3 Dosen, Jurusan Teknik Elektro dan Komputer Fakultas Teknik Universitas Udayana, Jln. Kampus Bukit Jimbaran INDONESIA (telp: ; fax: ; 1 rinas@unud.ac.id, 2 yanu.prapto@unud.ac.id,) persentase beban sebesar 50% menyuplai tegangan sebesar 0,29 pu pada fasa A, 0,24 pu pada fasa B dan 0,29 pu pada fasa C. Kata kunci : Hubung Singkat 3 Fasa, Kedip Tegangan, Dynamic Voltage Restorer, Simulink Matlab. I. PENDAHULUAN Perkembangan teknologi yang sangat pesat menyebabkan semakin meningkatnya kebutuhan energi listrik. Agar dapat memenuhi kebutuhan tersebut maka diperlukan sistem distribusi yang baik. Sistem distribusi adalah sistem yang berfungsi menyalurkan tenaga listrik dari gardu induk ke konsumen. Banyaknya gangguan yang timbul dalam pendistribusian energi listrik dapat mengakibatkan menurunnya kualitas daya listrik. Salah satu gangguan yang timbul dalam pendistribusian tenaga listrik yaitu gangguan hubung singkat 3 fasa. Gangguan hubung singkat 3 fasa yang terjadi dalam pendistribusian energi listrik tidak hanya menyebabkan timbulnya arus gangguan yang besar pada fasafasa yang mengalami gangguan akan tetapi juga menyebabkan kedip tegangan pada sistem distribusinya. Kedip tegangan adalah penurunan nilai rms tegangan pada frekuensi daya selama durasi waktu dari 0,5 cycles (0,01detik) sampai 1 menit dan rentang perubahan dari 0,1 sampai 0,9 pu pada harga rms besaran tegangan [1]. Kedip tegangan dapat diakibatkan oleh: pembebanan yang besar pada sistem, gangguan hubung singkat, dan starting motor berdaya besar. Suatu sistem yang diberi beban yang besar akan mengalirkan arus yang melebihi arus pada beban nominal, hal ini menyebabkan terjadinya tegangan jatuh antara titik sumber dengan titik pembebanan. Besar nilai tegangan jatuh yang diakibatkan oleh kedip tegangan tergantung dari besar nilai impedansi titik pakai bersama (PCC= Point Common Coupling). Hubung singkat adalah hubungan konduksi yang sengaja atau tidak sengaja melalui hambatan atau impedansi yang cukup rendah antara dua titik atau lebih yang dalam keadaan normalnya mempunyai beda potensial. Gangguan hubung singkat dapat disebabkan akibat hubungan kontak langsung dengan konduktor bertegangan, temperatur berlebih karena adanya arus berlebih (overload), pelepasan (discharge electron) yang merusak karena tegangan berlebih, busur (arcing) karena pengembunan bersama dengan udara terutama pada isolator [2]. Kedip tegangan berlangsung dalam waktu yang relatif singkat sehingga tidak diketahui dengan pasti saat terjadi gangguan. Gangguan kedip tegangan dapat menyebabkan trip ISSN ; e-issn: I Gusti Agung Alit Teja Kusuma Putra : Analisis Pengaruh Pemasangan Dynamic
2 Teknologi Elektro, Vol. 16, No. 3,September - Desember peralatan- peralatan pengaman yang peka terhadap perubahan tegangan. Secara umum gangguan kedip tegangan dapat mengakibatkan motor tiba- tiba berhenti, peralatan digital terreset yang menyebabkan hilangnya data, kerusakan/ kegagalan peralatan dan terganggunya kinerja peralatan pengaman jaringan seperti beroperasinya sistem rele undervoltage yang akan menyebabkan pemutusan suplai tegangan pada jaringan sistem tenaga listrik. Penyulang Kampus adalah penyulang dengan suplai tenaga listrik dari GI Nusa Dua yang terletak di wilayah Kuta Selatan. Penyulang ini memiliki konfigurasi sistem distribusi tipe radial, dengan panjang saluran 21,377 km. Gangguan hubung singkat pada penyulang dengan konfigurasi sistem radial menyebabkan terjadinya gangguan kedip tegangan pada busbar gardu induk. Selain itu, penyulang ini memiliki trafo distribusi sebanyak 57 buah dengan jumlah pelanggan sebanyak 7099 pelanggan. Gangguan kedip tegangan akan dirasakan oleh pelanggan yang disuplai dari transformator tegangan menengah dan tegangan rendah yang sama, maka dari itu kedip tegangan harus diantisipasi agar tidak terganggunya tegangan pada sisi beban. II. KEDIP TEGANGAN DAN DYNAMIC VOLTAGE RESTORER A. Kedip Tegangan Pada umumnya kedip tegangan disebabkan karena gangguan hubung singkat dan karena pengasutan beban yang kapasitasnya cukup besar [3]. Kedip tegangan dapat menyebabkan menurunnya kualitas daya listrik. Konsumen menginginkan kualitas daya listrik yang diterima berada pada tingkat yang baik, oleh karena itu kedip tegangan harus diantisipasi dengan cepat untuk menghindari kerugian yang ditimbulkan oleh gangguan kedip tegangan. Dynamic Voltage Restorer () adalah suatu peralatan elektronika daya yang berfungsi untuk melindungi peralatan yang sensitif terhadap perubahan tegangan akibat gangguan kedip tegangan. Untuk mengatasi gangguan kedip tegangan, menyuplai tegangan dinamik terkontrol untuk mengurangi pengaruh gangguan kedip tegangan pada bus yang mengalami gangguan kedip tegangan. Komponen dasar yang menyusun adalah : 1. Voltage Source Converter (VSC) VSC merupakan sebuah sistem elektronika daya yang terdiri dari peralatan penyimpanan dan pensaklaran, yang dapat membangkitkan tegangan listrik sinusoidal pada frekuensi dan sudut fasa yang diperlukan [5]. VSC berfungsi untuk mengkonversi tegangan DC menjadi tegangan AC yang dibutuhkan oleh transformator injeksi tegangan. 2. Sumber DC Sumber DC berfungsi untuk menyediakan kebutuhan daya aktif selama terjadinya kompensasi oleh dan juga berfungsi sebagai sumber tegangan input dari VSC. Sumber DC yang digunakan biasanya berupa baterai dan tenaga surya. 3. Transformator injeksi tegangan Fungsi transformator injeksi adalah menaikkan tegangan supply AC yang dihasilkan oleh VSC menjadi tegangan yang dibutuhkan untuk memulihkan kedip tegangan [6]. 4. Filter Pada biasanya menggunakan filter pasif. Penempatan filter pada sisi converter dapat mencegah orde harmonisa tidak mengalir melewati kumparan transformator namun filter tersebut menimbullkan tegangan drop dan pergeseran fasa pada (komponen fundamental) tegangan injeksi. Gambar 2. Dynamic Voltage Restorer [7] Gambar 1. Gangguan Kedip Tegangan akibat Gangguan Hubung Singkat Satu Fasa ke Tanah [4] (a) Bentuk Gelombang RMS karena Gangguan Kedip Tegangan. (b) Bentuk Gelombang Kedip Tegangan. B. Dynamic Voltage Restorer () C. Hubung Singkat Tiga Fasa Gangguan hubung singkat merupakan gangguan yang terjadi karena adanya kesalahan antara bagian- bagian yang bertegangan [8]. Gangguan hubung singkat tiga fasa merupakan gangguan simetris yang terjadi pada ketiga fasanya sehingga menyebabkan tegangan dan dan arus tetap seimbang setelah terjadinya gangguan. I Gusti Agung Alit Teja Kusuma Putra : Analisis Pengaruh Pemasangan Dynamic p-issn: ; e-issn:
