STUDI PENYETELAN RELAI DIFERENSIAL PADA TRANSFORMATOR PT CHEVRON PACIFIC INDONESIA

Ukuran: px
Mulai penontonan dengan halaman:

Download "STUDI PENYETELAN RELAI DIFERENSIAL PADA TRANSFORMATOR PT CHEVRON PACIFIC INDONESIA"

Transkripsi

1 STUDI PENYETELAN RELAI DIFERENSIAL PADA TRANSFORMATOR PT CHEVRON PACIFIC INDONESIA Liem Ek Bien & Dita Helna* Dosen Jurusan Teknik Elektro-FTI, Universitas Trisakti Abstract The quality of an electric power system is measured by its continuity of service, good control and maintenance. The good continuity of service can be obtained if all the components of power systems can operate well in every situation and condition, either in normal or in abnormal condition. In abnormal condition, the protection system has an important role in detecting every disturbance and disconnecting the disturbed parts from the system. The power transformer is the main component in a substation. The disturbances in the transformer should be isolated so as not to disturb the system during distribution of the electric power to other load. The differential relay on the power transformer is a protection relay to detect internal disturbance. This paper discusses the setting and mismatch error of differential relay in substation of Central Duri at switchgear #3 at PT Chevron Pacific Indonesia (PT CPI). Keywords: short circuit, differential relay, power transformer 1. Pendahuluan Sistem kelistrikan merupakan elemen penting untuk menunjang proses produksi pada industri. PT Chevron Pacific Indonesia merupakan salah satu perusahaan eksplorasi minyak asing di Indonesia dengan wilayah kerja yang cukup luas. PT Chevron memiliki sistem kelistrikan sendiri untuk memenuhi kebutuhan listrik yang cukup besar. Sistem pembangkitan untuk penyediaan tenaga listrik yang terdiri atas fasilitas-fasilitas pembangkitan, transmisi, dan distribusi diatur agar sistem tidak hanya beroperasi dengan efisiensi yang setinggi mungkin, tetapi seluruh peralatannya juga diamankan dan dilindungi terhadap kerusakan. Manfaat sistem proteksi dan relai-relai pengaman adalah agar pemutus-pemutus daya yang tepat dioperasikan supaya hanya bagian yang terganggu saja yang dipisahkan secepatnya dari sistem, sehingga kerusakan peralatan listrik yang disebabkan oleh gangguan menjadi sekecil mungkin. * Alumni Jurusan Teknik Elektro FTI, Universitas Trisakti

2 Salah satu komponen yang sangat penting peranannya dalam sistem tenaga listrik adalah transformator tenaga. Transformator tenaga ini berfungsi untuk mengubah besaran tegangan. Dengan menggunakan transformator tenaga, penyaluran energi dapat luas jangkauannya sehingga penempatan pembangkitan tidak harus berdekatan dengan beban. Untuk menjaga transformator tenaga dari gangguan diperlukan pengaman. Salah satu pengaman transformator tenaga adalah relai diferensial. Gambar sederhana sebuah sistem tenaga listrik diperlihatkan pada Gambar 1. berikut: Gambar 1. Sistem Tenaga Listrik 2. Relai Diferensial Relai diferensial adalah salah satu relai pengaman utama sistem tenaga listrik yang bekerja seketika tanpa koordinasi relai disekitarnya sehingga waktu kerja dapat dibuat secepat mungkin. Daerah pengamanannya dibatasi oleh pasangan trafo arus dimana relai diferensial dipasang sehingga relai diferensial tidak dapat dijadikan sebagai pengaman cadangan untuk daerah berikutnya. Proteksi relai diferensial bekerja dengan prinsip keseimbangan arus (current balance). 42

3 Liem Ek Bien & Dita Helna. Studi Penyetelan Relai Diferensial Pada Transformator PT Chevron Prinsip ini berdasarkan hukum kirchhoff yaitu membandingkan jumlah arus masuk ke primer (I p ) sama dengan jumlah arus yang keluar dari sekunder (I S ). (Kadarisman,No Year: 8-20). I diferensial = I d = P I S I (1) Dimana: I d = Arus Diferensial (A) I p = Arus Sisi Masuk (A) I s = Arus Sisi Keluar (A) Gambar 2. menunjukkan relai diferensial dalam keadaan arus normal, dimana I p dan I s sama besar dan berlawanan arah. Gambar 2. Relai Diferensial Saat Arus Normal 43

4 I d = I p + I s = 0 Ampere I dif = I P + I S = 0 Ampere Maka tidak ada tegangan yang melintasi coil relay dan tidak ada arus yang mengalir pada relai tersebut, sehingga relai diferensial tidak bekerja. (J lewis, Blackburn, 2004: 10) Gangguan Diluar Daerah yang Dilindungi Pada gangguan diluar (eksternal) daerah proteksi relai diferensial (diluar kedua trafo arus), relai diferensial tidak akan bekerja, karena I p dan I s sama besar dan berlawanan arah (I d = I p + I s = 0 Ampere, I dif = I P + I S = 0 Ampere), seperti yang ditunjukkan oleh Gambar 3. berikut. (J lewis, 2003: 10). Gambar 3. Relai Diferensial Saat Gangguan Eksternal 44

5 Liem Ek Bien & Dita Helna. Studi Penyetelan Relai Diferensial Pada Transformator PT Chevron 2.2. Gangguan Didalam Daerah yang Dilindungi Untuk gangguan didalam (internal) daerah proteksi relai diferensial (diantara kedua trafo arus), I p dan I s searah. I d = I p + I s > 0 Ampere I dif = I P + I S > 0 Ampere Karena arus akan menuju titik gangguan, sehingga relai diferensial akan bekerja, seperti yang ditunjukkan pada Gambar 4. Gambar 4. Relai Diferensial Saat Gangguan Internal 45

6 Pada saat ada arus yang mengalir lewat relai, maka relai akan mengirim sinyal pada lock out relay. Sinyal ini akan di teruskan ke C/S dan memerintahkannya untuk lock out sehingga aliran energi listrik terputus, maka transformator tenaga yang diamankan bebas dari pengaruh gangguan yang ada. 3. Karakteristik Relai Diferensial Karakteristik diferensial dibuat sejalan dengan Unbalances current (I μ ), untuk menghindari terjadinya kesalahan kerja. Kesalahan kerja disebabkan karena CT ratio mismatch, adanya pergeseran fasa akibat belitan transformator tenaga terhubung (Y) (Δ). I 1 I CT CT 2 i 1 i 1 i 2 Restraiting Coil Restraining Coil Operating Operating Coil Coil Gambar 5. Prinsip Pengoperasian Relai Diferensial Perubahan tap tegangan (perubahan posisi tap changer) pada transformator tenaga oleh On Load Tap Changer (OLTC) yang menyebabkan CT mismatch juga ikut berubah. Kesalahan akurasi CT, Perbedaan kesalahan CT di daerah jenuh (Saturasi CT), dan Inrush current pada saat transformator energize menimbulkan unbalances current (I μ ) yang bersifat transient. 46

