PERFORMANSI SISTEM REFRIGERASI HIBRIDA PERANGKAT PENGKONDISIAN UDARA MENGGUNAKAN REFRIGERAN HIDROKARBON SUBSITUSI R-22
|
|
- Teguh Atmadjaja
- 7 tahun lalu
- Tontonan:
Transkripsi
1 PERFORMANSI SISTEM REFRIGERASI HIBRIDA PERANGKAT PENGKONDISIAN UDARA MENGGUNAKAN REFRIGERAN HIDROKARBON SUBSITUSI Azridjal Aziz (1), Yazmendra Rosa (2) (1) Staf Pengajar Jurusan Teknik Mesin Universitas Riau (2) Staf Pengajar Jurusan Teknik Mesin Politeknik Negeri Padang ABSTRACT This research was conducted to determine the performance of air conditioning device which is modified into a hybrid refrigeration machines, such as cooling capacity, heating capacity, power compression, coefficient of performance (COP) and the performance factor (PF). The study was conducted by comparing data and test results between hydrocarbon refrigerant HCR22 and halocarbon refrigerant R22. The results shown the use of hydrocarbon refrigerant mass HCR22 on hybrid vapor refrigeration machine more efficient 57.78% compared to the use of halocarbon refrigerant mass R22, because the refrigerant HCR22 have a higher latent heat than the refrigerant R22. On the use of hydrocarbons HCR22 to halocarbon R22, the cooling effects increase 18.7% while warming effect decrease 9.3%, because it occurs at a lower condenser pressure (27.73%). The compressor electric power consumption using refrigerant HCR22 more efficient 25.4% than using the refrigerant R22. Performance of a hybrid vapor refrigeration machine performance increase using Hydrocarbon HCR22: COP increase 57.38%, PF increase 2.7%, and TP increase 35.43%. The cooling rate and heating rate using halocarbon R22 and hydrocarbons HCR22 tend to the same condition. Keywords: Refrigerant, refrigeration, halocarbon, hydrocarbon, air conditioning 1. PENDAHULUAN Salah satu usaha dalam meningkatkan efisiensi pemakaian energi adalah dengan memanfaatkan kembali (recovery) energi yang selama ini dibiarkan terbuang pada suatu mesin konversi energi. Alasan paling umum digunakan dalam usaha memodifikasi mesin refrigerasi adalah efisiensi penggunaan energi. Mesin refrigerasi yang berfungsi sebagai mesin pengkondisian udara (Air Conditioning) umumnya digunakan untuk mengkondisikan ruangan dengan memanfaatkan efek pendinginan dari evaporator yang memberikan rasa nyaman dan sejuk untuk penghuni atau orang yang bekerja di dalam ruangan tersebut baik di perumahan, perkantoran dan industri. Mesin refrigerasi adalah salah satu jenis mesin konversi energi, dimana sejumlah energi dibutuhkan untuk menghasilkan efek pendinginan. Di sisi lain, panas dibuang oleh sistem ke lingkungan untuk memenuhi prinsip-prinsip termodinamika agar mesin dapat berfungsi [2]. Bertolak dari kasus mesin refrigerasi dan mesin pompa panas di atas, maka berbagai usaha telah dilakukan untuk mengembangkan suatu sistem yang menggunakan prinsip refrigerasi dan pompa panas dalam satu mesin. Pada mesin terpadu ini efek pendinginan dan efek pemanasan dapat dihasilkan dan dimanfaatkan secara bersamaan, sehingga daya guna mesin menjadi lebih tinggi. Mesin terpadu dengan fungsi ganda ini dikenal dengan mesin refrigerasi hibrida, karena mesin refrigerasi paling banyak beroperasi dengan siklus kompesi uap, maka mesin ini disebut mesin refrigerasi siklus kompresi uap hibrida [1]. Untuk mengoperasikan mesin refrigerasi hibrida dibutuhkan refrigeran sebagai fluida kerja. Refrigeran yang paling banyak digunakan adalah refrigeran halokarbon (halogenated refrigerant) salah satunya adalah jenis HCFC-22 (Hydrochlorofluorocarbon) atau. Namun dari hasil penelitian, refrigeran halokarbon menunjukkan sifat yang dapat merusak lapisan ozon dan berpotensi besar terhadap peningkatan efek pemanasan global, sehingga penggunaan refrigeran tersebut dicanangkan untuk dihapuskan pembuatan dan pemakaiannya [4]. Salah satu refrigeran alternatif pengganti refrigeran halokarbon adalah refrigeran hidrokarbon (hydrocarbon referigerant). Beberapa kelebihan yang dimiliki refrigeran hidrokarbon subsitusi yaitu dapat digunakan sebagai pengganti langsung (drop in substitute) tanpa penggantian komponen, ramah lingkungan (tidak merusak lapisan ozon), pemakaian refrigeran lebih sedikit, hemat energi, dan memenuhi standar internasional [5].
2 Jurnal Teknik Mesin Vol.7, No.1, Juni 21 ISSN Gambar 1. Diagram p-h Siklus Kompresi Uap Ideal Performansi mesin refrigerasi kompresi uap ditentukan oleh beberapa parameter, di antaranya adalah kapasitas pendinginan, kapasitas pemanasan, daya kompresi, koefisien performansi dan performansi faktor. Diagram tekanan-entalpi (mollier diagram) pada Gambar (1) dapat membantu dalam menentukan parameter-parameter tersebut. Untuk menyatakan unjuk kerja dari suatu siklus kompresi uap, yang ditinjau dampak refrigerasi, laju pelepasan kalor, kerja kompresi, Coefficient of Performance (COP) dan Performance Factor (PF) [3,6]. 2. METODOLOGI Penelitian dilakukan di Laboratorium Perawatan dan Perbaikan, Teknik Mesin, Fakultas Teknik, Universitas Riau. Mesin refrigerasi hibrida yang digunakan adalah mesin refrigerasi hasil rancangan yang terdapat di Laboratorium Perawatan dan Perbaikan [2]. Mesin ini beroperasi menggunakan refrigeran hidrokarbon pengganti (HC). Fasilitas Pengujian Fasilitas pengujian terdiri dari satu unit mesin refrigerasi, seperangkat alat ukur dan beberapa peralatan pendukung. Mesin refrigerasi beroperasi pada dua siklus yaitu siklus primer dan siklus sekunder. Siklus primer merupakan siklus refrigeran sedangkan siklus sekunder merupakan siklus air dingin (chiller). Komponen siklus primer terdiri dari satu unit evaporator, satu unit kondensor, satu unit kompresor, satu unit pipa kapiler dan beberapa komponen pendukung seperti pompa air listrik, dan blower. Sedangkan siklus sekunder terdapat satu unit koil pendingin, satu unit koil pemanas dan satu unit koil dummy. Skema sederhana fasilitas pengujian dapat dilihat pada Gambar (2). Gambar 2. Skema Mesin Refrigerasi Hibrida 12
3 Alat ukur yang digunakan yaitu alat ukur tekanan, temperatur, tegangan listrik, arus listrik pada titiktitik yang perlu diuji dan diambil datanya yaitu: termokopel, thermometer digital, pressure gauge dan avometer, timbangan untuk mengukur masa refrigeran optimum dan stopwatch untuk menghitung laju masa air. 3. HASIL DAN PEMBAHASAN Massa Refrigeran R22 dan HCR22 Performansi Massa refrigeran optimum Gram COP HC COP Gambar 3. Grafik massa refrigeran optimum dan COP optimum Pada Gambar (3) terlihat bahwa massa refrigeran optimum R22 sebesar 9 gram pada COP 2,42. Sedangkan massa refrigeran optimum HCR22 sebesar 38 gram pada COP 2,55. Dengan menggunakan refrigeran HCR 22 massa refrigeran lebih hemat 57 persen dari massa refrigeran R22. Laju Pendinginan dan Laju Pemanasan Pada kondisi transient yaitu kondisi saat mesin refrigerasi hibrida mulai dijalankan sampai mencapai kondisi stabil, dapat dilihat bahwa laju pendinginan HCR22 hampir sama dengan R22 Gambar (4). Dimana waktu yang dibutuhkan untuk pendinginan sampai kondisi stabil untuk HCR22 sekitar 5 pada suhu 1,4 C, dan untuk R22 dibutuhkan waktu sekitar 5 pada suhu 1,3 C. Tc out evaporator Laju Pendinginan 4 5 Gambar 4. Laju pendinginan HCR22 dan R Hcr-22 Laju pemanasan sampai kondisi stabil pada HCR22 dan R22 juga menunjukkan laju yang hampir sama, dimana laju pemanasan untuk HCR22 sekitar 55 pada temperatur 46,5 C, dan untuk R22 sekitar 55 pada temperatur 5,4 C, seperti tampak pada Gambar (5). T out Kondensor Laju Pemanasan 4 5 Gambar 5. Laju pemanasan HCR22 dan R Hcr-22 Dampak pendinginan, Dampak pemanasan dan Kerja Kompressor (Perhitungan sisi refrigeran sekunder) KW Dampak Pendinginan Gambar 6. Dampak pendinginan HCR22 dan R22 HC Pada Gambar (6) dapat dilihat dampak pendinginan rata-rata dari HCR22 adalah 1,94 kw dan dampak pendinginan rata-rata R22 1,643 kw. Dampak pendinginan HCR22 lebih tinggi dari R22, hal ini dipengaruhi oleh kemampuan penyerapan kalor yang tinggi dari refrigeran hidrokarbon dibanding refrigeran halokarbon. Pada mesin refrigerasi hibrida yang sama HCR22 memiliki massa refrigeran yang lebih sedikit dibanding dengan R22 dengan volume pipa yang sama, karena HCR 22 memiliki kalor laten yang lebih besar dibanding dengan R22. Pada Gambar (7) dapat dilihat rata-rata dampak pemanasan HCR22 adalah 2,22 kw dan dampak pemanasan rata-rata R22 2,45 kw. Dampak pemanasan HCR22 lebih rendah dari R22. Hal ini diakibatkan tekanan kondensor pada R22 yang lebih tinggi dari pada dengan HCR22 seperti yang dapat dilihat pada Gambar (8). Pada tekanan kondensor yang lebih tinggi maka temperatur refrigeran juga lebih tinggi, sehingga kalor pemanasan air akan lebik besar pada temperatur yang lebih tinggi.