3 108 Teknologi Elektro, Vol. 16, No.03,September -Desember 2017 Gangguan hubung singkat tiga fasa yaitu ganggguan yang disebabkan oleh putusnya salah satu kawat fasa yang letaknya paling atas pada sistem transmisi atau sistem distribusi dengan konfigurasi kawat antar fasanya disusun secara vertikal [9]. Berikut merupakan gambar gangguan hubung singkat tiga fasa. Gambar 3. Gangguan Hubung Singkat Tiga Fasa [10] III. PEMODELAN SIMULASI Data- data yang digunakan pada penelitian ini merupakan data sekunder yang diperoleh dari PT. PLN (Persero) Area Jaringan Bali Selatan yang beralamat di Jl. P.B Sudirman No.2 Denpasar. Adapun tahapan penelitian yang dilakukan adalah sebagai berikut : 1. Mengumpulkan data-data, antara lain: data transformator tenaga, data saluran distribusi dan data Penyulang Kampus. 2. Menghitung resistansi sumber dan induktansi sumber yang akan digunakan pada simulasi. 3. Pemodelan sistem Penyulang Kampus pada Program Simulink MATLAB. 4. Menentukan parameter-parameter yang digunakan pada simulasi. 5. Simulasi kondisi di Penyulang Kampus pada saat tidak terjadi gangguan kedip tegangan dengan menggunakan program Simulink MATLAB. 6. Simulasi terjadinya gangguan kedip tegangan dengan beban yang divariasikan dan gangguan hubung singkat 3 phase. 7. Simulasi pemulihan kedip tegangan dengan menggunakan 8. Analisis pengaruh pemasangan terhadap gangguan kedip tegangan berdasarkan hasil simulasi dan menarik kesimpulan. A. Pemodelan Simulasi Single line diagram Penyulang Kampus dapat dilihat pada Lampiran Gambar 4. Penempatan pada simulasi yaitu dipasang seri antara sumber dan beban. Perangkat lunak Simulink MATLAB digunakan untuk simulasi pada penelitian ini. Model simulasi yang dibuat yaitu: 1. Model simulasi pada saat tidak terjadi gangguan kedip tegangan pada Penyulang Kampus. Model simulasi pada saat tidak terjadi gangguan kedip tegangan dapat dilihat pada Lampiran Gambar Model Simulasi gangguan kedip tegangan pada penyulang kampus. Model simulasi kedip tegangan adalah akibat dari gangguan hubung singkat 3 fasa. Model simulasi kedip tegangan dapat dilihat pada Lampiran Gambar Model simulasi pemulihan kedip tegangan dengan pemasangan. Model simulasi pemulihan kedip tegangan dengan pemasangan dapat dilihat pada Lampiran Gambar 7. Pada Lampiran Gambar 7 simulasi pemulihan gangguan kedip tegangan menggunakan PI (Proportional Integral) controler sebagai pengendali. pada Lampiran Gambar 7 dipasang seri, yaitu antara sumber dan beban. 4. Pemodelan sumber 3 fasa Data yang digunakan sebagai input pada blok parameter sumber 3 fasa adalah data teknik transformator distribusi. 5. Pemodelan beban Beban yang digunakan pada simulasi ini merupakan beban pada penyulang kampus. Input data pada blok parameter beban yang digunakan pada simulasi yaitu data daya aktif (P), daya reaktif (Q), tegangan (Vrms), dan frekuensi. IV. HASIL DAN PEMBAHASAN A. Hasil Simulasi Simulasi yang digunakan pada penelitian ini menggunakan 3 jenis simulasi yaitu : 1. Simulasi tanpa gangguan kedip tegangan 2. Simulasi gangguan kedip tegangan 3. Simulasi pemulihan kedip tegangan dengan memasang Simulasi gangguan kedip tegangan dan pemulihan kedip tegangan dilakukan dengan 5 variasi beban dan dengan gangguan hubung singkat 3 fasa. Simulasi dilakukan dengan periode gelombang T= 0,12 dan gangguan kedip tegangan yang terjadi diasumsikan mulai dari 0,04 detik sampai 0,08 detik. B. Hasil Simulasi tanpa Gangguan Simulasi tanpa gangguan kedip tegangan dilakukan untuk mengetahui bentuk gelombang tegangan jika tidak ada gangguan kedip tegangan di penyulang kampus. Hasil simulasi tanpa gangguan kedip tegangan dapat dilihat pada Lampiran Gambar 8. C. Hasil Simulasi Gangguan Kedip Tegangan dan Pemulihan Kedip Tegangan Simulasi gangguan kedip tegangan dan pemulihan kedip tegangan dilakukan pada beban 4.822,50 kva (50%), 5.304,75 kva (55%), kva (60%), 6.269,25 kva (65%), dan 6.751,50 kva (70%) dengan daya aktif dan reaktif seperti pada TABEl I dengan gangguan hubung singkat 3 fasa. Gangguan kedip tegangan yang terjadi diasumsikan mulai dari 0,04 detik sampai 0,08 detik dan resistansi gangguan diasumsikan sebesar 10 Ω. ISSN ; e-issn: I Gusti Agung Alit Teja Kusuma Putra : Analisis Pengaruh Pemasangan Dynamic
4 Teknologi Elektro, Vol. 16, No. 3,September - Desember TABEL I DAYA AKTIF (P) DAN DAYA REAKTIF (Q) No Persentase Beban Daya Aktif (P) Daya Reaktif (Q) 1 50% 4.099,125 kw ,511 VAR 2 55% 4.509,038 kw ,462 VAR 3 60% 4.918,950 kw ,413 VAR 4 65% 5.328,863 kw ,365 VAR 5 70% 5.738,775 kw ,316 VAR Hasil simulasi gangguan kedip tegangan dan pemulihan kedip tegangan pada beban 4.822,50 kva (50%) dapat dilihat pada Lampiran Gambar 9. Pada Lampiran Gambar 9 (a) dapat dilihat bahwa fasa A, B dan C mengalami kedip tegangan selama 0,04 detik yaitu dari 0,04 detik sampai 0,08 detik. Pada Lampiran Gambar 9 (b) terlihat fasa A, B, dan C kembali normal setelah dipasang. menyuplai tegangan pada fasa A, B dan C ketika mengalami penurunan tegangan, sehingga kedip tegangan tidak dirasakan pada sisi beban. Kedip tegangan menyebabkan turunnya tegangan pada setiap fasa yang mengalami gangguan. Besar nilai tegangan pada setiap fasa yang mengalami gangguan kedip tegangan dapat diketahui dengan menggunakan bantuan FFT tools yang ada pada MATLAB Simulink. Berikut merupakan tampilan FFT tools gelombang tegangan pada beban 4.822,50 kva (50%). 1. Gelombang Tegangan Fasa A Gambar 11. FFT analisis gelombang tegangan fasa A setelah dipasang Pada Gambar 11 merupakan gambar gelombang fasa A setelah dipasang. Pada Gambar 11 dapat dilihat tegangan fundamental naik menjadi 0,9921 pu dan THDv menurun menjadi 1,94%. 2. Gelombang Tegangan Fasa B Gambar 10. FFT analisis gelombang tegangan fasa A tanpa Pada Gambar 10 dapat dilihat tegangan fundamental mengalami penurunan menjadi 0,7353 pu pada durasi waktu 0,04 detik sampai 0,08 detik dengan THDv sebesar 13,98%. Hal ini disebabkan karena gangguan kedip tegangan yang terjadi. Gambar 12. FFT analisis gelombang tegangan fasa B tanpa Pada Gambar 12 dapat dilihat tegangan fundamental mengalami penurunan menjadi 0,7774 pu pada durasi waktu 0,04 detik sampai 0,08 detik dengan THDv sebesar I Gusti Agung Alit Teja Kusuma Putra : Analisis Pengaruh Pemasangan Dynamic p-issn: ; e-issn:
5 110 Teknologi Elektro, Vol. 16, No.03,September -Desember ,79%. Hal ini disebabkan karena gangguan kedip tegangan yang terjadi. Pada Gambar 14 dapat dilihat tegangan fundamental mengalami penurunan menjadi 0,729 pu pada durasi waktu 0,04 detik sampai 0,08 detik dengan THDv sebesar 8,09%. Hal ini disebabkan karena gangguan kedip tegangan yang terjadi. Gambar 13. FFT analisis gelombang tegangan fasa B setelah dipasang Pada Gambar 13 merupakan gambar gelombang fasa B setelah dipasang. Pada Gambar 13 dapat dilihat tegangan fundamental naik menjadi 0,991 pu dan THDv menurun menjadi 1,89%. 3. Gelombang Tegangan Fasa C Gambar 15. FFT analisis gelombang tegangan fasa C setelah dipasang Pada Gambar 15 merupakan gambar gelombang fasa C setelah dipasang. Pada Gambar 15 dapat dilihat tegangan fundamental naik menjadi 0,9906 pu dan THDv menurun menjadi 1,90%. Hasil simulasi kedip tegangan pada beban 4.822,50 kva (50%) dapat dilihat pada tabel II. TABEL II HASIL SIMULASI PADA BEBAN 4.822,50 KVA (50%) Fasa Vfundamental (pu) THDv (%) Tanpa Tanpa V suplai (pu) A 0,7353 0, ,98 1,94 0,2568 B 0,7774 0,991 5,79 1,89 0,2147 C 0,729 0,9906 8,09 1,90 0,2616 Gambar 14. FFT analisis gelombang tegangan fasa C tanpa D. Analisis Hasil Simulasi Berdasarkan hasil simulasi kedip tegangan pada persentase beban 50%, 55%, 60%, 665%, dan 70% dapat dilihat bahwa mampu mengurangi THDv dan memulihkan tegangan akibat kedip tegangan dengan menyuplai tegangan pada fasa yang mengalami gangguan kedip tegangan. Untuk lebih jelasnya dapat dilihat pada tabel III dan tabel IV. ISSN ; e-issn: I Gusti Agung Alit Teja Kusuma Putra : Analisis Pengaruh Pemasangan Dynamic