7 Liem Ek Bien & Dita Helna. Studi Penyetelan Relai Diferensial Pada Transformator PT Chevron Untuk mengatasi masalah unbalance current (I μ ) pada relai diferensial caranya dengan menambahkan kumparan yang menahan bekerjanya relai di daerah I μ. Kumparan ini di sebut Restraining Coil, sedangkan kumparan yang mengerjakan relai tersebut di sebut Operating Coil. Arus diferensial didapat dari menjumlahkan komponen arus sekunder perfasa di belitan 1 ( I 1 ) dan belitan 2 ( I 2 ) secara vektor perfasa. Jika arus berlawanan dalam arti yang satu menuju relai dan yang yang lainnya meninggalkan relai, maka akan saling mengurangi dan sebaliknya jika arus searah berarti yang kedua-duanya menuju atau meninggalkan relai, maka akan saling menjumlahkan. Arus penahan (restrain) didapat dari arus maksimal komponen arus sekunder perfasa di belitan 1 ( I 1 )dan belitan 2 ( I 2 ) I restrain = I r = max I 1, I 2 ) (2) Slope didapat dengan membagi antara komponen arus diferensial dengan arus penahan. Slope 1 akan menentukan arus diferensial dan arus penahan pada saat kondisi normal dan memastikan sensitifitas relai pada saat gangguan internal dengan arus gangguan yang kecil. Sedangkan Slope 2 berguna supaya relai tidak kerja oleh gangguan eksternal yang berarus sangat besar sehingga salah satu CT mengalami saturasi (diset dengan slope lebih dari 50%). % Slope = I I d r x 100% (3) Pada Gambar 6. halaman berikut merupakan karakteristik relai diferensial. Daerah di atas kurva adalah daerah kerja relai diferensial, sedangkan pada daerah di bawah kurva, relai tidak akan bekerja. (Anderson Anvenue, 2001: ) 47

8 I differential (xct) 200% OPERATE REGION SLOPE 2 100% 100% 1.00 PICKUP SLOPE 1 25% 15% 2.0 KNEEPOINT Gambar 6. Karakteristik Relai Diferensial 50% RESTRAINT REGION I restraint (xct) 3.1. Syarat Pengaman Relai Diferensial a. Trafo arus yang digunakan oleh relai diferensial ini harus memiliki rasio perbandingan CT 1 dan CT 2 sama, contohnya 200:5 dan 1500:5, sehinggga I p = Is, serta sambungan dan polaritas CT 1 dan CT 2 sama. Polaritas trafo arus memperlihatkan arah arus yang masuk dan keluar dari trafo arus Jika tidak, akan terjadi kesalahan dalam melihat arus yang masuk dan keluar melalui transformator tenaga. Hal ini, menyebabkan kesalahan dalam menentukan adanya gangguan di transformator tenaga. b. Adanya pergeseran fasa akibat hubungan trafo tenaga yang terhubung delta (Δ) - (Y) maka untuk mengembalikan sudut phasa arus yang tergeser tersebut, hubungan trafo arus di buat berbeda dan sudut pada CT di sisi primer dan CT di sisi sekunder trafo berbeda Hubungan CT di primer berbeda dengan CT di sekunder yaitu satu sisi terhubung Y, lainnya Δ. Yang terhubung Δ menghasilkan 48

9 Liem Ek Bien & Dita Helna. Studi Penyetelan Relai Diferensial Pada Transformator PT Chevron dan adanya arus magnetisasi dari trafo tenaga di sisi primer menyebabkan pergeseran fasa, Oleh karena itu diperlukan suatu CT tambahan (auxiliary CT ACT) yang terhubung Y, karena proteksi diferensial harus membandingkan arus pada dua sisi tanpa perbedaan fasa. c. Karakteristik kejenuhan CT 1 dan CT 2 harus sama 200:5 CT1 T 1500:5 CT2 200:5 CT1 1500:5 CT2 Ip Is RELE Relay DIFEREN Diferen SIAL sial Gambar 7. Polaritas Trafo Arus 3.2. Skema Rele Diferensial (87t) Gambar 8. mengilustrasikan skema pengaman diferensial trafo tiga fasa yang disederhanakan. Sisi tegangan tinggi 115 kv hubung RST yang mendahului sisi tegangan rendah 13.8 kv hubung (Y) XYZ dengan sudut 30. Untuk pemasangan relai diferensial perlu diperhatikan arus urutan nol, agar relai diferensial tidak salah kerja atau beroperasi pada saat gangguan luar. Selain itu, Trafo arus pada sisi primer trafo tenaga yang terhubung dengan belitan Delta dihubungkan Y dan trafo arus pada sisi sekunder trafo tenaga yang belitannya terhubung Y dihubungkan Δ sehingga 49

10 menghilangkan komponen urutan nol yang ada di sisi sekunder tranformer dan menyamakan arus yang keluar dari CT sehingga arus yang luar dari CT tetap sama fasa yakni ir-it, is-ir dan it-is. Dy 1 115/13,6 KV 28MVA R CT1 Primer / 115KV Sekunder /13,8KV CT4 X S CT2 CT5 Y T CT3 CT6 Z ir-it R R ix-iz O is-ir R R iy-ix it-is O iz-iy R R O AUX CT Relai diferensial (87T) Gambar 8. Skema Diferensial Trafo tenaga Pada Operasi Normal 50

11 Liem Ek Bien & Dita Helna. Studi Penyetelan Relai Diferensial Pada Transformator PT Chevron Keterangan: R : Restraint coil O : Operation coil ir,is,it : arus yang mengalir di sisi primer ix,iy,iz : arus yang mengalir di sisi sekunder R, S, T : line di sisi primer X, Y, Z : line di sisi sekunder CT1 = CT2 = CT3 = CT4 = CT5 = CT6 = Current Transformer 4. Data Perhitungan Setelan Relai Differensial Sistem transmisi yang akan dianalisa gangguan hubung singkatnya adalah saluran transmisi pada Gardu Induk Central Duri di switchgear #3 Pada gardu ini aliran dayanya berasal dari sumber Generator 29,6 MVA, 13,8 kv dan dihubung ke transformator tenaga berkapasitas 28 MVA untuk disalurkan ke sistem transmisi 115 kv. Analisa gangguan hubung singkat pada saluran ini adalah untuk menghitung setelan relai diferensial dan mengetahui seberapa besar perkiraan error relai diferensial yang mungkin dapat terjadi. Bagan gambar jaringan sistem tenaga listrik Gardu Induk central duri#3, terdapat pada Gambar Data Jaringan PT Chevron Pacific Indonesia Sebelum memulai perhitungan, perlu diketahui terlebih dahulu data yang diperlukan untuk menghitung penyetelan relai diferensial transformator, sebagai berikut: 1. Daerah yang akan dianalisa 2. Data impedansi 3. Data / name plate transformator Gardu Induk Central Duri di switchgear #3 4. Data sumber (GI) 5. Data 51

12 C Line kv GARDU INDUK CENTRAL DURI #3 B TX 15/28 MVA 115/13,8 kv A Line 1 13,8 kv G 29,6 MVA Gambar 9. Skema Gardu Induk Central Duri #3 Keterangan: A : Gardu Induk Central Duri di switchgear #3 B : Transformator Tenaga C : Sistem 115 kv Berikut data lengkap yang diberikan: 52

13 Liem Ek Bien & Dita Helna. Studi Penyetelan Relai Diferensial Pada Transformator PT Chevron Tabel 1. Data Transformator Gardu Induk Central Duri #3 Data Belitan 1 hubungan Δ Belitan 2 hubungan Y Diagram phasor daya Pergeseran fasa lag Rated MVA 28 MVA 28 MVA Tegangan Nominal fasa-fasa 115 KV 13,8KV Hubungan CT WYE DELTA CT ratio 200:5 1500:5 Tegangan fasa-netral 66,40 KV 7,97 KV Reaktansi trafo 8,07% 8,07% Pentanahan netral trafo 20Ω Tabel 2. Data impedansi Transformator Gardu Induk Central Duri #3 Kapasitas MVA Impedansi (%) pada MVA rating Rt Xt1 Rto Xto 28 0, ,0807 0,0044 0,102 Keterangan: Rt = resistansi urutan positif dan negatif 53