4 Jurnal Teknik Mesin Vol.7, No.1, Juni 21 ISSN KW Dampak Pemanasan HC Pada Gambar (1) dapat dilihat bahwa COP dari refrigeran HCR22 lebih tinggi dari R22.COP HCR22 4,125 KW dan R22 2,621 KW. Kondisi ini karena HCR22 dapat menyerap kalor yang lebih besar dari Q R22. Sesuai dengan persamaan e COP sehingga Wk semakin tinggi dampak pendinginan (Qe) maka COP akan semakin besar pula. COP Psi KW Gambar 7. Dampak pemanasan HCR22 dan R Tekanan Kondensor Tekanan Kondensor HC Tekanan Kondensor Gambar 8. Tekanan kondensor HCR22 dan R Daya Kompressor Gambar 9. Daya kompressor HCR22 dan R22 Wk HC Wk Daya kompresor dengan menggunakan refrigeran HCR22 lebih rendah dari daya kompresor yang menggunakan refrigeran R22. Gambar (9). Dimana daya kompressor rata-rata dengan HCR22 adalah,47 kw, sedangkan daya kompresor dengan menggunakan R22 adala,63 kw. Hal ini disebabkan karena jumlah massa refrigeran yang ditekan oleh kompressor dengan HCR22 lebih sedikit jumlahnya dibandingkan dengan massa refrigeran yang ditekan kompressor yang menggunakan R22. Karena kerja kompresor dengan HCR22 lebih ringan dari R22, maka daya listrik yang digunakan untuk menggerakkan kompresor akan lebih hemat dari R22. Kinerja Performansi Mesin Refrigerasi Kompresi Uap Hibrida (COP,PF,TP) (Perhitungan Sisi Refrigeran Sekunder) Satuan Gambar 1. COP mesin refrigerasi hibrida dengan refrigeran HCR22 dan R22 HC Pada Gambar (11) terlihat bahwa Performance Factor dari HCR22 lebih tinggi dari R22, meskipun dampak pemanasan (Qk) dari HCR 22 lebih rendah dari R22. Hal ini di sebabkan karena daya kompresor yang dibutuhkan pada penggunaan refrigeran HCR22 lebih kecil dari R22. Hal ini sesuai dengan persamaan Satuan Q k PF. PF W k HC Gambar 11. PF mesin refrigerasi hibrida dengan refrigeran HCR22 dan R22 Gambar (12) merupakan total performansi dari HCR22 dan R22. Pada gambar terlihat bahwa Total Performansi dari HCR22 lebih tinggi dari R22. Hal ini karena HCR22 memiliki COP dan PF yang lebih tinggi dari R22. 14
5 Performansi Sistem Refrigerasi Hibrida Perangkat Pengkondisian Udara Menggunakan Refrigeran Hidrokarbon Subsitusi (Azridjal Aziz) Satuan TP HC Gambar 12. TP mesin refrigerasi hibrida dengan refrigeran HCR22 dan R22 Pada Tabel (1) dapat dilihat hasil rekapitulasi hasil penelitian dimana dapat disimpulkan bahwa penggunaan refrigeran hidrokarbon terhadap penggunaan refrigeran halokarbon pada mesin kompresi uap hibrida terjadi penghematan massa refrigeran HCR22 sebesar 57,78 %. Laju pendinginan dan laju pemanasan baik refrigeran hidrokarbon maupun refrigeran halokarbon memperlihatkan hasil yang relatif sama. Nilai performansi HCR22 meningkat, yaitu COP naik 57,38 %, PF naik 2,7 %, TP naik 35,43 %. Dampak pendinginan dengan menggunakan refrigeran HCR22 naik 18,7 % dan dampak pemanasannya turun 9,3 %, dimana terjadi pada tekanan kondensor yang lebih rendah 27,73 %. Daya kompresor dengan HCR22 lebih hemat 25,3 % dari pada menggunakan R22. Tabel 1 Rekapitulasi Hasil Pengujian dengan HCR22 dan R22 Deskripsi Nilai Hasil % Massa Refrigeran (gram) HCR22 38 R22 9 Laju Pendinginan () HCR22 5 R22 5 Laju Pemanasan () HCR22 55 R22 55 Coefficient of Performance HCR22 4,125 R22 2,621 Performance Factor HCR22 4,716 Hemat 57,78 sama Sama Naik 57,38 R22 3,97 Naik 2,7 Total Performance HCR22 8,841 R22 6,528 Dampak Pendinginan (kwatt) Naik 35,43 HCR22 1,94 R22 1,643 Dampak Pemanasan (kwatt) HCR22 2,22 Naik 18,7 R22 2,45 Turun 9,3 Tekanan Kondensor (Psig) HCR22 262,33 R22 363,33 Daya Kompresor (kwatt) HCR22,47 R22, KESIMPULAN DAN SARAN Turun 27,73 Turun 25,4 Berdasarkan hasil kajian dapat diambil kesimpulan sebagai berikut : 1. Penggunaan massa refrigeran hidrokarbon HCR22 pada mesin kompresi uap hibrida lebih hemat 57,78 % dibanding penggunaan refrigeran halokarbon R22, karena refrigeran HCR22 mempunyai kalor laten yang lebih tinggi dibanding refrigeran R Laju pendinginan dan laju pemanasan Hidrokarbon HCR22 dan Halokarbon R22 cenderung sama. 3. Pada penggunaan hidrokarbon HCR22 terhadap halokarbon R22, dampak pendinginan naik 18,7 % sedangkan dampak pemanasan turun 9,3 %, karena terjadi pada tekanan kondensor yang lebih rendah 27,73 %. Daya kompresor dengan refrigeran HCR22 lebih hemat 25,4 % dibanding dengan menggunakan R Kinerja performansi mesin kompresi uap hibrida meningkat dengan menggunakan Hidrokarbon HCR22. COP naik 57,38 %, PF naik 2,7 %, TP naik 35,43 %. UCAPAN TERIMA KASIH Penulis mengucapkan terima kasih kepada Direktorat Jenderal Pendidikan Tinggi Departemen Pendidikan Nasional melalui Lembaga Penelitian Universitas Riau yang telah mendanai penelitian ini dari Dana Penelitian Dosen Muda Tahun Anggaran 27. (No. Kontrak 135/J16/PL/III/27) PUSTAKA 1. Amrul, Kaji Eksperimental Karakteristik Mesin Refrigerasi Hibrid Kompresi Uap Susunan Seri dan Paralel dengan Menggunakan Refrigeran Hidrokarbon HCR-12, Tesis, Jurusan Teknik Mesin, ITB, Bandung, Aziz, Azridjal, Penggunaan Hidrokarbon sebagai Refrigeran pada Mesin Refrigerasi 15