6 Teknologi Elektro, Vol. 16, No. 3,September - Desember TABEL III KANDUNGAN THD SETIAP FASA PADA BEBAN 4.822,50 KVA (50%), 5.304,75VA (55%), KVA (60%), 6.269,25 KVA (65%), DAN 6.751,50 KVA (70%). Beban (%) THDv (%) Tanpa THDv (%) Dengan A B C A B C 50 13,98 5,79 8,09 1,94 1,89 1, ,62 5,89 7,61 1,95 1,93 1, ,27 5,97 7,15 1,93 1,88 1, ,92 6,03 6,73 1,99 1,94 1, ,59 6,08 6,34 1,97 1,89 1,86 Pada tabel III dapat dilihat bahwa kandungan THDv pada setiap fasa berkurang. Hal ini disebabkan oleh filter pasif yang ditempatkan pada sisi keluaran VSC (Voltage Source Converter) telah mereduksi THDv. TABEL IV HASIL SIMULASI PADA BEBAN 4.822,50 KVA, 5.304,75 KVA, KVA, 6.269,25 KVA, DAN 6.751,50 KVA. B E B A N (%) V fundamental (pu) Tanpa V fundamental (pu) Dengan V suplai (pu) A B C A B C A B C 50 0,73 0,78 0,73 0,9 0,9 0,9 0,26 0,21 0, ,72 0,76 0,72 0,9 0,9 0,9 0,27 0,23 0, ,71 0,75 0,71 0,9 0,9 0,9 0,28 0,24 0, ,70 0,74 0,70 0,9 0,9 0,9 0,29 0,25 0, ,69 0,72 0,69 0,9 0,9 0,9 0,30 0,26 0,30 Pada tabel IV dapat dilihat bahwa semakin besar persentase beban maka tegangan fundamental pada setiap fasa menurun. Hal ini disebabkan karena gangguan kedip tegangan yang semakin besar. Penurunan tegangan dapat dipulihkan oleh dengan menyuplai tegangan pada setiap fasa yang mengalami penurunan tegangan. Pada persentase beban sebesar 50% terlihat menyuplai tegangan sebesar 0,26 pu pada fasa A, 0,21 pu pada fasa B dan 0,26 pu pada fasa C. Pada persentase beban sebesar 55% terlihat menyuplai tegangan sebesar 0,27 pu pada fasa A, 0,23 pu pada fasa B dan 0,27 pu pada fasa C. Pada persentase beban sebesar 60% terlihat menyuplai tegangan sebesar 0,28 pu pada fasa A, 0,24 pu pada fasa B dan 0,28 pu pada fasa C. Pada persentase beban sebesar 65% terlihat menyuplai tegangan sebesar 0,29 pu pada fasa A, 0,25 pu pada fasa B dan 0,29 pu pada fasa C. Pada persentase beban sebesar 70% terlihat menyuplai tegangan sebesar 0,30 pu pada fasa A, 0,26 pu pada fasa B dan 0,30 pu pada fasa C. mampu memulihkan tegangan setiap fasa yang mengalami gangguan menjadi 1 pu. V. SIMPULAN Berdasarkan hasil pembahasan dapat disimpulkan bahwa mampu memulihkan gangguan kedip tegangan pada penyulang kampus akibat gangguan hubung singkat 3 fasa dan beban yang bervariasi. memulihkan tegangan menjadi 1pu pada fasa yang mengalami gangguan kedip tegangan. memulihkan tegangan dengan menyuplai tegangan pada fasa yang mengalami gangguan. Pada hasil simulasi pemulihan kedip tegangan dengan persentase beban sebesar 50% terlihat menyuplai tegangan sebesar 0,26 pu pada fasa A, 0,21 pu pada fasa B dan 0,26 pu pada fasa C. REFERENSI [1] IEEE Standard Power Quality Monitoring. IEEE Standard Boards. [2] IEC Short-Circuit Currents in Three-Phase A.C. Systems. [3] M. W. N. Sabara, T. Yuwono, O. Penangsang, Pengaruh Kedip Tegangan dan Koordinasi Rele Arus Lebih pada Pabrik Semen, JURNAL TEKNIK ITS Vol. 1, No. 1, (Sept. 2012) ISSN: [4] R.C. Dugan, M.F. McGranaghan, S. Santoso, H.W. Beaty, Electrical Power System Quality-Second Edition. The McGraw-Hill, [5] Winarso, Perbaikan Kualitas Tegangan Menggunakan Dynamic Voltage Restorer (Dvr) Jurnal Ilmiah Foristek Vol.3, No. 1, Maret [6] I. M. Y. Dwipayana Analisis Kedip Tegangan Akibat Gangguan Hubung Singkat Pada Penyulang Abang Di Karangasem E-Journal SPEKTRUM Vol. 3, No. 2 Desember [7] K. R. Padiyar, Facts Controllers In Power Transmission and Distribution. New Age International, [8] B. Indra, Sukerayasa, dan Ariastina, STUDI KOORDINASI PERALATAN PROTEKSI OCRDANGFR PADA PENYULANG TIBUBENENG, Teknologi Elektro, Vol. 14, No. 2, pp , Juli Desember [9] M. B. Nurcahyadi, I. W. Rinas, A. A. G. M. Pemayun, Analisis Sistem Pengaman Arus Lebih pada Penyulang Abang Akibat Beroperasinya PLTS pada Saluran Distribusi Tegangan Listrik 20 Kv di Karangasem Teknologi Elektro, Vol. 16, No1, Januari-April [10] J. C. Das, Power System Analysis, Short-Circuit Load Flow and Harmonics. United States of America : Marcel Dekker, I Gusti Agung Alit Teja Kusuma Putra : Analisis Pengaruh Pemasangan Dynamic p-issn: ; e-issn:
7 112 Teknologi Elektro, Vol. 16, No.03,September -Desember 2017 LAMPIRAN Gambar 4. Single line diagram penyulang kampus Gambar 5. Pemodelan pada saat tidak terjadi gangguan kedip tegangan Gambar 6. Pemodelan simulasi gangguan kedip tegangan pada penyulang kampus ISSN ; e-issn: I Gusti Agung Alit Teja Kusuma Putra : Analisis Pengaruh Pemasangan Dynamic
8 Teknologi Elektro, Vol. 16, No. 3,September - Desember Gambar 7. Pemodelan simulasi pemulihan kedip tegangan dengan pemasangan Keterangan : = Fasa A = Fasa B = Fasa C Gambar 8. Gelombang tegangan 3 fasa tanpa gangguan kedip tegangan pada penyulang kampus (a) Gelombang tegangan 3 fasa akibat kedip tegangan (b) Gelombang tegangan 3 fasa setelah terpasang Keterangan : = Fasa A = Fasa B = Fasa C Gambar 9. Hasil simulasi gangguan kedip tegangan dan pemulihan kedip tegangan dengan beban 4.822,50 kva (50%) pada penyulang kampus I Gusti Agung Alit Teja Kusuma Putra : Analisis Pengaruh Pemasangan Dynamic p-issn: ; e-issn:
Kata kunci : Hubung Singkat 3 Fasa, Kedip Tegangan, Dynamic Voltage Restorer, Simulink Matlab.
ABSTRAK Banyaknya gangguan yang timbul dalam pendistribusian energi listrik dapat mengakibatkan menurunnya kualitas daya listrik. Salah satu gangguan yang timbul dalam pendistribusian tenaga listrik yaitu
Lebih terperinciANALISIS KEDIP TEGANGAN AKIBAT GANGGUAN HUBUNG SINGKAT PADA PENYULANG ABANG DI KARANGASEM
ANALISIS KEDIP TEGANGAN AKIBAT GANGGUAN HUBUNG SINGKAT PADA PENYULANG ABANG DI KARANGASEM I Made Yoga Dwipayana 1, I Wayan Rinas 2, I Made Suartika 3 Jurusan Teknik Elektro dan Komputer, Fakultas Teknik,
Lebih terperinciANALISIS KEDIP TEGANGAN AKIBAT GANGGUAN HUBUNG SINGKAT PADA PENYULANG ABANG DI KARANGASEM
SKRIPSI ANALISIS KEDIP TEGANGAN AKIBAT GANGGUAN HUBUNG SINGKAT PADA PENYULANG ABANG DI KARANGASEM I MADE YOGA DWIPAYANA JURUSAN TEKNIK ELEKTRO DAN KOMPUTER FAKULTAS TEKNIK UNIVERSITAS UDAYANA BUKIT JIMBARAN
Lebih terperinci92 Teknologi Elektro, Vol. 16, No.03,September -Desember I Gusti Ngurah Dwipayana 1, I Wayan Rinas 2, I Made Suartika 3
92 Teknologi Elektro, Vol. 16, No.03,September -Desember 2017 Analisis THD dan Peningkatan Arus pada Kawat Netral Akibat Pengoperasian Beban Non Linier yang Tak pada Sistem Tenaga Listrik di RSUD Kabupaten
Lebih terperinciI Wayan Rinas. Jurusan Teknik Elektro, Fakultas Teknik, Universitas Udayana Kampus Bukit Jimbaran, Bali, *
Simulasi Penggunaan Filter Pasif, Filter Aktif dan Filter Hybrid Shunt untuk Meredam Meningkatnya Distorsi Harmonisa yang Disebabkan Oleh Munculnya Gangguan Jurusan Teknik Elektro, Fakultas Teknik, Universitas
Lebih terperinciAnalisis Sistem Pengaman Arus Lebih pada Penyulang Abang Akibat Beroperasinya PLTS pada Saluran Distribusi Tegangan Listrik 20 Kv di Karangasem
Teknologi Elektro, Vol. 16, 1, Januari-April 2017 61 Analisis Sistem Pengaman Arus Lebih pada Penyulang Abang Akibat Beroperasinya PLTS pada Saluran Distribusi Tegangan Listrik 20 Kv di Karangasem Made
Lebih terperinciSIMULASI PEMULIHAN KEDIP TEGANGAN AKIBAT GANGGUAN ARUS HUBUNG SINGKAT MENGGUNAKAN DYNAMIC VOLTAGE RESTORER (DVR)
SIMULASI PEMULIHAN KEDIP TEGANGAN AKIBAT GANGGUAN ARUS HUBUNG SINGKAT MENGGUNAKAN DYNAMIC VOLTAGE RESTORER (DVR) Nizamul Muluk *), Agung Warsito, and Juningtyastuti Departemen Teknik Elektro, Universitas
Lebih terperinciANALISIS HARMONIK DAN PERANCANGAN SINGLE TUNED FILTER PADA SISTEM DISTRIBUSI STANDAR IEEE 18 BUS DENGAN MENGGUNAKAN SOFTWARE ETAP POWER STATION 4.