14 Xt 1 = reaktansi urutan positif dan negatif Rt o = resistansi urutan nol Xt o = reaktansi urutan nol Tabel 3. Data Daya Hubung Singkat Pada Sumber Sumber Daya hubung singkat (MVA) R sumber (Ω) X sumber (Ω) Generator 13,8 kv 87, ,57004 Sistem 115 kv 506, ,25789 Tabel 4. Data Generator Kapasitas (MVA) Impedansi (%) pada MVA rating Rd Xd Rd Xd Ro Xo 29,741 0, , ,01 0,12 0,0025 0,12 Keterangan: d : resistansi transien synchronous Xd : reaktansi transien synchronous Rd : resistansi subtransien synchronous Xd : reaktansi subtransien synchronous Ro : resistansi urutan nol Xo : reaktansi urutan nol Tabel 5. di bawah ini adalah hasil perhitungan admitansi jaringan urutan positif, urutan negatif dan urutan nol menggunakan program Microsoft Excel. 54

15 Dari bus Generator 13,8 kv Sistem 115 kv B B GENO GENO Tabel 5. Penyusunan Admitansi Jaringan Urutan Positif dan Negatif Untuk Gangguan pada Gardu Induk Central Duri #3 Ke bus A C C A A C R (pu) 0,064 0,006 0, jx (pu) 0,773 0,197 0,144 0, Z (pu) 0,776 0,197 0,144 0,144 10,05 10,05 Sudut Z (rad) 1,488 1,571 1,527 1,527 1,471 1,471 Y (pu) 1,289 5,065 6,933 6,933 Sudut Y (rad) -0,488-0,571-1,527-1,527-1,471-1,471 G (pu) 1,138 4,262 0,301 0,301 jb (pu) -0,604-2,737-6,926-6,926 Liem Ek Bien & Dita Helna. Studi Penyetelan Relai Diferensial Pada Transformator PT Chevron 55

16 3x10 15 Tabel 6. Penyusunan Admitansi Jaringan Urutan Nol Untuk Gangguan Pada Gardu Induk Central Duri #3 Dari bus Generator 13,8 kv Sistem 115 kv B B GENO GENO Ke bus A C C A A C R (pu) 1255,134 0,045 3x ,024 31,506 jx (pu) 0,403 0,197 10x ,182 0, Z (pu) 1255,135 0,203 10,4x ,184 31,508 10,4x10 15 Sudut Z (rad) 1,345 1,279 1,441 0,012 1,279 Y (pu) 0,001 4,936 5,444 0,032 Sudut Y (rad) -1,345-1,279-1,441-0,012-1,279 G (pu) 0,001 1,105 0,704 0,032 jb (pu) -4,811-5,

17 Liem Ek Bien & Dita Helna. Studi Penyetelan Relai Diferensial Pada Transformator PT Chevron 4.2. Pemilihan CT Ratio Pemilihan CT disesuaikan dengan alat ukur dan proteksi. Pemilihan CT dengan kualitas baik akan memberikan perlindungan sistem yang baik pula. Relai diferensial sangat tergantung terhadap karakteristik CT. Jika karakteristik CT bekerja dengan baik, maka sistem akan terlindungi oleh relai diferensial ini secara optimal. CT ditempatkan dikedua sisi peralatan yang akan diamankan (transformator tenaga), seperti yang terlihat pada Gambar 8. CT ratio untuk relai diferensial yang dipilih sebaiknya memiliki nilai yang mendekati nilai I rating. (Sukmawidjaja, 1995: 3-115) I n = kv S x 3 (4) Dimana: I S n : arus nominal (A) : Daya yang tersalur (MVA) Dari persamaan 4, arus nominal dikedua sisi transformator adalah sebagai berikut ; I n sisi 115 kv = 28 MVA =140,572 A 115 kv x 3 I n sisi 13,8 kv = 28 MVA 13,8kV x =1171,435 A 3 Transformator dapat menarik beban lebih hingga 110% dari kapasitasnya, selama temperatur belitan dibawah temperatur maksimumnya. I rating = 110% x I n (5) I rating primer CT sisi 115 kv = 1,10 x 140,572 = 154,629 A 57

18 I rating primer CT sisi 13,8 kv = 1,10 x 1171,432 = 1288,579 A Maka perbandingan ratio trafo arus (CT ratio) dapat dihitung dari nilai arus rating dikedua sisi tegangan transformator tenaga tersebut dan disesuaikan dengan spesifikasi CT ratio yang ada dipasaran sedangkan nilai sekunder CT (5A atau 1A) disesuikan dengan peralatan proteksinya. Dan Untuk CT ratio sisi 115 kv (CT 1 ) = 200 : 5 = 40 Untuk CT ratio sisi 13,8 kv (CT 2 ) = 1500 : 5 = Tap Auxillary Auxillary CT adalah CT bantu yang berguna untuk menyesuaikan besar arus yang masuk ke relai diferensial akibat proses pergeseran fasa oleh transformator tenaga dan beda tegangan primer dan sekunder transformator tenaga. Untuk pemilihan tap auxillary CT sama dengan CT dan penempatan CT auxillary diletakkan pada sisi 13,8 kv yang CT dihubung delta untuk menghilangkan arus urutan nol dan menyamakan fasa ( lihat pada Gambar 8 ). Untuk menghitung nilai tap ratio dari Auxillary CT di mulai dari arus nominal sekunder CT yang tidak dihubungkan Δ, yang untuk transformator ini ada di sisi 115 kv. Pada sisi tegangan 115 kv ini menggunakan ratio CT = 200:5 sehingga: I (13,8 kv) = 155 kv 13,8 kv 200 A = 1666,67 A 58

19 Liem Ek Bien & Dita Helna. Studi Penyetelan Relai Diferensial Pada Transformator PT Chevron Arus yang mengalir di sisi sekunder CT 2 adalah: I (CT2 ) = 5 A 1500 A x 1666,67 A = 5,56 A Karena Sekunder CT 2 di hubung Δ, maka arusnya menjadi: I = I x = 5,56 A x = 9,62 A Maka tap auxillary yang dipilih adalah 9,62 : Setelan Relai Diferensial Diatas telah dihitung nilai CT ratio pada kedua sisi transformator tenaga, maka sekarang dapat dihitung di hitung nilai arus diferensial (I d ) dan arus restraint (I r ) kemudian didapat nilai Setting Arus(I set ). Relai diferensial hanya akan beroperasi saat ada gangguan didalam transformator dan tidak beroperasi saat keadaan gangguan diluar dan keadaan normal Perhitungan setelan Relai Diferensial Pada Gangguan Dalam Untuk gangguan didalam transformator tenaga, relai diferensial beroperasi Jika: i set < i oper = relai diferensial beroperasi Arus diferensial (I d ) merupakan arus operasi (I oper ) pada relai diferensial. Dari hasil perhitungan arus gangguan fasa R, S dan T yang mengalir pada saat gangguan hubung singkat tiga fasa didalam transformator dengan menggunakan program Microsoft Excel didapat arus diferensial diperlihatkan pada tabel berikut. 59