6 Jurnal Teknik Mesin Vol.7, No.1, Juni 21 ISSN Siklus Kompresi Uap Hibrida dengan Memanfaatkan Panas Buang Perangkat Pengkondisian Udara, Proceding Hasil Penelitian Lembaga Penelitian Universitas Riau, Pekanbaru, Moran, M.J., Saphiro, H.N., Fundamental of Engineering Thermodinamycs, 3 rd ed, John Wiley & Sons, Inc., New York, Pasek, A.D.,Tandian, N.P., Short Course on the Applications of Hydrocarbon Refrigerants, International Conference on Fluid and Thermal Energy Conversion 2, Bandung, Pasek, A.D.,Tandian, N.P., Adriansyah W., Training of Trainer Refrigeration Servicing Sector, Training Manual, ITB, Bandung, Reynolds, William, Perkins, Henry, Engineering Thermodynamics, 2 nd ed., McGraw- Hill Co, Singapore,
Azridjal Aziz (1), Hanif (2) ABSTRACT
PENGGUNAAN HIDROKARBON SEBAGAI REFRIGERAN PADA MESIN REFRIGERASI SIKLUS KOMPRESI UAP HIBRIDA DENGAN MEMANFAATKAN PANAS BUANG PERANGKAT PENGKONDISIAN UDARA Azridjal Aziz (1), Hanif () (1) Staf Pengajar
Lebih terperinciAzridjal Aziz (1) Hanif (2) ABSTRAK
PENGGUNAAN HIDROKARBON SEBAGAI REFRIGERAN PADA MESIN REFRIGERASI SIKLUS KOMPRESI UAP HIBRIDA DENGAN MEMANFAATKAN PANAS BUANG PERANGKAT PENGKONDISIAN UDARA Azridjal Aziz () Hanif () () Staf Pengajar Jurusan
Lebih terperinciBAB 2. TINJAUAN PUSTAKA
State of the art penelitian BAB 2. TINJAUAN PUSTAKA Mesin refrigerasi Siklus Kompresi Uap Standar (SKU) pada adalah salah satu jenis mesin konversi energi, dimana sejumlah energi dibutuhkan untuk menghasilkan
Lebih terperinciBAB I PENDAHULUAN. 1.1 Latar Belakang Penelitian. Air Conditioning (AC) adalah suatu mesin pendingin sebagai sistem pengkondisi
BAB I PENDAHULUAN 1.1 Latar Belakang Penelitian Air Conditioning (AC) adalah suatu mesin pendingin sebagai sistem pengkondisi udara yang digunakan dengan tujuan untuk memberikan rasa nyaman bagi penghuni
Lebih terperinciPENGARUH PENGGUNAAN KATUP EKSPANSI JENIS KAPILER DAN TERMOSTATIK TERHADAP TEKANAN DAN TEMPERATUR PADA MESIN PENDINGIN SIKLUS KOMPRESI UAP HIBRIDA
PENGARUH PENGGUNAAN KATUP EKSPANSI JENIS KAPILER DAN TERMOSTATIK TERHADAP TEKANAN DAN TEMPERATUR PADA MESIN PENDINGIN SIKLUS KOMPRESI UAP HIBRIDA Eko Saputra 1, Azridjal Aziz 2, Rahmat Iman Mainil 3 Laboratorium
Lebih terperinciPenggunaan Thermal Energy Storage sebagai Penyejuk Udara Ruangan dan Pemanas Air pada Residential Air Conditioning Hibrida
Banjarmasin, 7-8 Oktober 2 Penggunaan Thermal Energy Storage sebagai Penyejuk Udara Ruangan dan Pemanas Air pada Residential Air Conditioning Hibrida Azridjal Aziz,a *, Herisiswanto2,b, Rahmat Iman Mainil3,c,
Lebih terperinciPERFORMANSI RESIDENTIAL AIR CONDITIONING HIBRIDA DENGAN STANDBY MODE MENGGUNAKAN REFRIGERAN HCR-22 UNTUK PENDINGIN DAN PEMANAS RUANGAN
PERFORMANSI RESIDENTIAL AIR CONDITIONING HIBRIDA DENGAN STANDBY MODE MENGGUNAKAN REFRIGERAN HCR- UNTUK PENDINGIN DAN PEMANAS RUANGAN Eko Prasetyo 1, Azridjal Aziz, Rahmat Iman Mainil 3 Laboratorium Rekayasa
Lebih terperinciPengaruh Penggunaan Katup Ekspansi Termostatik dan Pipa Kapiler terhadap Efisiensi Mesin Pendingin Siklus Kompresi Uap
Pengaruh Penggunaan Katup Ekspansi Termostatik dan Pipa Kapiler terhadap Efisiensi Mesin Pendingin Siklus Kompresi Uap Azridjal Aziz 1,a* dan Boby Hary Hartanto 2,b 1,2 Jurusan Teknik Mesin, Fakultas Teknik
Lebih terperinciLAPORAN PENELITIAN. Oleh :
LAPORAN PENELITIAN KAJI EKSPERIMENTAL MESIN REFRIGERASI KOMPRESI UAP HIBRIDA MEMANFAATKAN PANAS BUANG PERANGKAT PENGKONDISIAN UDARA SEBAGAI POMPA PANAS PADA LEMARI PENGERING (DRYING ROOM) MENGGUNAKAN REFRIGERAN
Lebih terperinciKampus Bina Widya Km 12,5 Simpang Baru Panam, Pekanbaru 28293, Indonesia 2 Jurusan Teknik Mesin, Fakultas Teknik, Universitas Bengkulu,
Jurnal Sains dan Teknologi 15 (2), September 16: 51-56 EFEK BEBAN PENDINGIN TERHADAP TEMPERATUR MESIN REFRIGERASI SIKLUS KOMPRESI UAP HIBRIDA DENGAN KONDENSOR DUMMY TIPE TROMBONE COIL ( 1/4, 7,9 m) SEBAGAI
Lebih terperinciBAB IV METODE PENELITIAN
BAB IV METODE PENELITIAN Tahapan-tahapan pengerjaan yang dilakukan dalam penelitian ini adalah sebagai berikut : 1. Tahap Persiapan Penelitian Pada tahapan ini akan dilakukan studi literatur dan pendalaman
Lebih terperinciAzridjal Aziz, ST. MT. NIP
KATA PENGANTAR Alhamdulillah, sebagai rasa terima kasih penulis panjatkan kehadirat Allah SWT, atas kekuatan dan rahmat-nya lah maka penulis akhirnya dapat menyelesaikan laporan penelitian ini. Dalam mengerjakan
Lebih terperinciGambar 5. Skematik Resindential Air Conditioning Hibrida dengan Thermal Energy Storage
BAB 5. HASIL DAN PEMBAHASAN Prinsip Kerja Instalasi Instalasi ini merupakan instalasi mesin pendingin kompresi uap hibrida yang berfungsi sebagai mesin pendingin pada lemari pendingin dan pompa kalor pada
Lebih terperinciKINERJA AIR CONDITONING HIBRIDA PADA LAJU ALIRAN AIR BERBEDA DENGAN KONDENSOR DUMMY TIPE HELICAL COIL (1/4", 6,7 m) SEBAGAI WATER HEATER
Jurnal Sains dan Teknologi 15 (2), September 216: 43-5 KINERJA AIR CONDITONING HIBRIDA PADA LAJU ALIRAN AIR BERBEDA DENGAN KONDENSOR DUMMY TIPE HELICAL COIL (1/4", 6,7 m) SEBAGAI WATER HEATER Faisal Tanjung