Jurnal Emitor Vol. 15 No. 02 ISSN 1411-8890 ANALISIS HARMONIK DAN PERANCANGAN SINGLE TUNED FILTER PADA SISTEM DISTRIBUSI STANDAR IEEE 18 BUS DENGAN MENGGUNAKAN SOFTWARE ETAP POWER STATION 4.0 Novix Jefri
Lebih terperinciVoltage sag atau yang sering juga disebut. threshold-nya. Sedangkan berdasarkan IEEE Standard Voltage Sag
2.3. Voltage Sag 2.3.1. Gambaran Umum Voltage sag atau yang sering juga disebut sebagai voltage dip merupakan suatu fenomena penurunan tegangan rms dari nilai nominalnya yang terjadi dalam waktu yang singkat,
Lebih terperinciBAB I PENDAHULUAN 1.1 Latar Belakang Energi listrik sangat di butuhkan pada zaman modern ini, karena saat ini kebutuhan manusia akan teknologi
BAB I PENDAHULUAN 1.1 Latar Belakang Energi listrik sangat di butuhkan pada zaman modern ini, karena saat ini kebutuhan manusia akan teknologi semakin meningkat. Oleh karena itu para ilmuan berlomba-lomba
Lebih terperinciANALISIS PENGARUH PENGOPERASIAN BEBAN- BEBAN NON-LINIER TERHADAP DISTORSI HARMONISA PADA BLUE POINT BAY VILLA & SPA
ANALISIS PENGARUH PENGOPERASIAN BEBAN- BEBAN NON-LINIER TERHADAP DISTORSI HARMONISA PADA BLUE POINT BAY VILLA & SPA I Putu Alit Angga Widiantara 1, I Wayan Rinas 2, Antonius Ibi Weking 3 Jurusan Teknik
Lebih terperinciBAB I PENDAHULUAN. Transmisi, dan Distribusi. Tenaga listrik disalurkan ke masyarakat melalui jaringan
BAB I PENDAHULUAN 1.1 Latar Belakang Tenaga Listrik disalurkan ke konsumen melalui Sistem Tenaga Listrik. Sistem Tenaga Listrik terdiri dari beberapa subsistem, yaitu Pembangkitan, Transmisi, dan Distribusi.
Lebih terperinciBAB 2 TINJAUAN PUSTAKA. induk agar keandalan sistem daya terpenuhi untuk pengoperasian alat-alat.
BAB 2 TINJAUAN PUSTAKA 2.1 Distribusi daya Beban yang mendapat suplai daya dari PLN dengan tegangan 20 kv, 50 Hz yang diturunkan melalui tranformator dengan kapasitas 250 kva, 50 Hz yang didistribusikan
Lebih terperinciANALISA DISTORSI HARMONISA PADA PENYULANG ABANG KARANGASEM SETELAH TERPASANGNYA PEMBANGKIT LISTRIK TENAGA SURYA (PLTS)
TUGAS AKHIR ANALISA DISTORSI HARMONISA PADA PENYULANG ABANG KARANGASEM SETELAH TERPASANGNYA PEMBANGKIT LISTRIK TENAGA SURYA (PLTS) Oleh : I Gede Aries Gunawan JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS
Lebih terperinciAnalisis Pengaruh Total Harmonic Distortion Terhadap Losses dan Efisiensi Transformator RSUD Kabupaten Klungkung
Teknologi Elektro, Vol. 16, No1, Januari-April 2017 107 Analisis Pengaruh Total Harmonic Distortion Terhadap Losses dan Efisiensi Transformator RSUD Kabupaten Klungkung Wayan Agus Adi Widiastra 1, I Wayan
Lebih terperinciANALISIS HARMONIK DAN PERANCANGAN HIGH PASS DAMPED FILTER
NASKAH PUBLIKASI ANALISIS HARMONIK DAN PERANCANGAN HIGH PASS DAMPED FILTER PADA SISTEM DISTRIBUSI STANDAR IEEE 13 BUS DENGAN MENGGUNAKAN SOFTWARE ETAP POWER STATION 7.0 Diajukan oleh: AGUS WIDODO D 400
Lebih terperinciABSTRAK. Kata kunci : Kondisi tanpa Harmonisa, Kondisi dengan Harmonisa, Harmonic Analysis Load Flow, Rugi Daya, Sistem Tegangan Rendah.
ABSTRAK Penyulang Menjangan merupakan sistem jaringan tegangan menengah 20 kv yang melayani daerah Gilimanuk dan sebagian Buleleng. Penyulang Menjangan memiliki total gardu terpasang sebanyak 69 Gardu,
Lebih terperinciPeredaman Harmonik Arus pada Personal Computer All In One Menggunakan Passive Single Tuned Filter
Mustamam, Azmi Rizki Lubis, Peredaman... ISSN : 598 99 (Online) ISSN : 5 364 (Cetak) Peredaman Harmonik Arus pada Personal Computer All In One Menggunakan Passive Single Tuned Filter Mustamam ), Azmi Rizki
Lebih terperinciANALISIS HUBUNG SINGKAT 3 FASA PADA SISTEM DISTRIBUSI STANDAR IEEE 18 BUS DENGAN ADANYA PEMASANGAN DISTRIBUTED GENERATION (DG)
ANALISIS HUBUNG SINGKAT 3 FASA PADA SISTEM DISTRIBUSI STANDAR IEEE 18 BUS DENGAN ADANYA PEMASANGAN DISTRIBUTED GENERATION (DG) Agus Supardi 1, Tulus Wahyu Wibowo 2, Supriyadi 3 1,2,3 Jurusan Teknik Elektro,
Lebih terperinciBAB 1 PENDAHULUAN. Sistem Distribusi daya listrik idealnya harus dapat memberikan kepada
BAB 1 PENDAHULUAN 1.1. Latar Belakang Sistem Distribusi daya listrik idealnya harus dapat memberikan kepada pelanggan mereka aliran energi yang tidak terganggu, dalam bentuk gelombang tegangan sinusoidal
Lebih terperinci20 Teknologi Elektro, Vol. 16, No. 02, Mei - Agustus I Gede Krisnayoga Kusuma 1, I Gede Dyana Arjana 2, I Wayan Arta Wijaya 3
20 Teknologi Elektro, Vol. 16, No. 02, Mei - Agustus 2017 Studi Analisa Koordinasi Relai GFR Incoming Busbar 20 kv dan GFR Saluran Dalam Mengamankan Gangguan Satu Phasa Ketanah di Transformator 3 Gardu
Lebih terperinciRancang Bangun Rangkaian AC to DC Full Converter Tiga Fasa dengan Harmonisa Rendah
Rancang Bangun Rangkaian AC to DC Full Converter Tiga Fasa dengan Harmonisa Rendah Mochammad Abdillah, Endro Wahyono,SST, MT ¹, Ir.Hendik Eko H.S., MT ² 1 Mahasiswa D4 Jurusan Teknik Elektro Industri Dosen
Lebih terperinciNASKAH PUBLIKASI PERANCANGAN HIGH PASS DAMPED FILTER PADA SISTEM DISTRIBUSI STANDAR IEEE 9 BUS DENGAN MENGGUNAKAN SOFTWARE ETAP POWER STATION 7.