20 Tabel. 7. Arus diferensial Untuk Gangguan Hubung Singkat Tiga Fasa (K-K-K) Pada gangguan di tranformator di saluran Gardu Induk Central Duri #3 fasa I riel I imaj I (A) sudut R -55,653-1,642 55, ,310 S 26,404 49,018 55,677 61,690 T 29,249-47,375 55,677-58,310 Arus penahan (restrain) didapat dari arus maksimal komponen arus sekunder perfasa di belitan 1 ( I 1 ) dan belitan 2 ( I 2 ) pada persamaan 2: I restrain = I r = max ( I 1, I 2 ) Dari hasil perhitungan dengan menggunakan program Microsoft Excel didapat: I 1 = 41,242 A I 2 = 14,626 A I r = max (41,242;14,626) = 41,242 A Tabel. 8. Arus Restrain Untuk Gangguan Hubung Singkat Tiga Fasa (K-K-K) Pada gangguan di tranformator di saluran Gardu Induk Central Duri #3 Fasa Ir (A) R 41,242 S 41,242 T 41,242 60

21 Liem Ek Bien & Dita Helna. Studi Penyetelan Relai Diferensial Pada Transformator PT Chevron Slope pada Karakteristik relai difererensial pada gambar ada dua, yaitu slope 1 untuk gangguan didalam transformator 25% dan slope 2 untuk gangguan diluar transformator 100%. Untuk gangguan didalam transformator tenaga, setelan relai diferensial sebesar 25% dan untuk gangguan diluar transformator tenaga setelan relai diferensial sebesar 100%. Setelan persenan ini telah ditentukan dari karakteristik kerja relai diferensial. Pada gangguan didalam transformator tenaga slope 1 di set 25%, dan relai diferensial bekerja jika i set < i oper maka I set untuk gangguan tiga fasa ini pada fasa R adalah: I set = slope 1 x I r (6) = 25% x 41,242 = 10,310 A Arus operasi sama dengan arus diferensial (I oper = I d ), pada Tabel 7. I d = 55,677 A I oper = 55,677 A I set = 10,310 trip Gambar 10. Perbandingan nilai I oper dan I set saat gangguan didalam transformator Karena i set < i oper maka relai diferensial trip. Untuk letak titik gangguan di gambar karakteristik relai diferensial arus diferensial dan arus restraint diubah dalam satuan pu. I d = 55,677 A I r = 41,242 A I dasar sec CT = 5 A 61

22 Untuk menghitung arus dalam pu: I pu = I I ada dasar I d = I r = 55, ,242 5 = 11,135 pu = 8,248 pu Dibawah ini adalah gambar karakteristik relai diferensial yang memperlihatkan letak titik nilai gangguan, untuk gangguan fasa R, S dan T yang mengalir pada saat gangguan hubung singkat tiga fasa didalam transformator tenaga. I d TRIP tidak TRIP Gambar 11. Karakteristrik Relai Diferensial T60 Dititik Gangguan Dalam Transformator Untuk gangguan Tiga Fasa Keterangan: a : Karakteristrik Relai Diferensial T60 Dititik Gangguan Dalam Transformator Untuk gangguan Tiga Fasa. b : gangguan didalam jangkauan relai diferensial b gangguan a DIF gangguan I r 62

23 Liem Ek Bien & Dita Helna. Studi Penyetelan Relai Diferensial Pada Transformator PT Chevron Perhitungan Setelan Relai Diferensial Pada Gangguan Luar Untuk kerja relai diferensial agar tidak salah kerja saat operasi normal dan gangguan luar maka setelan relai diferensial adalah: i set > i oper maka relai diferensial tidak beroperasi. Dari hasil perhitungan saat ada gangguan fasa R-S-T di bus A di saluran transmisi Gardu Induk Central Duri #3 dengan menggunakan program Microsoft Excel didapat arus diferensial diperlihatkan pada tabel berikut adalah sama perhitungannya dengan Tabel 9. Tabel. 9. Arus diferensial Untuk Gangguan Hubung Singkat Tiga Fasa (K- K-K) Di bus A di Saluran Gardu Induk Central Duri #3 fasa I riel I imaj I (A) sudut R -5,288-14,026 14, ,655 S -9,503 11,592 14, ,345 T 14,791 2,434 14,990 9,345 Hasil perhitungan Arus restraint saat ada gangguan tiga fasa R-S-T di bus A di saluran transmisi Gardu Induk Central Duri #3 dengan menggunakan program Microsoft Excel diperlihatkan pada tabel berikut adalah sama perhitungannya dengan Tabel 10. Tabel. 10. Arus Restrain Untuk Gangguan Hubung Singkat Tiga Fasa (K-K- K) Di bus A di Saluran Gardu Induk Central Duri #3 Fasa Ir (A) R 28,958 S 28,958 T 28,958 63

24 Setelah hasil perhitungan Arus restraint untuk gangguan tiga fasa R-S-T di bus A di saluran transmisi Gardu Induk Central Duri #3 kemudian dihitung setelan rele diferensial. Pada gangguan diluar transformator slope 2 di set 100%, dan relai diferensial tidak bekerja jika i set > i oper maka I set untuk gangguan ini pada fasa R adalah: I set = slope 2 x I r (7) = 100% x 28,958 A = 28,958 A Arus operasi sama dengan arus diferensial (I oper = I d ), pada Tabel 9. I d = 14,990 A I oper = 14,990 A I set = 28,958 A tidak trip Gambar 12. Perbandingan nilai I oper dan I set saat gangguan diluar transformator Karena i set > i oper maka relai diferensial tidak trip. Untuk melihat letak titik gangguan di gambar karakteristik relai diferensial arus diferensial dan arus restraint diubah dalam satuan pu. I d = 14,990 A I r = 28,958 A I dasar sec CT = 5 A Untuk menghitung arus dalam pu: I pu = I I ada dasar 64

25 Liem Ek Bien & Dita Helna. Studi Penyetelan Relai Diferensial Pada Transformator PT Chevron I d = I r = 14, ,958 5 = 2,998 pu = 5,792 pu Dibawah ini adalah gambar karakteristik relai diferensial yang memperlihatkan letak titik nilai gangguan, untuk gangguan fasa R, S dan T yang mengalir pada saat gangguan hubung singkat tiga fasa di bus A. I d a DIF 5 gangguan 4 TRIP 3 gangguan 2 b 1 0 tidak TRIP Gambar 13. Karakteristik Relai Diferensial T60 Dititik Gangguan di bus A Untuk gangguan Tiga Fasa Keterangan: a : Karakteristrik Relai Diferensial T60 Dititik Gangguan diluar transformator Untuk gangguan Tiga Fasa b : gangguan diluar jangkauan relai diferensial 4.5. Error Mismatch Meskipun dari perhitungan telah di dapat ratio CT Pada halaman 10 yaitu pada sisi 115 kv (CT 1 ) = 200 : 5, dan pada sisi 13,8 kv (CT 2 ) = 1500 : 5. Nilai CT ratio yang dipilih ini adalah sesuai dengan CT yang ada dipasaran. Karena adanya perbedaan ini maka akan terjadi kesalahan dalam I r 65

26 membaca perbedaan arus dan tegangan di sisi primer dan sekunder transformator tenaga serta pergeseran fasa di trafo arus. kesalahan ini disebut mismatch error. (Anderson Anvenue, 2001: ). Pada relai diferensial untuk melihat mismatch error didapat dari perbandingan CT dengan tegangan pada persamaan (8): CT 2 V = 1 CT1 V2 (8) Untuk menghitung error mismatch sebelumnya terlebih dahulu menghitung nilai CT yang ideal di salah satu sisi transformator tenaga, misal untuk sisi 13,8 kv (CT 2 ) dengan persamaan (9): CT 2 (ideal) = CT 1 x V V 1 2 (9) Dimana: CT 1 : current transformer pada sisi primer CT 2 : current transformer pada sisi sekunder V 1 : tegangan di sisi primer (KV) V 1 : tegangan di sisi sekunder (KV) CT 2 (ideal) = kv x 5 13,8 kv Maka ratio CT 2 di sisi 13,8 kv saat maxsimum load adalah = 1666,667 : 5 Ratio CT yang digunakan di sisi 13,8 kv adalah 1500 : 5, sedangkan idealnya CT untuk sisi 13,8 kv adalah 1666,667 : 5.Maka, error mismatch didapat dari perbandingan antara CT ideal dengan CT yang ada dipasaran. Error mismatch untuk relai diferensial adalah: CT ideal 1666,67 % = CT = 1,111% 66