Lebih terperinciPENGARUH BEBAN PENDINGIN TERHADAP TEMPERATUR SISTEM PENDINGIN SIKLUS KOMPRESI UAP DENGAN PENAMBAHAN KONDENSOR DUMMY
PENGARUH BEBAN PENDINGIN TERHADAP TEMPERATUR SISTEM PENDINGIN SIKLUS KOMPRESI UAP DENGAN PENAMBAHAN KONDENSOR DUMMY TIPE TROMBONE COIL SEBAGAI WATER HEATER Arya Bhima Satria 1, Azridjal Aziz 2 Laboratorium
Lebih terperinciPENGARUH ALAT EKSPANSI TERHADAP TEMPERATUR DAN TEKANAN PADA MESIN PENDINGIN SIKLUS KOMPRESI UAP
PENGARUH ALAT EKSPANSI TERHADAP TEMPERATUR DAN TEKANAN PADA MESIN PENDINGIN SIKLUS KOMPRESI UAP Boby Hary Hartanto 1, Azridjal Aziz 2 Laboratorium Perawatan, Jurusan Teknik Mesin, Fakultas Teknik Universitas
Lebih terperinciBAB 6. RENCANA TAHAPAN BERIKUTNYA
BAB 6. RENCANA TAHAPAN BERIKUTNYA Tahapan berikutnya yang akan dilakukan adalah sebagai berikut: 1. Tahapan realisasi mesin refrigerasi hibrida dengan modul Evaporative Cooling dan modul Heat Recovery
Lebih terperinciPERBANDINGAN UNJUK KERJA FREON R-12 DAN R-134a TERHADAP VARIASI BEBAN PENDINGIN PADA SISTEM REFRIGERATOR 75 W
PERBANDINGAN UNJUK KERJA FREON R-2 DAN R-34a TERHADAP VARIASI BEBAN PENDINGIN PADA SISTEM REFRIGERATOR 75 W Ridwan Jurusan Teknik Mesin Fakultas Teknologi Industri Universitas Gunadarma e-mail: ridwan@staff.gunadarma.ac.id
Lebih terperinciANALISIS KINERJA AIR CONDITIONING SEKALIGUS SEBAGAI WATER HEATER (ACWH)
ANALISIS KINERJA AIR CONDITIONING SEKALIGUS SEBAGAI WATER HEATER (ACWH) Azridjal Aziz, Herisiswanto, Hardianto Ginting, Noverianto Hatorangan, Wahyudi Rahman Jurusan Teknik Mesin Fakultas Teknik Universitas
Lebih terperinciDAFTAR ISI. KATA PENGANTAR... i. ABSTRAK... iii. DAFTAR GAMBAR... viii. DAFTAR TABEL... x. DAFTAR NOTASI... xi Rumusan Masalah...
DAFTAR ISI KATA PENGANTAR... i ABSTRAK... iii ABSTRACT... iv DAFTAR ISI... v DAFTAR GAMBAR... viii DAFTAR TABEL... x DAFTAR NOTASI... xi BAB I PENDAHULUAN... 1 1.1. Latar Belakang... 1 1.2. Rumusan Masalah...
Lebih terperinciANALISA KINERJA MESIN REFRIGERASI RUMAH TANGGA DENGAN VARIASI REFRIGERAN
ANALISA KINERJA MESIN REFRIGERASI RUMAH TANGGA DENGAN VARIASI REFRIGERAN 1 Amrullah, 2 Zuryati Djafar, 3 Wahyu H. Piarah 1 Program Studi Perawatan dan Perbaikan Mesin, Politeknik Bosowa, Makassar 90245,Indonesia
Lebih terperinciRecovery Energi pada Residential Air Conditioning Hibrida sebagai Pemanas Air dan Penyejuk Udara yang Ramah Lingkungan
Recovery Energi pada Residential Air Conditioning Hibrida sebagai Pemanas Air dan Penyejuk Udara yang Ramah Lingkungan Azridjal Aziz, Herisiswanto, Hardianto Ginting, Noverianto Hatorangan, Wahyudi Rahman
Lebih terperinciBAB II TINJAUAN PUSTAKA. temperatur di bawah 123 K disebut kriogenika (cryogenics). Pembedaan ini
BAB II TINJAUAN PUSTAKA 21 Mesin Refrigerasi Secara umum bidang refrigerasi mencakup kisaran temperatur sampai 123 K Sedangkan proses-proses dan aplikasi teknik yang beroperasi pada kisaran temperatur
Lebih terperinciPENDAHULUAN TINJAUAN PUSTAKA
Jurnal Desiminasi Teknologi, Volume 3, No. 2, Juli 2015 ANALISIS PENGARUH VARIASI MODE KERJA TERHADAP PERFORMANSI MESIN REFRIGERASI KOMPRESI UAPWATER CHILLER TYPE WITH WATER COOLED CONDENSER DENGAN REFRIGERAN
Lebih terperinciPENGARUH STUDI EKSPERIMEN PEMANFAATAN PANAS BUANG KONDENSOR UNTUK PEMANAS AIR
PENGARUH STUDI EKSPERIMEN PEMANFAATAN PANAS BUANG KONDENSOR UNTUK PEMANAS AIR Arif Kurniawan Institut Teknologi Nasional (ITN) Malang; Jl.Raya Karanglo KM. 2 Malang 1 Jurusan Teknik Mesin, FTI-Teknik Mesin
Lebih terperinciBAB 6. RENCANA TAHAPAN BERIKUTNYA
BAB 6. RENCANA TAHAPAN BERIKUTNYA Untuk tahapan berikutnya, analisis mesin refrigerasi hibrida dengan thermal energy strorage dilakukan menggunakan storage ice on coil. Pada prinsipnya perbedaaan mendasar
Lebih terperinciStudi Eksperimen Pemanfaatan Panas Buang Kondensor untuk Pemanas Air
Studi Eksperimen Pemanfaatan Panas Buang Kondensor untuk Pemanas Air Arif Kurniawan Jurusan Teknik Mesin Institut Teknologi Nasional (ITN) Malang E-mail : arifqyu@gmail.com Abstrak. Pada bagian mesin pendingin
Lebih terperinciANALISA PERBANDINGAN PERFORMANSI MESIN PENDINGIN KOMPRESI UAP MENGGUNAKAN R22 DAN R134a DENGAN KAPASITAS KOMPRESOR 1 PK
ANALISA PERBANDINGAN PERFORMANSI MESIN PENDINGIN KOMPRESI UAP MENGGUNAKAN R22 DAN R134a DENGAN KAPASITAS KOMPRESOR 1 PK Dwi Bayu Saputro, Suryadimal, S.T.,M.T 1), Ir. Wenny Marthiana., M.T 2) Program Studi
Lebih terperinciPENGGUNAAN ENCAPSULATED ICE THERMAL ENERGY STORAGE
PENGGUNAAN ENCAPSULATED ICE THERMAL ENERGY STORAGE PADA RESIDENTIAL AIR CONDITIONING MENGGUNAKAN REFRIGERAN HIDROKARBON SUBSTITUSI R-22 YANG RAMAH LINGKUNGAN Azridjal Aziz (1), Afdhal Kurniawan Mainil
Lebih terperinciKAJI EKSPERIMENTAL KARAKTERISTIK PIPA KAPILER DAN KATUP EKSPANSI TERMOSTATIK PADA SISTEM PENDINGIN WATER-CHILLER
No. Vol. Thn.XVII April ISSN : 85-87 KAJI EKSPERIMENTAL KARAKTERISTIK PIPA KAPILER DAN KATUP EKSPANSI TERMOSTATIK PADA SISTEM PENDINGIN WATER-CHILLER Iskandar R. Laboratorium Konversi Energi Jurusan Teknik