NASKAH PUBLIKASI PERANCANGAN HIGH PASS DAMPED FILTER PADA SISTEM DISTRIBUSI STANDAR IEEE 9 BUS DENGAN MENGGUNAKAN SOFTWARE ETAP POWER STATION 7.0 Diajukan Oeh : INDRIANA ZELLA MARGARETA D 400 130 001 JURUSAN
Lebih terperinciArrifat Lubis
Seminar Tugas Akhir (Gasal 2010-2011) Teknik Sistem Tenaga Jurusan Teknik Elektro ITS ANALISIS DAN SIMULASI KUALITAS DAYA : FAKTOR DAYA, TEGANGAN KEDIP DAN HARMONISA PADA PERENCANAAN SISTEM KELISTRIKAN
Lebih terperinciAnalisis Tegangan Sags Akibat Pengasutan Motor Induksi Menggunakan Dynamic Voltage Restorer (DVR)
Analisis Tegangan Sags Akibat Pengasutan Motor Induksi Menggunakan Dynamic Voltage Restorer (DVR) Lauhil M. Hayusman 1, Hadi Suyono 2, Taufik Hidayat 3 1,3 Jurusan Teknik Elektro, Institut Teknologi Nasional
Lebih terperinciSTUDI KOORDINASI RELE ARUS LEBIH DAN PENGARUH KEDIP TEGANGAN AKIBAT PENAMBAHAN BEBAN PADA SISTEM KELISTRIKAN DI PT. ISM BOGASARI FLOUR MILLS SURABAYA
Presentasi Sidang Tugas Akhir (Gasal 2013/2014) Teknik Sistem Tenaga Jurusan Teknik Elektro ITS STUDI KOORDINASI RELE ARUS LEBIH DAN PENGARUH KEDIP TEGANGAN AKIBAT PENAMBAHAN BEBAN PADA SISTEM KELISTRIKAN
Lebih terperinci50 Frekuensi Fundamental 100 Harmonik Pertama 150 Harmonik Kedua 200 Harmonik Ketiga
PENGGUNAAN FILTER HIBRID KONFIGURASI SERI UNTUK MEMPERBAIKI KINERJA FILTER PASIF DALAM UPAYA PENINGKATAN PEREDUKSIAN HARMONISA PADA SISTEM KELISTRIKAN DI RSUP SANGLAH Jurusan Teknik Elektro Fakultas Teknik
Lebih terperinciBAB 1 PENDAHULUAN. 1.1 Latar Belakang. rendah banyak dibahas dalam forum-forum kelistrikan. Permasalahan kualitas daya
BAB 1 PENDAHULUAN 1.1 Latar Belakang Pada era sekarang ini, permasalahan kualitas daya pada sistem tegangan rendah banyak dibahas dalam forum-forum kelistrikan. Permasalahan kualitas daya sistem disebabkan
Lebih terperinciSIMULASI TEGANGAN DIP PADA SISTEM DISTRIBUSI TEGANGAN RENDAH MENGGUNAKAN MODEL EMTP
SIMULASI TEGANGAN DIP PADA SISTEM DISTRIBUSI TEGANGAN RENDAH MENGGUNAKAN MODEL EMTP Dwi Sulistyo Handoyo, Abdul Syakur, Agung Warsito Jurusan Teknik Elektro Fakultas Teknik - Universitas Diponegoro Jl.
Lebih terperinciPerencanaan Rekonfigurasi Jaringan Tegangan Menengah Pada Kampus Universitas Udayana Bukit Jimbaran
56 Teknologi Elektro, Vol. 15, No. 1, Januari - Juni 2016 Perencanaan Rekonfigurasi Jaringan Tegangan Menengah Pada Kampus Universitas Udayana Bukit Jimbaran I Putu Andithya Chrisna Budi 1, I. A. Dwi Giriantari
Lebih terperinci: Distributed Generation, Voltage Profile, Power Losses, Load Flow Analysis, EDSA 2000
ABSTRAK Salah satu teknik untuk memperbaiki jatuh tegangan adalah dengan pemasangan (DG) Distributed Generation. Salah satu teknologi Distributed Generation yang ada di Bali adalah PLTS Kubu Karangasem
Lebih terperinciANALISIS HARMONISA YANG DIHASILKAN CYCLOCONVERTER DENGAN BERBAGAI PARAMETER
ANALISIS HARMONISA YANG DIHASILKAN CYCLOCONVERTER DENGAN BERBAGAI PARAMETER Prof. Dr. Ir. Iwa Garniwa M.K., MT., Fikri Umar Bajuber Departemen Teknik Elektro, Fakultas Teknik, Kampus UI, Depok, 16424,
Lebih terperinciSTUDI PENGATURAN TEGANGAN PADA JARINGAN DISTRIBUSI 20 KV YANG TERHUBUNG DENGAN DISTRIBUTED GENERATION (STUDI KASUS: PENYULANG TR 5 GI TARUTUNG)
STUDI PENGATURAN TEGANGAN PADA JARINGAN DISTRIBUSI 20 KV YANG TERHUBUNG DENGAN DISTRIBUTED GENERATION (STUDI KASUS: PENYULANG TR 5 GI TARUTUNG) Andika Handy (1), Zulkarnaen Pane (2) Konsentrasi Teknik
Lebih terperinciBeban Linier Beban Non Linier Harmonisa Total Harmonic Distortion (THD)
DAFTAR ISI JUDUL... i LEMBAR PERNYATAAN ORISINALITAS... ii LEMBAR PERSYARATAN GELAR SARJANA... iii LEMBAR PERSETUJUAN PEMBIMBING... iv KATA PENGANTAR... v ABSTRAK... vi ABSTRACT... vii DAFTAR ISI... viii
Lebih terperinci14 Teknologi Elektro, Vol. 16, No. 02, Mei - Agustus Z 2eq = Impedansi eqivalen urutan negatif
Teknologi Elektro, Vol. 16, No. 02, Mei - Agustus 2017 13 Studi Analisis Kapasitas Pengaman Kopel dalam Mensuplai Daya di Bandara Internasional Ngurah Rai Saat Hilangnya Suplai Daya Dari Gayatri atau Bandara
Lebih terperinciBAB I PENDAHULUAN 1.1 Latar Belakang
BAB I PENDAHULUAN 1.1 Latar Belakang Dalam perkembangan teknologi seperti saat ini, peralatan listrik yang berbasis elektronika daya berkembang pesat, karena mempunyai efisiensi yang tinggi dan perancangannya
Lebih terperinciABSTRAK Kata kunci : Beban non linier, Harmonisa, THD, filter aktif high-pass.
ABSTRAK Hotel The Bene Kuta yang berlokasi di jalan Bene Sari Kuta-Bali, memiliki suplai daya terpasang berkapasitas 630 KVA. Beban non linier yang terdapat pada SDP mengakibatkan adanya distorsi harmonisa
Lebih terperinciBAB 2 TINJAUAN PUSTAKA. Beban non linier pada peralatan rumah tangga umumnya merupakan peralatan
BAB 2 TINJAUAN PUSTAKA 2.1. Sumber Harmonisa Beban non linier pada peralatan rumah tangga umumnya merupakan peralatan elektronik yang didalamnya banyak terdapat penggunaan komponen semi konduktor pada
Lebih terperinciBAB II TINJAUAN PUSTAKA
BAB II TINJAUAN PUSTAKA 2.1 Kualitas Daya Listrik Peningkatan terhadap kebutuhan dan konsumsi energi listrik yang baik dari segi kualitas dan kuantitas menjadi salah satu alasan mengapa perusahaan utilitas
Lebih terperinciBAB 1 PENDAHULUAN. adalah rectifier, converter, inverter, tanur busur listrik, motor-motor listrik,
BAB 1 PENDAHULUAN 1.1. Latar Belakang Dewasa ini banyak konsumen daya listrik menggunakan beban tidak linier, baik konsumen rumah tangga, perkantoran maupun industri. Contoh beban tidak linier adalah rectifier,
Lebih terperinciStudi Perencanaan Filter Hybrid Untuk Mengurangi Harmonisa Pada Proyek Pakistan Deep Water Container Port
JURNAL TEKNIK ITS Vol. 4, No. 2, (2015) ISSN: 2337-3539 (2301-9271 Print) A-142 Studi Perencanaan Filter Hybrid Untuk Mengurangi Harmonisa Pada Proyek Pakistan Deep Water Container Port Rahman Efandi,
Lebih terperinciDAFTAR ISI JUDUL... LEMBAR PRASYARAT GELAR... LEMBAR PERNYATAAN ORISINALITAS... LEMBAR PENGESAHAN... UCAPAN TERIMAKASIH... ABSTRAK...
DAFTAR ISI JUDUL... LEMBAR PRASYARAT GELAR... LEMBAR PERNYATAAN ORISINALITAS... LEMBAR PENGESAHAN... UCAPAN TERIMAKASIH... ABSTRAK... ABSRACT... DAFTAR ISI... DAFTAR TABEL... DAFTAR GAMBAR... DAFTAR LAMPIRAN...