27 Liem Ek Bien & Dita Helna. Studi Penyetelan Relai Diferensial Pada Transformator PT Chevron Kesalahan relai diferensial dalam mengamankan transformator dari gangguan adalah sebesar 1,111 %.Untuk memperbaiki error mismatch pada relai diferensial ini dapat dilakukan dengan menaikkan atau menurunkan tap pada CT. Error mismatch diharapkan nilainya sekecil mungkin agar proteksi relai diferensial bekerja secara optimal dalam mengamankan transformator tenaga. Dengan syarat kesensitifan relai diferensial dalam pengoperasian Mismatch error tidak boleh lebih dari 5%. Syarat ini ditentukan untuk proteksi agar optimal menjaga sistem tenaga listrik dari gangguan. 5. Kesimpulan 1. Relai diferensial transformator adalah relai utama yang bekerja mengamankan transformator tenaga dari gangguan didalam transformator tenaga dan tidak bekerja saat terjadi gangguan di luar transformator tenaga. 2. Pada karakteristik relai diferensial, setelan rele diferensial untuk gangguan didalam transformator tenaga sebesar 25% lebih kecil dibandingkan untuk gangguan di luar transformator sebesar yang 100% dan untuk nilai pick up di ambil dari ratio error CT. 3. Error mismatch adalah kesalahan dalam membaca perbedaan arus dan tegangan di sisi primer dan sekunder transformator tenaga serta pergeseran fasa di trafo arus. Nilai Error mismatch harus lebih kecil dari 5 % agar proteksi relai diferensial lebih optimal dalam mengamankan transformator tenaga. Daftar Pustaka 1. Anderson Anvenue, Markham, Ontario Transformer Management Relay Instruction Manual GE Power Management. Canada Anderson Anvenue, Markham, Ontario T60 Transformer Management Relay UR Series Instruction Manual GE Power Management. Canada J lewis, Blackburn Protective Relaying Principles And Applications second edition Kadarisman, Pribadi, Diktat Kuliah Sistem Proteksi. 5. Sukmawidjaja, Maula Edisi ke-2. Teori Soal Dan Penyelesaian Analisa Sistem Tenaga Listrik II. Jakarta: Jurusan Teknik Elektro, Universitas Trisakti. 67

28 6. Instructions Transformer Differential Relays With Percentagee And Harmonic Restraint Types STD15C And STD16C. GE Meter and control

Penentuan Setting Rele Arus Lebih Generator dan Rele Diferensial Transformator Unit 4 PLTA Cirata II

Penentuan Setting Rele Arus Lebih Generator dan Rele Diferensial Transformator Unit 4 PLTA Cirata II Jurnal Reka Elkomika 2337-439X Februari 2013 Jurnal Online Institut Teknologi Nasional Teknik Elektro Itenas Vol.1 No.2 Penentuan Setting Rele Arus Lebih Generator dan Rele Diferensial Transformator Unit

Lebih terperinci

Institut Teknologi Padang Jurusan Teknik Elektro BAHAN AJAR SISTEM PROTEKSI TENAGA LISTRIK. TATAP MUKA X&XI. Oleh: Ir. Zulkarnaini, MT.

Institut Teknologi Padang Jurusan Teknik Elektro BAHAN AJAR SISTEM PROTEKSI TENAGA LISTRIK. TATAP MUKA X&XI. Oleh: Ir. Zulkarnaini, MT. Institut Teknologi Padang Jurusan Teknik Elektro BAHAN AJAR SISTEM PROTEKSI TENAGA LISTRIK TATAP MUKA X&XI. Oleh: Ir. Zulkarnaini, MT. 2011 1/25/2011 1 Relay Differential Relay differential merupakan pengaman

Lebih terperinci

STUDI SISTEM PROTEKSI RELE DIFERENSIAL PADA TRANSFORMATOR PT. PLN (PERSERO) KERAMASAN PALEMBANG

STUDI SISTEM PROTEKSI RELE DIFERENSIAL PADA TRANSFORMATOR PT. PLN (PERSERO) KERAMASAN PALEMBANG STUDI SISTEM PROTEKSI RELE DIFERENSIAL PADA TRANSFORMATOR PT. PLN (PERSERO) KERAMASAN PALEMBANG Subianto Program Studi Teknik Elektro Universitas Palembang Email : subidan11@gmail.com Abstract The distribution

Lebih terperinci

BAB IV DATA DAN PEMBAHASAN. panasbumi Unit 4 PT Pertamina Geothermal Energi area Kamojang yang. Berikut dibawah ini data yang telah dikumpulkan :

BAB IV DATA DAN PEMBAHASAN. panasbumi Unit 4 PT Pertamina Geothermal Energi area Kamojang yang. Berikut dibawah ini data yang telah dikumpulkan : BAB IV DATA DAN PEMBAHASAN 4.1 Data yang Diperoleh Dalam penelitian ini menggunakan data di Pembangkit listrik tenaga panasbumi Unit 4 PT Pertamina Geothermal Energi area Kamojang yang telah dikumpulkan

Lebih terperinci

ANALISA TROUBLE DIFFERENTIAL RELAY TERHADAP TRIP CB ( CIRCUIT BREAKER ) 150 KV TRANSFORMATOR 30 MVA PLTGU PANARAN

ANALISA TROUBLE DIFFERENTIAL RELAY TERHADAP TRIP CB ( CIRCUIT BREAKER ) 150 KV TRANSFORMATOR 30 MVA PLTGU PANARAN ANALISA TROUBLE DIFFERENTIAL RELAY TERHADAP TRIP CB ( CIRCUIT BREAKER ) 150 KV TRANSFORMATOR 30 MVA PLTGU PANARAN Muhammad Irsyam Program Studi Teknik Elektro, Fakultas Teknik, Universitas Riau Kepulauan

Lebih terperinci

BAB III PEMBAHASAN RELAY DEFERENSIAL DAN RELEY DEFERENSIAL GRL 150

BAB III PEMBAHASAN RELAY DEFERENSIAL DAN RELEY DEFERENSIAL GRL 150 BAB III PEMBAHASAN RELAY DEFERENSIAL DAN RELEY DEFERENSIAL GRL 150 Secara garis besar bagian dari relay proteksi terdiri dari tiga bagian utama, seperti pada blok diagram berikut, Gambar 3.1 Blok diagram

Lebih terperinci

STUDI SETTING RELE DIFFERENTIAL PADA TRANSFORMATOR TENAGA DI PT PERTAMINA REFINERY UNIT IV CILACAP

STUDI SETTING RELE DIFFERENTIAL PADA TRANSFORMATOR TENAGA DI PT PERTAMINA REFINERY UNIT IV CILACAP STUDI SETTING RELE DIFFERENTIAL PADA TRANSFORMATOR TENAGA DI PT PERTAMINA REFINERY UNIT IV CILACAP Disusun sebagai salah satu syarat menyelesaikan Program Studi Strata I pada Jurusan Teknik Elektro Fakultas