Lebih terperinciLAPORAN PENELITIAN. Oleh : Azridjal Aziz, ST. MT. NIP Ir. Herisiswanto, MT. NIP
LAPORAN PENELITIAN PENGEMBANGAN ENERGY EFFICIENT RESIDENTIAL AIR CONDITIONING SYSTEMS DENGAN ENCAPSULATED ICE THERMAL ENERGY STORAGE BERBASIS MESIN REFRIGERASI KOMPRESI UAP MENGGUNAKAN REFRIGERAN HIDROKARBON
Lebih terperinciPROGRAM PENDIDIKAN SARJANA EKSTENSI DEPARTEMEN TEKNIK MESIN FAKULTAS TEKNIK UNIVERSITAS SUMATERA UTARA MEDAN 2016
STUDI EKSPERIMENTAL PERFORMANSI MESIN PENDINGIN (AC SPLIT) 1PK DENGAN PENAMBAHAN ALAT AKUMULATOR MENGGUNAKAN REFRIGERAN MC-22 SKRIPSI Skripsi Yang Diajukan Untuk Melengkapi Syarat Memperoleh Gelar Sarjana
Lebih terperinciPengaruh Aplikasi Refrigeran Hidrokarbon Terhadap Performansi Mobile Air Conditioning
Pengaruh Aplikasi Refrigeran Hidrokarbon Terhadap Performansi Mobile Air Conditioning Puji Saksono Program Studi Teknik Mesin Fakultas Teknologi Industri Universitas Balikpapan Jl. Pupuk Raya PO BOX 335
Lebih terperinciKomparasi Katup Ekspansi Termostatik dan Pipa Kapiler terhadap Temperatur dan Tekanan Mesin Pendingin
Komparasi Katup Ekspansi Termostatik dan Pipa Kapiler terhadap Temperatur dan Tekanan Mesin Pendingin Azridjal Aziz Program Studi Teknik Mesin, Fakultas Teknik, Universitas Riau Kampus Binawidya Km 12,5
Lebih terperinciAPLIKASI MODUL EVAPORATIVE COOLING AKTIF PADA AC SPLIT 1 PK
APLIKASI MODUL EVAPORATIVE COOLING AKTIF PADA AC SPLIT 1 PK Ahmad Wisnu Sulaiman 1, Azridjal Aziz 2, Rahmat Iman Mainil 3 Laboratorium Rekayasa Termal, Jurusan Teknik Mesin, Fakultas Teknik, Universitas
Lebih terperinciPENGGUNAAN ENCAPSULATED ICE THERMAL ENERGY STORAGE
PENGGUNAAN ENCAPSULATED ICE THERMAL ENERGY STORAGE PADA RESIDENTIAL AIR CONDITIONING MENGGUNAKAN REFRIGERAN HIDROKARBON SUBSTITUSI R-22 YANG RAMAH LINGKUNGAN Azridjal Aziz (1), Afdhal Kurniawan Mainil
Lebih terperinciPenerapan Evaporative Cooling Untuk Peningkatan Kinerja Mesin Pengkondisian Udara Tipe Terpisah (AC Split)
Penerapan Evaporative Cooling Untuk Peningkatan Kinerja Mesin Pengkondisian Udara Tipe Terpisah (AC Split) Azridjal Aziz1,a *, Idral2,b, Herisiswanto3,b Rahmat Iman Mainil4,c, David Jenvrizen5,d 1,,2,3,4
Lebih terperinciBAB 2. TINJAUAN PUSTAKA
BAB 2. TINJAUAN PUSTAKA State of the art penelitian Residential Air Conditioning (RAC) didisain untuk memindahkan kalor dari dalam ruangan (indoor) dan membuangnya ke bagian luar ruangan atau ke lingkungan
Lebih terperinciPENGARUH PENAMBAHAN KONDENSOR DUMMY (TIPE HELICAL COIL, TROMBONE COIL DAN MULTI HELICAL COIL) TERHADAP TEMPERATUR RUANGAN DAN TEMPERATUR AIR PANAS
Jurnal Sains dan Teknologi 14 (1), Maret 15: 17- PENGARUH PENAMBAHAN KONDENSOR DUMMY (TIPE HELICAL COIL, TROMBONE COIL DAN MULTI HELICAL COIL) TERHADAP TEMPERATUR RUANGAN DAN TEMPERATUR AIR PANAS Adi Hans
Lebih terperinciPengaruh Debit Udara Kondenser terhadap Kinerja Mesin Tata Udara dengan Refrigeran R410a
Pengaruh Debit Udara Kondenser terhadap Kinerja Mesin Tata Udara dengan Refrigeran R410a Faldian 1, Pratikto 2, Andriyanto Setyawan 3, Daru Sugati 4 Politeknik Negeri Bandung 1,2,3 andriyanto@polban.ac.id
Lebih terperinciBAB I PENDAHULUAN. Sistem refrigerasi telah memainkan peran penting dalam kehidupan
1 BAB I PENDAHULUAN 1.1. Latar belakang Sistem refrigerasi telah memainkan peran penting dalam kehidupan sehari-hari, tidak hanya terbatas untuk peningkatan kualitas dan kenyamanan hidup, namun juga telah
Lebih terperinciLAPORAN PENELITIAN. Oleh : Azridjal Aziz, ST. MT. NIP Ir. Herisiswanto, MT. NIP Dibiayai oleh :
LAPORAN PENELITIAN Pengembangan Cold Storage Hemat Energi Sebagai Mesin Refrigerasi Hibrida Memanfaatkan Panas Buang Kondensor Pada Drying Room Menggunakan Refrigeran Hidrokarbon Subsitusi R-22 Oleh :
Lebih terperinciEFEKTIVITAS PENGGUNAAN THERMOSTATIC EXPANTION VALVE PADA REFRIGERASI AC SPLIT. Harianto 1 dan Eka Yawara 2
EFEKTIVITAS PENGGUNAAN THERMOSTATIC EXPANTION VALVE PADA REFRIGERASI AC SPLIT Harianto 1 dan Eka Yawara 2 Abstract Vapor compression refrigeration is one of refrigeration systems that is most widely used
Lebih terperinciPotensi Air Kondensat Sebagai Media Pendingin Untuk Aplikasi Modul Evaporative Cooling Terhadap Performansi AC Split 1 PK
Potensi Air Kondensat Sebagai Media Pendingin Untuk Aplikasi Modul Evaporative Cooling Terhadap Performansi AC Split 1 PK Muhammad Rif at Syahnan 1, Azridjal Aziz 2, Rahmat Iman Mainil 3 Laboratorium Rekayasa
Lebih terperinciPengaruh Pipa Kapiler yang Dililitkan pada Suction Line terhadap Kinerja Mesin Pendingin
Pengaruh Pipa Kapiler yang Dililitkan pada Suction Line terhadap Kinerja Mesin Pendingin BELLA TANIA Program Pendidikan Fisika Sekolah Tinggi Keguruan dan Ilmu Pendidikan Surya May 9, 2013 Abstrak Mesin
Lebih terperinciPOTENSI PEMANFAATAN ENERGI PANAS TERBUANG PADA KONDENSOR AC SENTRAL UNTUK PEMANAS AIR HEMAT ENERGI
POTENSI PEMANFAATAN ENERGI PANAS TERBUANG PADA KONDENSOR AC SENTRAL UNTUK PEMANAS AIR HEMAT ENERGI Azridjal Aziz 1, Joko Harianto 1, Afdhal Kurniawan Mainil 2 1 Jurusan Teknik Mesin, Universitas Riau Jl.