Lebih terperinciANALISIS PENYEBAB KEGAGALAN KERJA SISTEM PROTEKSI PADA GARDU AB
ANALISIS PENYEBAB KEGAGALAN KERJA SISTEM PROTEKSI PADA GARDU AB 252 Oleh Vigor Zius Muarayadi (41413110039) Jurusan Teknik Elektro, Fakultas Teknik, Universitas Mercu Buana Sistem proteksi jaringan tenaga
Lebih terperinciANALISIS KETIDAKSEIMBANGAN BEBAN PADA JARINGAN DISTRIBUSI SEKUNDER GARDU DISTRIBUSI DS 0587 DI PT. PLN (Persero) DISTRIBUSI BALI RAYON DENPASAR
E-Journal SPEKTRUM Vol., No. 2 Desember 2016 ANALSS KETDAKSEMBANGAN BEBAN PADA JARNGAN DSTRBUS SEKUNDER GARDU DSTRBUS DS 0587 D PT. PLN (Persero) DSTRBUS BAL RAYON DENPASAR W. Susongko 1, N. Setiawan 2,
Lebih terperinciImplementasi Dynamic Voltage Restorer (DVR) Multifungsi untuk perbaikan kualitas daya
Implementasi Dynamic Voltage Restorer (DVR) Multifungsi untuk perbaikan kualitas daya Ir. M. Abdul Hamid, MT, Ir. Eko Nurcahyo, MT Program Studi Teknik Elektro, Fakultas Teknologi Industri, ITN Malang
Lebih terperinciIII PENGUMPULAN DAN PENGOLAHAN DATA
III PENGUMPULAN DAN PENGOLAHAN DATA 3.1. Umum Berdasarkan standard operasi PT. PLN (Persero), setiap pelanggan energi listrik dengan daya kontrak di atas 197 kva dilayani melalui jaringan tegangan menengah
Lebih terperinciAnalisis Pengaruh Harmonisa Terhadap Rugi-Rugi Daya (Losses) Pada Transformator di Penyulang Sedap Malam
Teknologi Elektro, Vol. 16, No1, Januari-April 2017 97 Analisis Pengaruh Harmonisa Terhadap Rugi-Rugi Daya (Losses) Pada Transformator di Penyulang Sedap Malam I.G Ariana 1,I.W. Rinas 2, I.G.D Arjana 3
Lebih terperinciNASKAH PUBLIKASI ANALISIS GANGGUAN HUBUNG SINGKAT TIGA FASE LINE TO GROUND
NASKAH PUBLIKASI ANALISIS GANGGUAN HUBUNG SINGKAT TIGA FASE LINE TO GROUND PADA SISTEM DISTRIBUSI STANDAR IEEE 13 BUS DENGAN MENGGUNAKAN PROGRAM ETAP POWER STATION 7.0 Diajukan oleh: INDRIANTO D 400 100
Lebih terperinciBAB 3 METODE PENELITIAN. Serdang. Dalam memenuhi kebutuhan daya listrik industri tersebut menggunakan
BAB 3 METODE PENELITIAN 3.1 Lokasi Penelitian Penelitian yang dilakukan adalah studi kasus pada pabrik pengolahan plastik. Penelitian direncanakan selesai dalam waktu 6 bulan dan lokasi penelitian berada
Lebih terperinciJURNAL TEKNIK ITS Vol. 1, No. 1 (Sept. 2012) ISSN: B-97
JURNAL TEKNIK ITS Vol. 1, No. 1 (Sept. 2012) ISSN: 2301-9271 B-97 Evaluasi Harmonisa dan Perencanaan Filter Pasif pada Sisi Tegangan 20 Akibat Penambahan Beban pada Sistem Kelistrikan Pabrik Semen Tuban
Lebih terperinciTeknologi Elektro, Vol. 14, No.2, Juli - Desember
Teknologi Elektro, Vol. 14, No.2, Juli - Desember 2015 1 ANALISA KEANDALAN SISTEM DISTRIBUSI PENYULANG KAMPUS DENGAN MENGGUNAKAN PENGGABUNGAN METODE SECTION TECKNIQUE DAN RIA Gusti Putu Budi Arigandi 1,
Lebih terperinciAplikasi Filter Pasif Pada Beban Inverter Tiga Fase Berbeban
Aplikasi Filter Pasif Pada Beban Inverter Tiga Fase Berbeban Wahri Sunanda Jurusan Teknik Elektro Fakultas Teknik Universitas Bangka Belitung wahrisunanda@ubb.ac.id Abstract Harmonic is one of sinusoidal
Lebih terperinciStudi Penempatan Titik Pentanahan Kawat Tanah pada Penyulang Serangan
Teknologi Elektro, Vol.15, No.1, Januari - Juni 016 7 Studi Penempatan Titik Pentanahan Kawat Tanah pada Penyulang Serangan I W. A. Teja Baskara 1, I G. Dyana Arjana, I W. Rinas 3 Abstract Ground wire
Lebih terperinciSTUDI PENENTUAN KAPASITAS PEMUTUS TENAGA SISI 20 KV PADA GARDU INDUK SEKAYU
Mikrotiga, Vol 2, No.1 Januari 2015 ISSN : 2355-0457 16 STUDI PENENTUAN KAPASITAS PEMUTUS TENAGA SISI 20 KV PADA GARDU INDUK SEKAYU Hendra 1*, Edy Lazuardi 1, M. Suparlan 1 1 Jurusan Teknik Elektro, Fakultas
Lebih terperinciPENGARUH CAPACITOR BANK SWITCHING TERHADAP KUALITAS DAYA EFFECT OF CAPACITOR BANK SWITCHING ON POWER QUALITY
Jurnal Teknik dan Ilmu Komputer PENGARUH CAPACITOR BANK SWITCHING TERHADAP KUALITAS DAYA EFFECT OF CAPACITOR BANK SWITCHING ON POWER QUALITY Emmy Hosea 1, Ontoseno Penangsang 2, Algavien Tinus 3 1&3 Program
Lebih terperinciPENGARUH HARMONISA PADA GARDU TRAFO TIANG DAYA 200 KVA DI PT PLN (Persero) APJ SURABAYA UTARA
PENGARUH HARMONISA PADA GARDU TRAFO TIANG DAYA 200 KVA DI PT PLN (Persero) APJ SURABAYA UTARA Titiek Suheta Teknik Elektro, Fakultas Teknologi Industri, Institut Teknologi Adhi Tama Surabaya sondysuheta@yahoo.com
Lebih terperinciANALISA KEDIP TEGANGAN PADA SISTEM DISTRIBUSI TENAGA LISTRIK 20 KV AKIBAT HUBUNG SINGKAT PADA PENYULANG PEDAN 1 KLATEN
ANALISA KEDIP TEGANGAN PADA SISTEM DISTRIBUSI TENAGA LISTRIK 20 KV AKIBAT HUBUNG SINGKAT PADA PENYULANG PEDAN 1 KLATEN Disusun sebagai salah satu syarat menyelesaikan Program Studi Strata I pada Jurusan
Lebih terperinciABSTRAK Kata Kunci :
ABSTRAK Transformator 3 pada GI Pesanggaran mendapat penambahan 4 blok pembangkit dengan daya maksimum sebesar 60 MW daya dari keempat blok pembangkit tersebut digunakan untuk mensuplai beban penyulang
Lebih terperinciPENGARUH HARMONISA PADA GARDU TRAFO TIANG DAYA 200 KVA DI PT PLN (Persero) APJ SURABAYA UTARA
PENGARUH HARMONISA PADA GARDU TRAFO TIANG DAYA 200 KVA DI PT PLN (Persero) APJ SURABAYA UTARA Titiek Suheta Teknik Elektro, Fakultas Teknologi Industri, Institut Teknologi Adhi Tama Surabaya sondysuheta@yahoo.com
Lebih terperinciWATAK HARMONIK PADA INVERTER TIGA FASA TAK BERBEBAN
WATAK HARMONIK PADA INVERTER TIGA FASA TAK BERBEBAN Wahri Sunanda 1, Yuli Asmi Rahman 2 1 Teknik Elektro Fakultas Teknik Universitas Bangka Belitung 2 Teknik Elektro Fakultas Teknik Universitas Tadulako
Lebih terperinciTotal Loss Energy Efisiensi Transformator Kualitas Daya Listrik (Power Quality) Harmonisa
DAFTAR ISI JUDUL... i LEMBAR PERNYATAAN ORISINALITAS... ii LEMBAR PRASYARAT GELAR SARJANA... iii LEMBAR PENGESAHAN... iv UCAPAN TERIMAKASIH... v ABSTRAK... vii ABSTRACT... viii DAFTAR ISI... ix DAFTAR
Lebih terperinciANALISA SETTING RELAI PENGAMAN AKIBAT REKONFIGURASI PADA PENYULANG BLAHBATUH
ANALISA SETTING RELAI PENGAMAN AKIBAT REKONFIGURASI PADA PENYULANG BLAHBATUH I K.Windu Iswara 1, G. Dyana Arjana 2, W. Arta Wijaya 3 1,2,3 Jurusan Teknik Elektro, Fakultas Teknik Universitas Udayana, Denpasar
Lebih terperinciDesain Filter Pasif Pada Sistem Kelistrikan Industri Guna Mengurangi Distorsi Harmonisa
Desain Filter Pasif Pada Sistem Kelistrikan Industri Guna Mengurangi Distorsi Harmonisa Soedibyo dan Sjamsjul Anam Jurusan Teknik Elektro Fakultas Teknologi Industri - Institut Teknologi Sepuluh Nopember
Lebih terperinciKARYA ILMIAH ANALISA DISTORSI HARMONISA PENGOPERASIAN INVERTER PADA PLTS ABANG DI KARANGASEM
KARYA ILMIAH ANALISA DISTORSI HARMONISA PENGOPERASIAN INVERTER PADA PLTS ABANG DI KARANGASEM oleh : I WAYAN RINAS NIP. 196412311992031028 JURUSAN TEKNIK ELEKTRO DAN KOMPUTER FAKULTAS TEKNIK UNIVERSITAS
Lebih terperinciAnalisa Pengaruh Pemasangan Distributed Generation Terhadap Profil Tegangan Pada Penyulang Abang Karangasem
Teknologi Elektro, Vol. 16, No. 3,September - Desember 217 79 Analisa Pengaruh Pemasangan Distributed Generation Terhadap Profil Pada Penyulang Abang Karangasem I Nyoman Cita Artawa 1, I Wayan Sukerayasa
Lebih terperinciPenentuan Nilai Arus Pemutusan Pemutus Tenaga Sisi 20 KV pada Gardu Induk 30 MVA Pangururan
Yusmartato, Ramayulis, Abdurrozzaq Hsb., Penentuan... ISSN : 598 1099 (Online) ISSN : 50 364 (Cetak) Penentuan Nilai Arus Pemutusan Pemutus Tenaga Sisi 0 KV pada Gardu Induk 30 MVA Pangururan Yusmartato
Lebih terperinciDAFTAR ISI SAMPUL DALAM... LEMBAR PERNYATAAN ORISINALITAS... PERSYARATAN GELAR... LEMBAR PENGESAHAN... UCAPAN TERIMA KASIH... ABSTRACT...