Lebih terperinci

ANALISIS ARUS INRUSH TERHADAP PENGARUH KINERJA RELAI DIFERENSIAL PADA TRANSFORMATOR 150 KV

ANALISIS ARUS INRUSH TERHADAP PENGARUH KINERJA RELAI DIFERENSIAL PADA TRANSFORMATOR 150 KV ANALISIS ARUS INRUSH TERHADAP PENGARUH KINERJA RELAI DIFERENSIAL PADA TRANSFORMATOR 150 KV Oxiandra Ali Rizki, Muhamad Mujahidin, ST., MT, Ibnu Kahfi Bachtiar, ST, M.Sc Jurusan Teknik Elektro, Fakultas

Lebih terperinci

PENGGUNAAN RELAY DIFFERENSIAL. Relay differensial merupakan suatu relay yang prinsip kerjanya berdasarkan

PENGGUNAAN RELAY DIFFERENSIAL. Relay differensial merupakan suatu relay yang prinsip kerjanya berdasarkan PENGGUNAAN RELAY DIFFERENSIAL Relay differensial merupakan suatu relay yang prinsip kerjanya berdasarkan kesimbangan (balance), yang membandingkan arus-arus sekunder transformator arus (CT) terpasang pada

Lebih terperinci

BAB III PENGAMANAN TRANSFORMATOR TENAGA

BAB III PENGAMANAN TRANSFORMATOR TENAGA 41 BAB III PENGAMANAN TRANSFORMATOR TENAGA 3.1 Pengamanan Terhadap Transformator Tenaga Sistem pengaman tenaga listrik merupakan sistem pengaman pada peralatan - peralatan yang terpasang pada sistem tenaga

Lebih terperinci

Analisa Koordinasi Rele Pengaman Transformator Pada Sistem Jaringan Kelistrikan di PLTD Buntok

Analisa Koordinasi Rele Pengaman Transformator Pada Sistem Jaringan Kelistrikan di PLTD Buntok Analisa Koordinasi Rele Pengaman Transformator Pada Sistem Jaringan Kelistrikan di PLTD Buntok Yusuf Ismail Nakhoda, Awan Uji Krismanto, dan Maskur Usmanto Jurusan Teknik Elektro, Institut Teknologi Nasional

Lebih terperinci

BAB I PENDAHULUAN. atau konsumen, peranan transformator daya pada Gardu Induk Pauh Limo

BAB I PENDAHULUAN. atau konsumen, peranan transformator daya pada Gardu Induk Pauh Limo BAB I PENDAHULUAN 1.1 Latar Belakang Dalam menyalurkan daya listrik dari sistem pembangkit menuju ke beban atau konsumen, peranan transformator daya pada Gardu Induk Pauh Limo sangatlah penting. Kenyataannya,

Lebih terperinci

GT 1.1 PLTGU Grati dan Rele Jarak

GT 1.1 PLTGU Grati dan Rele Jarak Evaluasi Setting Rele Overall Differential GT 1.1 PLTGU Grati dan Rele Jarak GITET Grati pada Bus 500 kv Hari Wisatawan 2209106057 JURUSAN TEKNIK ELEKTRO Fakultas Teknologi Industri Institut Teknologi

Lebih terperinci

BAB VI. RELE DIFFERENTIAL

BAB VI. RELE DIFFERENTIAL BAB VI. RELE DIFFERENTIAL 6.1 Pendahuluan. Relay differential merupakan pengaman utama pada generator, transformator dan bus-bar, sangat selektif, cepat bekerja tidak perlu berkoordinasi dengan relay lain

Lebih terperinci

SETTING RELAY DIFFERENSIAL PADA GARDU INDUK KALIWUNGU GUNA MENGHINDARI KEGAGALAN PROTEKSI

SETTING RELAY DIFFERENSIAL PADA GARDU INDUK KALIWUNGU GUNA MENGHINDARI KEGAGALAN PROTEKSI SETTING RELAY DIFFERENSIAL PADA GARDU INDUK KALIWUNGU GUNA MENGHINDARI KEGAGALAN PROTEKSI Yuniarto *), Arkhan Subari, and Dinda Hapsari Kusumastuti PSD III Teknik Elektro Fakultas Teknik, Universitas Diponegoro

Lebih terperinci

BAB II LANDASAN TEORI

BAB II LANDASAN TEORI BAB II LANDASAN TEORI Pada bab ini akan dijelaskan tentang gangguan pada sistem tenaga listrik, sistem proteksi tenaga listrik, dan metoda proteksi pada transformator daya. 2.1 Gangguan dalam Sistem Tenaga

Lebih terperinci

STUDI PERENCANAAN PENGGUNAAN PROTEKSI POWER BUS DI PT. LINDE INDONESIA GRESIK

STUDI PERENCANAAN PENGGUNAAN PROTEKSI POWER BUS DI PT. LINDE INDONESIA GRESIK STUDI PERENCANAAN PENGGUNAAN PROTEKSI POWER BUS DI PT. LINDE INDONESIA GRESIK Nama : Sandi Agusta Jiwantoro NRP : 2210105021 Pembimbing : 1. Dr. Ir. Margo Pujiantara, MT. 2. Dr. Dedet Candra Riawan, ST.

Lebih terperinci

ANALISIS PENYEBAB KEGAGALAN KERJA SISTEM PROTEKSI PADA GARDU AB

ANALISIS PENYEBAB KEGAGALAN KERJA SISTEM PROTEKSI PADA GARDU AB ANALISIS PENYEBAB KEGAGALAN KERJA SISTEM PROTEKSI PADA GARDU AB 252 Oleh Vigor Zius Muarayadi (41413110039) Jurusan Teknik Elektro, Fakultas Teknik, Universitas Mercu Buana Sistem proteksi jaringan tenaga

Lebih terperinci

ANALISIS PENGGUNAAN RELE DIFERENSIAL SEBAGAI PROTEKSI PADA TRANSFORMATOR DAYA 16 MVA DI GARDU INDUK JAJAR

ANALISIS PENGGUNAAN RELE DIFERENSIAL SEBAGAI PROTEKSI PADA TRANSFORMATOR DAYA 16 MVA DI GARDU INDUK JAJAR ANALISIS PENGGUNAAN RELE DIFERENSIAL SEBAGAI PROTEKSI PADA TRANSFORMATOR DAYA 16 MVA DI GARDU INDUK JAJAR PUBLIKASI ILMIAH Disusun sebagai salah satu syarat menyelesaikan Program Studi Strata I pada Jurusan

Lebih terperinci

Sidang Tugas Akhir (Genap ) Teknik Sistem Tenaga Jurusan Teknik Elektro ITS

Sidang Tugas Akhir (Genap ) Teknik Sistem Tenaga Jurusan Teknik Elektro ITS Nama : Luqman Erwansyah NRP : 2210 105 027 Pembimbing : 1. Dr. Ir. Margo Pujiantara, MT. 2. Dr. Eng. Rony Seto Wibowo, ST. MT. Sidang Tugas Akhir (Genap 2011-2012) Teknik Sistem Tenaga Jurusan Teknik Elektro

Lebih terperinci

BAB II TINJAUAN PUSTAKA

BAB II TINJAUAN PUSTAKA 5 BAB II TINJAUAN PUSTAKA 2.1 Dasar-Dasar Sistem Proteksi 1 Sistem proteksi adalah pengaman listrik pada sistem tenaga listrik yang terpasang pada : sistem distribusi tenaga listrik, trafo tenaga, transmisi