Lebih terperinciPengaruh High Pressure Kompresor Terhadap Performansi Sistem Refrigerasi Dengan Menggunakan R-134a Dan Refrigeran Hidrokarbon
Pengaruh High Pressure Kompresor Terhadap Performansi Sistem Refrigerasi Dengan Menggunakan Dan Refrigeran Hidrokarbon 1 Puji Saksono, 2 Budha Maryanti Program Studi Teknik Mesin Fakultas Teknologi Industri
Lebih terperinciBAB VI PENGOLAHAN DATA dan ANALISIS DATA
BAB VI PENGOLAHAN DATA dan ANALISIS DATA Dalam pengambilan data perlu diperhatikan beberapa hal yang harus dipersiapkan terlebih dahulu sebelum pengambilan data dilakukan agar tidak terjadi kesalahan yang
Lebih terperinciPENENTUAN EFISIENSI DAN KOEFISIEN PRESTASI MESIN PENDINGIN MERK PANASONIC CU-PC05NKJ ½ PK
PROS ID I NG 2 0 1 3 HASIL PENELITIAN FAKULTAS TEKNIK PENENTUAN EFISIENSI DAN KOEFISIEN PRESTASI MESIN PENDINGIN MERK PANASONIC CU-PC05NKJ ½ PK Jurusan Teknik Mesin Fakultas Teknik Universitas Hasanuddin
Lebih terperinciMUSICOOL HYDROCARBON REFRIGERANT OVERVIEW
{sidebar id=3} MUSICOOL HYDROCARBON REFRIGERANT OVERVIEW MUSICOOL adalah refrigerant dengan bahan dasar hydrocarbon alam dan termasuk dalam kelompok refrigerant ramah lingkungan, dirancang sebagai alternatif
Lebih terperinciLAPORAN AKHIR FISIKA ENERGI II PEMANFAATAN ENERGI PANAS TERBUANG PADA MESIN AC NPM : NPM :
LAPORAN AKHIR FISIKA ENERGI II PEMANFAATAN ENERGI PANAS TERBUANG PADA MESIN AC Nama Praktikan : Utari Handayani NPM : 140310110032 Nama Partner : Gita Maya Luciana NPM : 140310110045 Hari/Tgl Percobaan
Lebih terperinciPENGUJIAN PERBANDINGAN UNJUK KERJA ANTARA SISTEM AIR-COOLED CHILLER
TUGAS SARJANA PENGUJIAN PERBANDINGAN UNJUK KERJA ANTARA SISTEM AIR-COOLED CHILLER MENGGUNAKAN REFRIGERAN R-22 DENGAN REFRIGERAN HCR-22, PADA TEMPERATUR KELUAR KONDENSOR 28 S.D 29 C, DAN ANALISA PRESSURE
Lebih terperinciAhmad Farid* dan Moh. Edi.S. Iman Program Studi Teknik Mesin, Universitas Pancasakti Tegal Jl. Halmahera km 1, Tegal *
ANALISA EFEKTIFITAS PENAMBAHAN MEDIA AIR KONDENSAT PADA AC SPLIT 1,5 PK TERHADAP RASIO EFISIENSI ENERGI (EER) Ahmad Farid* dan Moh. Edi.S. Iman Program Studi Teknik Mesin, Universitas Pancasakti Tegal
Lebih terperinciPENGUJIAN PERFORMANCE DAN ANALISA PRESSURE DROP SISTEM WATER-COOLED CHILLER MENGGUNAKAN REFRIGERAN R-22 DAN HCR-22
PENGUJIAN PERFORMANCE DAN ANALISA PRESSURE DROP SISTEM WATER-COOLED CHILLER MENGGUNAKAN REFRIGERAN DAN Muchammad 1) Abstrak Efek pemanasan Global (GWP) merupakan salah satu permasalahan yang disebabkan
Lebih terperinciBAB II LANDASAN TEORI
BAB II LANDASAN TEORI 2.1 Sistem Refrigerasi Refrigerasi merupakan suatu kebutuhan dalam kehidupan saat ini terutama bagi masyarakat perkotaan. Refrigerasi dapat berupa lemari es pada rumah tangga, mesin
Lebih terperinciAnalisa Performansi Pengkondisian Udara Tipe Window dengan Penambahan Alat Penukar Kalor
Jurnal Ilmiah Teknik Mesin CakraM Vol. 3 No.2, Oktober 2009 ( 157-163 ) Analisa Performansi Pengkondisian Udara Tipe Window dengan Penambahan Alat Penukar Kalor I Ketut Gede Wirawan Jurusan Teknik Mesin,
Lebih terperinciROTASI Volume 7 Nomor 3 Juli
ROTASI Volume 7 Nomor 3 Juli 2005 25 PENGARUH PERUBAHAN TEMPERATUR EVAPORATOR TERHADAP PRESTASI AIR COOLED CHILLER DENGAN REFREGERAN R-134a, PADA TEMPERATUR KODENSOR TETAP Bambang Yunianto 1) Abstrak Pengujian
Lebih terperinciUJI EKSPERIMENTAL MESIN PENDINGIN BERPENDINGIN UDARA, DENGAN MENGGUNAKAN REFRIGERAN R22 DAN REFRIGERAN R407C.
UJI EKSPERIMENTAL MESIN PENDINGIN BERPENDINGIN UDARA, DENGAN MENGGUNAKAN REFRIGERAN R22 DAN REFRIGERAN Kevin Sanjaya 1), I Made Kartika Dhiputra 2) dan Harto Tanujaya 1) 1) Program Studi Teknik Mesin,
Lebih terperinciStudi Eksperimen Variasi Beban Pendinginan pada Evaporator Mesin Pendingin Difusi Absorpsi R22-DMF
JURNAL TEKNIK ITS Vol. 4, No. 1, (2015) ISSN: 2337-3539 (2301-9271 Print) F-18 Studi Eksperimen Variasi Beban Pendinginan pada Evaporator Mesin Pendingin Difusi Absorpsi R22-DMF Akhmad Syukri Maulana dan
Lebih terperinciBAB II TINJAUAN PUSTAKA
BAB II TINJAUAN PUSTAKA 2.1 Pengeringan Pengeringan adalah proses mengurangi kadar air dari suatu bahan [1]. Dasar dari proses pengeringan adalah terjadinya penguapan air ke udara karena perbedaan kandungan
Lebih terperinciBAB II DASAR TEORI Prinsip Kerja Mesin Refrigerasi Kompresi Uap
4 BAB II DASAR TEORI 2.1 Sistem Pengkondisian Udara Pengkondisian udara adalah proses untuk mengkondisikan temperature dan kelembapan udara agar memenuhi persyaratan tertentu. Selain itu kebersihan udara,
Lebih terperinciBAB II DASAR TEORI. 2.1 Pengertian Sistem Heat pump
BAB II DASAR TEORI 2.1 Pengertian Sistem Heat pump Heat pump adalah pengkondisi udara paket atau unit paket dengan katup pengubah arah (reversing valve) atau pengatur ubahan lainnya. Heat pump memiliki
Lebih terperinciSKRIPSI ANALISA KOMPARASI EKSPERIMENTAL KINERJA POMPA KALOR DENGAN MENGGUNAKAN REFRIGERAN R 134A DAN MC 134 UNTUK PRODUKSI AIR PANAS
SKRIPSI ANALISA KOMPARASI EKSPERIMENTAL KINERJA POMPA KALOR DENGAN MENGGUNAKAN REFRIGERAN R 134A DAN MC 134 UNTUK PRODUKSI AIR PANAS Oleh: I Gede Putu Adi Pratama 1219351005 JURUSAN TEKNIK MESIN FAKULTAS
Lebih terperinciBAB I PENDAHULUAN 1.1 Definisi Pengkondisian Udara
BAB I PENDAHULUAN 1.1 Definisi Pengkondisian Udara Sistem pengkondisian udara adalah suatu proses mendinginkan atau memanaskan udara sehingga dapat mencapai temperatur dan kelembaban yang sesuai dengan