ABSTRAK Gangguan hubung singkat yang terjadi pada sistem tenaga listrik dapat mengakibatkan terputusnya penyaluran tenaga listrik kepada konsumen. Gangguan tersebut bisa disebabkan dari gangguan internal
Lebih terperinciPENGARUH PEMASANGAN DISTRIBUTED GENERATION (DG) TERHADAP RESPON GANGGUAN PADA SISTEM DISTRIBUSI
PENGARUH PEMASANGAN DISTRIBUTED GENERATION (DG) TERHADAP RESPON GANGGUAN PADA SISTEM DISTRIBUSI Agus Supardi Jurusan Teknik Elektro, Fakultas Teknik, Universitas Muhammadiyah Surakarta Jl. A. Yani Tromol
Lebih terperinciSTUDI RUGI DAYA SISTEM KELISTRIKAN BALI AKIBAT PERUBAHAN KAPASITAS PEMBANGKITAN DI PESANGGARAN
Teknologi Elektro, Vol.,., Juli Desember 0 9 STUDI RUGI DAYA SISTEM KELISTRIKAN BALI AKIBAT PERUBAHAN KAPASITAS PEMBANGKITAN DI PESANGGARAN I P. A. Edi Pramana, W. G. Ariastina, I W. Sukerayasa Abstract
Lebih terperinciSIMULASI PEMASANGAN FILTER HARMONISA PADA SISTEM TENAGA LISTRIK MENGGUNAKAN SOFTWARE ETAP
Prosiding Seminar Nasional Volume 02, Nomor 1 ISSN 2443-1109 SIMULASI PEMASANGAN FILTER HARMONISA PADA SISTEM TENAGA LISTRIK MENGGUNAKAN SOFTWARE ETAP Abdul Haris Mubarak 1 Universitas Cokroaminoto Palopo
Lebih terperinciLAMPIRAN A RANGKAIAN CATU DAYA BEBAN TAK LINIER. Berikut adalah gambar rangkaian catu daya pada lampu hemat energi :
LAMPIRAN A RANGKAIAN CATU DAYA BEBAN TAK LINIER Berikut adalah gambar rangkaian catu daya pada lampu hemat energi : Gb-A.1. Rangkaian Catu Daya pada Lampu Hemat Energi Gb-A.2. Rangkaian Catu Daya pada
Lebih terperinci2.2.6 Daerah Proteksi (Protective Zone) Bagian-bagian Sistem Pengaman Rele a. Jenis-jenis Rele b.
DAFTAR ISI JUDUL SAMPUL DALAM... ii LEMBAR PERNYATAAN ORISINALITAS... iii LEMBAR PERSYARATAN GELAR... iv LEMBAR PENGESAHAN... v UCAPAN TERIMA KASIH... vi ABSTRAK... viii ABSTRACT... ix DAFTAR ISI... x
Lebih terperinciAplikasi Filter Pasif Rc Untuk Mereduksi Harmonik Pada Ac/Dc/Ac Konverter. Asnil*) *Staf Pengajar Jurusan Teknik Elektro, FT-UNP
Aplikasi Filter Pasif Rc Untuk Mereduksi Harmonik Pada Ac/Dc/Ac Konverter Asnil*) *Staf Pengajar Jurusan Teknik Elektro, FT-UNP Abstract This paper presents the design and analysis of a low pass passive
Lebih terperinciBAB V PENUTUP 5.1 Simpulan Saran DAFTAR PUSTAKA LAMPIRAN LAMPIRAN
DAFTAR ISI HALAMAN SAMPUL DALAM... i PRASYARAT GELAR... ii LEMBAR PERNYATAAN ORISINALITAS... iii LEMBAR PERSETUJUAN PEMBIMBING... iv UCAPAN TERIMAKASIH... v ABSTRAK... vii ABSTRACT... viii DAFTAR ISI...
Lebih terperinciFILTER AKTIF SHUNT 3 PHASE BERBASIS ARTIFICIAL NEURAL NETWORK (ANN) UNTUK MENGKOMPENSASI HARMONISA PADA SISTEM DISTRIBUSI 220/380 VOLT
FILTER AKTIF SHUNT 3 PHASE BERBASIS ARTIFICIAL NEURAL NETWORK (ANN) UNTUK MENGKOMPENSASI HARMONISA PADA SISTEM DISTRIBUSI 220/380 VOLT Nama : Andyka Bangun Wicaksono NRP : 22 2 111 050 23 Dosen Pembimbing
Lebih terperinciOLEH : FRANS JOYOKO SIANTURI / MTE
SIMULASI PEMULIHAN KEDIP TEGANGAN AKIBAT GANGGUAN HUBUNG SINGKAT SATU FASA KE TANAH PADA SISTEM DISTRIBUSI TIGA FASA MENGGUNAKAN DVR BERBASIS PENGENDALI LOGIKA FUZZY TESIS OLEH : FRANS JOYOKO SIANTURI
Lebih terperinciJurnal Media Elektro Vol. V No. 2 ISSN: ANALISIS RUGI-RUGI DAYA JARINGAN DISTRIBUSI 20 kv PADA SISTEM PLN KOTA KUPANG
ANALISIS RUGI-RUGI DAYA JARINGAN DISTRIBUSI 20 kv PADA SISTEM PLN KOTA KUPANG Sri Kurniati. A, Sudirman. S Jurusan Teknik Elektro, Fakultas Sains dan Teknik, Undana, AdiSucipto Penfui, Kupang, Indonesia,
Lebih terperinciBAB I PENDAHULUAN. sistem tenaga listrik terdiri dari beberapa sub sistem, yaitu pembangkitan,
BAB I PENDAHULUAN 1.1. Latar Belakang Masalah Tenaga listrik disuplai ke konsumen melalui sistem tenaga listrik. sistem tenaga listrik terdiri dari beberapa sub sistem, yaitu pembangkitan, transmisi, dan
Lebih terperinciBAB 2 TINJAUAN PUSTAKA
BAB 2 TINJAUAN PUSTAKA 2.1 Distributed Generation Distributed Generation adalah sebuah pembangkit tenaga listrik yang bertujuan menyediakan sebuah sumber daya aktif yang terhubung langsung dengan jaringan
Lebih terperinciStudi Analisis Koordinasi Over Current Relay (OCR) dan Ground Fault Relay (GFR) pada Recloser di Saluran Penyulang Penebel
Teknologi Elektro, Vol. 16, No. 02, Mei - Agustus 2017 37 Studi Analisis Koordinasi Over Current Relay (OCR) dan Ground Fault Relay (GFR) pada Recloser di Saluran Penyulang Penebel I D.G.Agung Budhi Udiana
Lebih terperinciBAB 2 TINJAUAN PUSTAKA. 2.1 Sistem Catu Daya Listrik dan Distribusi Daya
9 BAB 2 TINJAUAN PUSTAKA 2.1 Sistem Catu Daya Listrik dan Distribusi Daya Pada desain fasilitas penunjang Bandara Internasional Kualanamu adanya tuntutan agar keandalan sistem tinggi, sehingga kecuali
Lebih terperinciPOLITEKNIK NEGERI SRIWIJAYA BAB I PENDAHULUAN
BAB I PENDAHULUAN 1.1 Latar Belakang Dalam operasi pelayanan penyediaan energi listrik khususnya di GI Bungaran, sistem tenaga listrik dapat mengalami berbagai macam gangguan, misal gangguan dari hubung
Lebih terperinciANALISIS DAN PERANCANGAN FILTER PASIF UNTUK MEREDUKSI PENGARUH HARMONISA PADA INVERTER 3-FASA MENGGUNAKAN MATLAB/SIMULINK
ANALISIS DAN PERANCANGAN FILTER PASIF UNTUK MEREDUKSI PENGARUH HARMONISA PADA INVERTER 3-FASA MENGGUNAKAN MATLAB/SIMULINK PUBLIKASI ILMIAH Disusun sebagai salah satu syarat menyelesaikan Program Studi