Lebih terperinci

BAB II TINJAUAN PUSTAKA

BAB II TINJAUAN PUSTAKA BAB II TINJAUAN PUSTAKA 2.1 Transformator Daya Transformator ini merupakan suatu alat listrik statis yang dipergunakan untuk memindahkan daya dari satu rangakaian ke rangkaian lain dengan mengubah tegangan

Lebih terperinci

KEMENTRIAN PENDIDIKAN DAN KEBUDAYAAN UNIVERSITAS BRAWIJAYA FAKULTAS TEKNIK JURUSAN TEKNIK ELEKTRO

KEMENTRIAN PENDIDIKAN DAN KEBUDAYAAN UNIVERSITAS BRAWIJAYA FAKULTAS TEKNIK JURUSAN TEKNIK ELEKTRO KEMENTRIAN PENDIDIKAN DAN KEBUDAYAAN UNIVERSITAS BRAWIJAYA FAKULTAS TEKNIK JURUSAN TEKNIK ELEKTRO Jalan MT Haryono 167 Telp& Fax. 0341 554166 Malang 65145 KODE PJ-01 PENGESAHAN PUBLIKASI HASIL PENELITIAN

Lebih terperinci

ABSTRAK Kata Kunci :

ABSTRAK Kata Kunci : ABSTRAK Transformator 3 pada GI Pesanggaran mendapat penambahan 4 blok pembangkit dengan daya maksimum sebesar 60 MW daya dari keempat blok pembangkit tersebut digunakan untuk mensuplai beban penyulang

Lebih terperinci

LANDASAN TEORI Sistem Tenaga Listrik Tegangan Menengah. adalah jaringan distribusi primer yang dipasok dari Gardu Induk

LANDASAN TEORI Sistem Tenaga Listrik Tegangan Menengah. adalah jaringan distribusi primer yang dipasok dari Gardu Induk II LANDASAN TEORI 2.1. Sistem Tenaga Listrik Tegangan Menengah Sistem Distribusi Tenaga Listrik adalah kelistrikan tenaga listrik mulai dari Gardu Induk / pusat listrik yang memasok ke beban menggunakan

Lebih terperinci

BAB III PROTEKSI TRANSFORMATOR DAYA

BAB III PROTEKSI TRANSFORMATOR DAYA BAB III PROTEKSI TRANSFORMATOR DAYA 3.1 Sistem Proteksi Pada Transformator Daya 3.1.1 Peralatan Proteksi Jaringan tenaga listrik secara garis besar terdiri dari pusat pembangkit, jaringan transmisi (gardu

Lebih terperinci

BAB III GANGGUAN PADA JARINGAN LISTRIK TEGANGAN MENENGAH

BAB III GANGGUAN PADA JARINGAN LISTRIK TEGANGAN MENENGAH BAB III GANGGUAN PADA JARINGAN LISTRIK TEGANGAN MENENGAH 3.1 KOMPONEN KOMPONEN SIMETRIS Tiga fasor tak seimbang dari sistem fasa tiga dapat diuraikan menjadi tiga sistem fasor yang seimbang. Himpunan seimbang

Lebih terperinci

PENGUJIAN RELAY DIFFERENSIAL GI

PENGUJIAN RELAY DIFFERENSIAL GI EKSERGI Jurnal Teknik Energi Vol 9 No. 2 Mei 2013 ; 74-79 PENGUJIAN RELAY DIFFERENSIAL GI Hery Setijasa Jurusan Teknik Elektro Polines Jln. Prof. Sudarto Tembalang Semarang abstrak Salah satu peralatan

Lebih terperinci

Jurusan Teknik Elektro Fakultas Teknologi Industri Institut Teknologi Sepuluh Nopember Surabaya

Jurusan Teknik Elektro Fakultas Teknologi Industri Institut Teknologi Sepuluh Nopember Surabaya Jurusan Teknik Elektro Fakultas Teknologi Industri Institut Teknologi Sepuluh Nopember Surabaya Tujuan Melakukan analisis terhadap sistem pengaman tenaga listrik di PT.PLN (PERSERO) Melakukan evaluasi

Lebih terperinci

Analisis Setting Relay Proteksi Pengaman Arus Lebih Pada Generator (Studi Kasus di PLTU 2X300 MW Cilacap)

Analisis Setting Relay Proteksi Pengaman Arus Lebih Pada Generator (Studi Kasus di PLTU 2X300 MW Cilacap) Analisis Setting Relay Proteksi Pengaman Arus Lebih Pada Generator (Studi Kasus di PLTU 2X300 MW Cilacap) Fitrizawati 1, Siswanto Nurhadiyono 2, Nur Efendi 3 1,2,3 Program Studi Teknik Elektro Sekolah

Lebih terperinci

BAB II TINJAUAN PUSTAKA DAN DASAR TEORI. pernah dilakukan sebagai rujukan penulis guna mendukung penyusunan

BAB II TINJAUAN PUSTAKA DAN DASAR TEORI. pernah dilakukan sebagai rujukan penulis guna mendukung penyusunan BAB II TINJAUAN PUSTAKA DAN DASAR TEORI 2.1 Tinjauan Pustaka Berikut beberapa penelitian mengenai analisis proteksi serta setting rele diferensial pada Busbar di suatu Switchyard atau Gardu induk yang

Lebih terperinci

RELE. Klasifikasi Rele

RELE. Klasifikasi Rele RELE Berasal dari teknik telegrafi, dimana sebuah coil di-energize oleh arus lemah, dan coil ini menarik armature untuk menutup kontak. Rele merupakan jantung dari proteksi sistem TL, dan telah berkembang

Lebih terperinci

BAB II KAJIAN PUSTAKA

BAB II KAJIAN PUSTAKA BAB II KAJIAN PUSTAKA 2.1 Tinjauan Mutakhir Penelitian mengenai pengaman yang terdapat pada busbar 150 kv telah banyak dilakukan. Beberapa penelitian yang telah dilakukan sebelumnya terkait dengan pengaman

Lebih terperinci

BAB V PENUTUP 5.1 Simpulan Saran DAFTAR PUSTAKA LAMPIRAN LAMPIRAN

BAB V PENUTUP 5.1 Simpulan Saran DAFTAR PUSTAKA LAMPIRAN LAMPIRAN DAFTAR ISI HALAMAN SAMPUL DALAM... i PRASYARAT GELAR... ii LEMBAR PERNYATAAN ORISINALITAS... iii LEMBAR PERSETUJUAN PEMBIMBING... iv UCAPAN TERIMAKASIH... v ABSTRAK... vii ABSTRACT... viii DAFTAR ISI...

Lebih terperinci

BAB III METODOLOGI. 3.2 Tahap Pelaksanaan Penyusunan Laporan Akhir

BAB III METODOLOGI. 3.2 Tahap Pelaksanaan Penyusunan Laporan Akhir 29 BAB III METODOLOGI 3.1 Waktu dan Tempat Untuk menyelesaikan Laporan akhir ini dibutuhkan data penunjang yang diperoleh dari : Tempat Penelitian : 1. PT. PLN (Persero) Gardu Induk (GI) Kraksaan 2. PT.