Lebih terperinciAnalisis Beban Thermal Rancangan Mesin Es Puter Dengan Kompresor ½ PK Untuk Skala Industri Rumah Tangga
Analisis Beban Thermal Rancangan Mesin Es Puter Dengan Kompresor ½ PK Untuk Skala Industri Rumah Tangga IDG Agus Tri Putra (1) dan Sudirman (2) (2) Program Studi Teknik Pendingin dan Tata Udara, Jurusan
Lebih terperinciPengaruh Penggunaan Suction Liquid Heat Exchanger dan Tube in Tube Heat Exchanger Pada Refrigerator Terhadap Daya Kompresor dan Waktu Pendinginan
Pengaruh Penggunaan Suction Liquid Heat Exchanger dan Tube in Tube Heat Exchanger Pada Refrigerator Terhadap Daya Kompresor dan Waktu Pendinginan Ega Taqwali Berman * Jurusan Pendidikan Teknik Mesin, FPTK
Lebih terperinciSTUDI EKSPERIMENTAL PENGARUHPENGGUNAAN EJEKTOR SEBAGAI PENGGANTI KATUP EKSPANSI UNTUK MENINGKATKAN KINERJA SIKLUS REFRIGERASI PADA MESIN AC
STUDI EKSPERIMENTAL PENGARUHPENGGUNAAN EJEKTOR SEBAGAI PENGGANTI KATUP EKSPANSI UNTUK MENINGKATKAN KINERJA SIKLUS REFRIGERASI PADA MESIN A Sunanto Jurusan Teknik Pendingin dan Tata Udara, Politeknik Negeri
Lebih terperinciEFEK PERUBAHAN LAJU ALIRAN MASSA AIR PENDINGIN PADA KONDENSOR TERHADAP KINERJA MESIN REFRIGERASI FOCUS 808
ek SIPIL MESIN ARSITEKTUR ELEKTRO EFEK PERUBAHAN LAJU ALIRAN MASSA AIR PENDINGIN PADA KONDENSOR TERHADAP KINERJA MESIN REFRIGERASI FOCUS 808 Muhammad Hasan Basri * Abstract The objectives of study to describe
Lebih terperinciSeminar Nasional Mesin dan Industri (SNMI4) 2008 ANALISIS PERBANDINGAN UNJUK KERJA REFRIGERATOR KAPASITAS 2 PK DENGAN REFRIGERAN R-12 DAN MC 12
ANALISIS PERBANDINGAN UNJUK KERJA REFRIGERATOR KAPASITAS 2 PK DENGAN REFRIGERAN R-12 DAN MC 12 Suroso, I Wayan Sukania, dan Ian Mariano Jl. Let. Jend. S. Parman No. 1 Jakarta 11440 Telp. (021) 5672548
Lebih terperinciANALISA PERFORMANSI MESIN PENDINGIN 1-PK DENGAN PENAMBAHAN SUBCOOL MENGGUNAKAN REFRIGERANT R-22
ANALISA PERFORMANSI MESIN PENDINGIN 1-PK DENGAN PENAMBAHAN SUBCOOL MENGGUNAKAN REFRIGERANT R-22 SKRIPSI Skripsi Yang Diajukan Untuk Melengkapi Syarat Memperoleh Gelar Sarjana Teknik RIKARDO GOODLAS MANURUNG
Lebih terperinciBAB II DASAR TEORI. 2.1 Cooling Tunnel
BAB II DASAR TEORI 2.1 Cooling Tunnel Cooling Tunnel atau terowongan pendingin merupakan sistem refrigerasi yang banyak digunakan di industri, baik industri pengolahan makanan, minuman dan farmasi. Cooling
Lebih terperinciBAB II TINJAUAN PUSTAKA
BAB II TINJAUAN PUSTAKA 2.1 Tinjauan Pustaka Refrigeran merupakan media pendingin yang bersirkulasi di dalam sistem refrigerasi kompresi uap. ASHRAE 2005 mendefinisikan refrigeran sebagai fluida kerja
Lebih terperinciPERFORMANSI MESIN REFRIGERASI KOMPRESI UAP TERHADAP MASSA REFRIGERAN OPTIMUM MENGGUNAKAN REFRIGERAN HIDROKARBON
PERFORMANSI MESIN REFRIGERASI KOMPRESI UAP TERHADAP MASSA REFRIGERAN OPTIMUM MENGGUNAKAN REFRIGERAN HIDROKARBON Azridjal Aziz (1) (1) Staf Pengajar Jurusan Teknik Mesin Universitas Riau ABSTRAK Julah assa
Lebih terperinciOPTIMASI PENGGUNAAN AC SEBAGAI ALAT PENDINGIN RUANGAN
OPTIMASI PENGGUNAAN AC SEBAGAI ALAT PENDINGIN RUANGAN Irnanda Priyadi Jurusan Teknik Elektro, Fakultas Teknik, Universitas Bengkulu, Staf Pengajar Program Studi Teknik Elektro Universitas Bengkulu Jl.
Lebih terperinciKaji Eksperimental Pemanfaatan Panas Kondenser pada Sistem Vacuum Drying untuk Produk Kentang
Kaji Eksperimental Pemanfaatan Panas Kondenser pada Sistem Vacuum Drying untuk Produk Kentang Ade Suryatman Margana, Doni Oktaviana Refrigeration And Air Conditioning Department Politeknik Negeri Bandung
Lebih terperinciPENGARUH VARIASI DIAMETER PIPA KAPILER PADA SIKLUS TEMPERATUR RENDAH TERHADAP PERFORMANSI TRAINER UNIT SISTEM REFRIGERASI CASCADE
JURNAL LOGIC. VOL. 16. NO. 3. NOPEMBER 2016 161 PENGARUH VARIASI DIAMETER PIPA KAPILER PADA SIKLUS TEMPERATUR RENDAH TERHADAP PERFORMANSI TRAINER UNIT SISTEM REFRIGERASI CASCADE I Wayan Adi Subagia dan
Lebih terperinciPENGARUH MEDIA PENDINGIN AIR PADA KONDENSOR TERHADAP KEMAMPUAN KERJA MESIN PENDINGIN
PENGARUH MEDIA PENDINGIN AIR PADA KONDENSOR TERHADAP KEMAMPUAN KERJA MESIN PENDINGIN Kemas. Ridhuan 1), I Gede Angga J. 2) Jurusan Teknik Mesin Fakultas Teknik Universitas Muhammadiyah Metro Jl. Ki Hjar
Lebih terperinciKajian Eksperimen Heat Exchahger Pada Heat Pump Menggunakan Refrijeran Hidrokarbon
Kajian Eksperimen Heat Exchahger Pada Heat Pump Menggunakan Refrijeran Hidrokarbon Kusnandar, Gusniawan, Fajar Sentosa Program Studi Teknik Pendingin dan Tata Udara, Politeknik Negeri Indramayu. Alamat:
Lebih terperinciANALISIS PERFORMANSI MODEL PENGERING GABAH POMPA KALOR
ANALISIS PERFORMANSI MODEL PENGERING GABAH POMPA KALOR Budi Kristiawan 1, Wibowo 1, Rendy AR 1 Abstract : The aim of this research is to analyze of rice heat pump dryer model performance by determining
Lebih terperinciSimposium Nasional Teknologi Terapan (SNTT) 2013 ISSN X
ANALISIS KARAKTERISTIK MESIN REFRIGERASI MOBIL MENGGUNAKAN MOTOR LISTRIK SEBAGAI ALAT UJI Annisa Wulan Sari 1* Sunaryo 1** 1 Jurusan Teknik Mesin Fakultas Teknik Universitas Muhammadiyah Riau Jl. K.H.
Lebih terperinciSTUDI EKSPERIMENTAL PERBANDINGAN REFRIJERAN R-12 DENGAN HYDROCARBON MC-12 PADA SISTEM PENDINGIN DENGAN VARIASI PUTARAN KOMPRESOR. Ir.