Lebih terperinciAnalisis Gangguan Hubung Singkat untuk Penentuan Breaking Capacity Pada Penyulang Kutai, Ludruk, dan Reog di GIS Gambir Lama
Analisis Gangguan Hubung Singkat untuk Penentuan Breaking Capacity Pada Kutai, Ludruk, dan Reog di GIS Gambir Lama Ir. I Made Ardita Y, M.T., Farekh Huzair Departemen Teknik Elektro,, Depok 644 Tel: (0)
Lebih terperinciJURNAL TEKNIK ITS Vol. 1, No. 1 (Sept. 2012) ISSN: B-91
JURNAL TEKNIK ITS Vol. 1, No. 1 (Sept. 2012) ISSN: 2301-9271 B-91 Desain dan Simulasi Switched Filter Compensation Berbasis Tri Loop Error Driven Weighted Modified Pid Controller untuk Peningkatan Kualitas
Lebih terperinciSimulasi dan Analisis Fenomena Resonansi Akibat Harmonisa Orde Genap dengan Menggunakan Software ETAP
Simulasi dan Analisis Fenomena Resonansi Akibat Harmonisa Orde Genap dengan Menggunakan Software ETAP Nanang Joko Aris Wibowo 2206 100 006 Bidang Studi Teknik Sistem Tenaga Jurusan Teknik Elektro, ITS,
Lebih terperinciAnalisa Koordinasi Over Current Relay Dan Ground Fault Relay Di Sistem Proteksi Feeder Gardu Induk 20 kv Jababeka
Analisa Koordinasi Over Current Relay Dan Ground Fault Relay Di Sistem Proteksi Feeder Gardu Induk 20 kv Jababeka Erwin Dermawan 1, Dimas Nugroho 2 1) 2) Jurusan Teknik Elektro Fakultas Teknik Universitas
Lebih terperinciBAB IV ANALISIS DAN PEMBAHASAN
BAB IV ANALISIS DAN PEMBAHASAN 4.1 Gambaran Umum Fakultas Teknik UMY 4.1.1 Sejarah Fakultas Teknik UMY didirikan pada tanggal 24 Rabi ul Akhir 1401 H, bertepatan dengan tanggal 1 Maret 1981 M, berdasarkan
Lebih terperinciBAB 1 PENDAHULUAN. Peradaban manusia modern adalah salah satunya ditandaidengan kemajuan
1 BAB 1 PENDAHULUAN 1.1. Latar Belakang Peradaban manusia modern adalah salah satunya ditandaidengan kemajuan teknologi. Dalam bidang elektronika, peralatan seperti TV, komputer, Air Conditioner, ataulampu
Lebih terperinciBAB II LANDASAN TEORI ANALISA HUBUNG SINGKAT DAN MOTOR STARTING
BAB II LANDASAN TEORI ANALISA HUBUNG SINGKAT DAN MOTOR STARTING 2.1 Jenis Gangguan Hubung Singkat Ada beberapa jenis gangguan hubung singkat dalam sistem tenaga listrik antara lain hubung singkat 3 phasa,
Lebih terperinciSIMULASI TEGANGAN DIP PADA JARINGAN TEGANGAN MENENGAH MENGGUNAKAN MODEL EMTP
SIMULASI TEGANGAN DIP PADA JARINGAN TEGANGAN MENENGAH MENGGUNAKAN MODEL EMTP Agung Warsito, Abdul Syakur, Nur Taat Sayekti Jurusan Teknik Elektro Fakultas Teknik Universitas Diponegoro Jl. Prof. Soedarto
Lebih terperinciANALISIS TEORITIS PENEMPATAN TRANSFORMATOR DISTRIBUSI MENURUT JATUH TEGANGAN DI PENYULANG BAGONG PADA GARDU INDUK NGAGEL
Analisis Teoritis Penempatan Transformator Distribusi Menurut Jatuh Tegangan Di Penyulang Bagong ANALISIS TEORITIS PENEMPATAN TRANSFORMATOR DISTRIBUSI MENURUT JATUH TEGANGAN DI PENYULANG BAGONG PADA GARDU
Lebih terperinciBAB III PERANCANGAN ALAT
BAB III PERANCANGAN ALAT 3.1 Flow Chart Pengujian Deskripsi sistem rancang rangkaian untuk pengujian transformator ini digambarkan dalam flowchart sebagai berikut : Mulai Peralatan Uji Merakit Peralatan
Lebih terperinciANALISIS PENGARUH HARMONISA TERHADAP PANAS PADA BELITAN TRANSFORMATORDISTRIBUSI
SINGUDA ENSIKOM VOL. 6 NO.3 /Maret 24 ANALISIS PENGARUH HARMONISA TERHADAP PANAS PADA BELITAN TRANSFORMATORDISTRIBUSI Hotbe Hasugian, Panusur SML.Tobing Konsentrasi Teknik Energi Listrik, Departemen Teknik
Lebih terperinciBAB I PENDAHULUAN. Dalam segi peningkatan kualitas sistem tenaga listrik, banyak aspek yang bisa
BAB I PENDAHULUAN 1.1 Latar Belakang Dalam segi peningkatan kualitas sistem tenaga listrik, banyak aspek yang bisa dievaluasi, salah satunya adalah pada proses proteksi saluran transmisi listrik menggunakan
Lebih terperinciAnalisis Pemasangan Filter Pasif untuk Menanggulangi Distorsi Harmonisa Terhadap Beban non Linier di PT.Wisesa Group
88 Teknologi Elektro, Vol. 16, No. 02, Mei - Agustus 2017 Analisis Pemasangan Pasif untuk Menanggulangi Distorsi Harmonisa Terhadap Beban non Linier di PT.Wisesa Group I Wayan Wahyu Adi Merta 1, I Gusti
Lebih terperinciANALISIS KETIDAKSEIMBANGAN BEBAN TRAFO 1 GI SRONDOL TERHADAP RUGI-RUGI AKIBAT ARUS NETRAL DAN SUHU TRAFO MENGGUNAKAN ETAP
ANALISIS KETIDAKSEIMBANGAN BEBAN TRAFO 1 GI SRONDOL TERHADAP RUGI-RUGI AKIBAT ARUS NETRAL DAN SUHU TRAFO MENGGUNAKAN ETAP 12.6.0 Dennis Satria Wahyu Jayabadi *), Bambang Winardi, and Mochammad Facta Departemen
Lebih terperinciANALISIS GANGGUAN HUBUNG SINGKAT TIGA FASE PADA SISTEM DISTRIBUSI STANDAR IEEE 13 BUS
NASKAH PUBLIKASI ANALISIS GANGGUAN HUBUNG SINGKAT TIGA FASE PADA SISTEM DISTRIBUSI STANDAR IEEE 13 BUS DENGAN MENGGUNAKAN PROGRAM ETAP POWER STATION 7.0 Diajukan oleh: FAJAR WIDIANTO D 400 100 060 JURUSAN
Lebih terperinciSTUDI ANALISIS KEDIP TEGANGAN AKIBAT PENGASUTAN MOTOR INDUKSI DI PT. PRIMATEXCO INDONESIA BATANG
STUDI ANALISIS KEDIP TEGANGAN AKIBAT PENGASUTAN MOTOR INDUKSI DI PT. PRIMATEXCO INDONESIA BATANG TUGAS AKHIR Disusun Guna Memperoleh Gelar Sarjana Strata Satu Teknik Fakultas Teknik Jurusan Teknik Elektro
Lebih terperinciBAB 1 PENDAHULUAN. proses yang kontinu membutuhkan komponen-komponen elektronika dan komponen
BAB 1 PENDAHULUAN 1.1. Latar Belakang Masalah Kebutuhan peningkatan produktifitas dalam industri dan diinginkannya suatu proses yang kontinu membutuhkan komponen-komponen elektronika dan komponen elektronika
Lebih terperinci