STUDI EKSPERIMENTAL PERBANDINGAN REFRIJERAN R-12 DENGAN HYDROCARBON MC-12 PADA SISTEM PENDINGIN DENGAN VARIASI PUTARAN KOMPRESOR OLEH : RAGIL HERI NURAMBYAH 2108 100 523 DOSEN PEMBIMBING : Ir. KADARISMAN
Lebih terperinciBAB I PENDAHULUAN 1.1. LATAR BELAKANG
BAB I PENDAHULUAN 1.1. LATAR BELAKANG Teknologi ejector refrigeration telah lama diketahui dan dikembangkan, pertama kali ditemukan oleh Charles Parsons awal tahun 1900. Ejector pertama kali digunakan
Lebih terperinciEFEK UDARA DI DALAM SISTEM REFRIGERASI
EFEK UDARA DI DALAM SISTEM REFRIGERASI Daud Patabang* * Abstract The performance of refrigeration system are affected by condenser, evaporator,compressor and regulating valve. Besides cooling system itself
Lebih terperinciPerformansi Mesin Pendingin Tipe Chiller untuk Cold Storage dan Indoor Menggunakan Ethylene Glycol Coolant
Performansi Mesin Pendingin Tipe Chiller untuk Cold Storage dan Indoor Menggunakan Ethylene Glycol Coolant Azridjal Aziz 1, Hendrik Syahputra 1,Rahmat Iman Mainil 1, Afdhal Kurniawan M 2 1 Laboratorium
Lebih terperinciBAB II DASAR TEORI BAB II DASAR TEORI
BAB II DASAR TEORI 2.1 Sistem refrigerasi kompresi uap Sistem refrigerasi yang umum dan mudah dijumpai pada aplikasi sehari-hari, baik untuk keperluan rumah tangga, komersial dan industri adalah sistem
Lebih terperinciKAJI EKSPERIMENTAL KARAKTERISTIK TERMODINAMIKA DARI PEMANASAN REFRIGERANT 12 TERHADAP PENGARUH PENDINGINAN
KAJI EKSPERIMENTAL KARAKTERISTIK TERMODINAMIKA DARI PEMANASAN REFRIGERANT 12 TERHADAP PENGARUH PENDINGINAN Mochtar Asroni, Basuki Widodo, Dwi Bakti S Program Studi Teknik Mesin, Institut Teknologi Nasional
Lebih terperinciAnalisa Performansi Sistem Pendingin Ruangan dan Efisiensi Energi Listrik padasistem Water Chiller dengan Penerapan Metode Cooled Energy Storage
Analisa Performansi Sistem Pendingin Ruangan dan Efisiensi Energi Listrik padasistem Water Chiller dengan Penerapan Metode Cooled Energy Storage Sugiyono 1, Ir Sumpena, MM 2 1. Mahasiswa Elektro, 2. Dosen
Lebih terperinciPengujian Model Water Chiller System dengan Hidrokarbon sebagai Refrigeran Primer
Jurnal Ilmiah Teknik Mesin CakraM Vol. 3 No. 1, April 29 (62 66) Pengujian Model Water System dengan Hidrokarbon sebagai Refrigeran Primer Nengah Suarnadwipa & Ketut Astawa Jurusan Teknik Mesin, Universitas
Lebih terperinciCOEFFICIENT OF PERFORMANCE (COP) MINI FREEZER DAGING AYAM KAPASITAS 4 KG
ISSN-P 2460-8408 Jurnal Teknologi Pendingin dan Tata Udara Politeknik Sekayu (PETRA) Volume 1, No. 1, November 2015, h. 44-54 COEFFICIENT OF PERFORMANCE (COP) MINI FREEZER DAGING AYAM KAPASITAS 4 KG Arief
Lebih terperinciBAB III TINJAUAN PUSTAKA
11 BAB III TINJAUAN PUSTAKA 3.1 PENDAHULUAN Air conditioner atau yang biasa di sebut AC merupakan sebuah alat yang mampu mengondisikan udara. Dengan kata lain, AC berfungsi sebagai penyejuk udara. Penggunaan
Lebih terperinciLAPORAN TAHUNAN. Penelitian Unggulan Perguruan Tinggi. Tahun ke 1 dari rencana 2 tahun. Oleh :
LAPORAN TAHUNAN Penelitian Unggulan Perguruan Tinggi PENGEMBANGAN RESIDENTIAL AIR CONDITIONING HIBRIDA HEMAT ENERGI DENGAN KONDENSOR DUMMY SEBAGAI WATER HEATER MENGGUNAKAN REFRIGERAN HIDROKARBON SUBSITUSI
Lebih terperinciSILABUS MATA KULIAH D4 REFRIGERASI DASAR KURIKULUM 2011 tahun ajaran 2010/2011. Materi Tujuan Ket.
SILABUS MATA KULIAH D4 REFRIGERASI DASAR KURIKULUM 2011 tahun ajaran 2010/2011 No Minggu ke 1 1-2 20 Feb 27 Feb Materi Tujuan Ket. Pendahuluan, Jenis dan Contoh Aplikasi system Refrigerasi Siswa mengetahui
Lebih terperinciJurnal Teknik Mesin (JTM): Vol. 05, No. 3, Oktober
Jurnal Teknik Mesin (JTM): Vol. 05, No. 3, Oktober 2016 114 PENGUJIAN PENGARUH VARIASI PUTARAN MESIN TERHADAP PERFORMANSI SISTEM PENGKONDISIAN UDARA PADA KENDARAAN PENUMPANG 1.500 cc Suadi Program Studi
Lebih terperinciPENGARUH VARIASI BEBAN PENDINGIN TERHADAP PRESTASI KERJA MESIN PENDINGIN DENGAN REFRIGERAN R12 DAN LPG
PENGARUH VARIASI BEBAN PENDINGIN TERHADAP PRESTASI KERJA MESIN PENDINGIN DENGAN REFRIGERAN R12 DAN LPG Moch. Rizal A.Y, Nasrul Ilminnafik, Digdo Listyadi Jurusan Teknik Mesin, Fakultas Teknik, Universitas
Lebih terperinciPenggunaan Refrigeran R22 dan R134a pada Mesin Pendingin. Galuh Renggani Wilis, ST.,MT
Penggunaan Refrigeran R22 dan R134a pada Mesin Pendingin Galuh Renggani Wilis, ST.,MT ABSTRAKSI Pengkondisian udara disebut juga system refrigerasi yang mengatur temperature & kelembaban udara. Dalam beroperasi
Lebih terperinciPengaruh Laju Aliran Air terhadap Performansi Mesin Pengkondisian Udara Hibrida dengan Kondensor Dummy Tipe Multi Helical Coil sebagai Water Heater
Pengaruh Laju Aliran Air terhadap Performansi Mesin Pengkondisian Udara Hibrida dengan Kondensor Dummy Tipe Multi Helical Coil sebagai Water Heater Azridjal Aziz 1, Sarwo Fikri 1, Afdhal Kurniawan M 2,
Lebih terperinciBAB II DASAR TEORI BAB II DASAR TEORI
BAB II DASAR TEORI 2.1 Penyimpanan Energi Termal Es merupakan dasar dari sistem penyimpanan energi termal di mana telah menarik banyak perhatian selama beberapa dekade terakhir. Alasan terutama dari penggunaan
Lebih terperinciANALISIS KINERJA INSTALASI SISTEM PENGKONDISIAN UDARA BANGUNAN KOMERSIAL ABSTRACT
ANALISIS KINERJA INSTALASI SISTEM PENGKONDISIAN UDARA BANGUNAN KOMERSIAL Drajat Samyono ABSTRACT Instalasi system pengkondisian udara merupakan suatu proses penanganan udara. Mesin pendingin (water chiller)
Lebih terperinciPERFORMANSI MODULAR CHILLER KAPASITAS 120 TR
Jurnal Mekanikal, Vol. 6 No. 1: Januari 2015: 532-539 ISSN 2086-3403 PERFORMANSI MODULAR CHILLER KAPASITAS 120 TR Azridjal Aziz 1, Joko Harianto 1, Afdhal Kurniawan Mainil 2 1 Jurusan Teknik Mesin, Universitas
Lebih terperinciUNJUK KERJA MESIN PENDINGIN KOMPRESI UAP PADA BEBERAPA VARIASI SUPERHEATING DAN SUBCOOLING
UNJUK KERJA MESIN PENDINGIN KOMPRESI UAP PADA BEBERAPA VARIASI SUPERHEATING DAN SUBCOOLING Mega Nur Sasongko 1 Teknik Mesin Universitas Brawijaya Jalan M.T Haryono 167 Malang Telp. 0341-587710 E-mail:
Lebih terperinci