Lebih terperinci

ANALISIS PROTEKSI RELE DIFERENSIAL PADA TRAFO GARDU INDUK KONSUMEN TEGANGAN TINGGI DI GARDU INDUK SEMEN MERAH PUTIH REMBANG

ANALISIS PROTEKSI RELE DIFERENSIAL PADA TRAFO GARDU INDUK KONSUMEN TEGANGAN TINGGI DI GARDU INDUK SEMEN MERAH PUTIH REMBANG ANALISIS PROTEKSI RELE DIFERENSIAL PADA TRAFO GARDU INDUK KONSUMEN TEGANGAN TINGGI DI GARDU INDUK SEMEN MERAH PUTIH REMBANG PUBLIKASI ILMIAH Disusun sebagai salah satu syarat menyelesaikan Program Studi

Lebih terperinci

BAB III SISTEM PROTEKSI DENGAN RELAI JARAK. terutama untuk masyarakat yang tinggal di kota-kota besar. Kebutuhan tenaga

BAB III SISTEM PROTEKSI DENGAN RELAI JARAK. terutama untuk masyarakat yang tinggal di kota-kota besar. Kebutuhan tenaga BAB III SISTEM PROTEKSI DENGAN RELAI JARAK 3.1. Umum Tenaga listrik merupakan suatu kebutuhan pokok dalam kehidupan manusia, terutama untuk masyarakat yang tinggal di kota-kota besar. Kebutuhan tenaga

Lebih terperinci

BAB IV PEMBAHASAN. Gardu Induk Godean berada di jalan Godean Yogyakarta, ditinjau dari

BAB IV PEMBAHASAN. Gardu Induk Godean berada di jalan Godean Yogyakarta, ditinjau dari BAB IV PEMBAHASAN 4.1 Gardu Induk Godean Gardu Induk Godean berada di jalan Godean Yogyakarta, ditinjau dari peralatannya, Gardu Induk ini merupakan gardu induk pasangan luar, gardu induk godean memiliki

Lebih terperinci

STUDI KOORDINASI RELE PROTEKSI PADA SISTEM KELISTRIKAN PT. BOC GASES GRESIK JAWA TIMUR

STUDI KOORDINASI RELE PROTEKSI PADA SISTEM KELISTRIKAN PT. BOC GASES GRESIK JAWA TIMUR 1 STUDI KOORDINASI RELE PROTEKSI PADA SISTEM KELISTRIKAN PT. BOC GASES GRESIK JAWA TIMUR Albertus Rangga P. 2206100149 Jurusan Teknik Elektro ITS Surabaya Abstrak - Suatu industri membutuhkan sistem kelistrikan

Lebih terperinci

BAB 2 GANGGUAN HUBUNG SINGKAT DAN PROTEKSI SISTEM TENAGA LISTRIK

BAB 2 GANGGUAN HUBUNG SINGKAT DAN PROTEKSI SISTEM TENAGA LISTRIK BAB 2 GANGGUAN HUBUNG SINGKAT DAN PROTEKSI SISTEM TENAGA LISTRIK 2.1 PENGERTIAN GANGGUAN DAN KLASIFIKASI GANGGUAN Gangguan adalah suatu ketidaknormalan (interferes) dalam sistem tenaga listrik yang mengakibatkan

Lebih terperinci

Rifgy Said Bamatraf Dosen Pembimbing Dr. Ir. Margo Pujiantara, MT Dr. Dedet Chandra Riawan, ST., M.Eng.

Rifgy Said Bamatraf Dosen Pembimbing Dr. Ir. Margo Pujiantara, MT Dr. Dedet Chandra Riawan, ST., M.Eng. Rifgy Said Bamatraf 2207100182 Dosen Pembimbing Dr. Ir. Margo Pujiantara, MT Dr. Dedet Chandra Riawan, ST., M.Eng. Latar Belakang Masalah Batasan Masalah Sistem Kelistrikan PLTU dan PLTG Unit Pembangkit

Lebih terperinci

BAB II TINJAUAN PUSTAKA. c. Memperkecil bahaya bagi manusia yang ditimbulkan oleh listrik.

BAB II TINJAUAN PUSTAKA. c. Memperkecil bahaya bagi manusia yang ditimbulkan oleh listrik. 6 BAB II TINJAUAN PUSTAKA 2.1 Sistem Proteksi Sistem proteksi merupakan sistem pengaman yang terpasang pada sistem distribusi tenaga listrik, trafo tenaga transmisi tenaga listrik dan generator listrik.

Lebih terperinci

Studi Koordinasi Proteksi PT. PJB UP Gresik (PLTGU Blok 3)

Studi Koordinasi Proteksi PT. PJB UP Gresik (PLTGU Blok 3) JURNAL TEKNIK POMITS Vol. 1, No. 1, (2014) 1-6 1 Studi Koordinasi Proteksi PT. PJB UP Gresik (PLTGU Blok 3) Ahmad Yusuf Kurniawan, Dr. Ir. Margo Pujiantara, MT. 1), Ir. Arif Musthofa, MT 2). Jurusan Teknik

Lebih terperinci

BAB I PENDAHULUAN. yang menjadi salah satu penentu kehandalan sebuah sistem. Relay merupakan

BAB I PENDAHULUAN. yang menjadi salah satu penentu kehandalan sebuah sistem. Relay merupakan BAB I PENDAHULUAN 1.1 Latar Belakang Sistem proteksi merupakan bagian penting dalam sebuah sistem kelistrikan yang menjadi salah satu penentu kehandalan sebuah sistem. Relay merupakan bagian dari sistem

Lebih terperinci

BAB IV ANALISA DAN PEMBAHASAN

BAB IV ANALISA DAN PEMBAHASAN BAB IV ANALISA DAN PEMBAHASAN 4.1. Gangguan yang Terjadi pada SKTT Gangguan yang terjadi pada saluran kabel tegangan tinggi (SKTT) umumnya bersifat permanen dan diikuti kerusakan sehingga diperlukan perbaikan

Lebih terperinci

BAB II TINJAUAN PUSTAKA

BAB II TINJAUAN PUSTAKA BAB II TINJAUAN PUSTAKA 2.1. Sistem Distribusi 1 Bagian dari sistem tenaga listrik yang paling dekat dengan pelanggan adalah sistem distribusi. Sistem distribusi adalah bagian sistem tenaga listrik yang

Lebih terperinci

2.2.6 Daerah Proteksi (Protective Zone) Bagian-bagian Sistem Pengaman Rele a. Jenis-jenis Rele b.

2.2.6 Daerah Proteksi (Protective Zone) Bagian-bagian Sistem Pengaman Rele a. Jenis-jenis Rele b. DAFTAR ISI JUDUL SAMPUL DALAM... ii LEMBAR PERNYATAAN ORISINALITAS... iii LEMBAR PERSYARATAN GELAR... iv LEMBAR PENGESAHAN... v UCAPAN TERIMA KASIH... vi ABSTRAK... viii ABSTRACT... ix DAFTAR ISI... x

Lebih terperinci

Bambang Prio Hartono, Eko Nurcahyo, Lauhil Mahfudz Hayusman 1

Bambang Prio Hartono, Eko Nurcahyo, Lauhil Mahfudz Hayusman 1 ANALISIS SISTEM PROTEKSI DIRECTIONAL OVER CURRENT RELAYS (DOCR) DENGAN INTERKONEKSI DISTRIBUTED GENERATION (DG) PADA PENYULANG JOLOTUNDO Bambang Prio Hartono, Eko Nurcahyo, Lauhil Mahfudz Hayusman 1 Abstrak:

Lebih terperinci

III PENGUMPULAN DAN PENGOLAHAN DATA

III PENGUMPULAN DAN PENGOLAHAN DATA III PENGUMPULAN DAN PENGOLAHAN DATA 3.1. Umum Berdasarkan standard operasi PT. PLN (Persero), setiap pelanggan energi listrik dengan daya kontrak di atas 197 kva dilayani melalui jaringan tegangan menengah

Lebih terperinci

EVALUASI SETTING RELAY PROTEKSI GENERATOR DAN TRAFO GENERATOR DI PLTGU TAMBAK LOROK BLOK 1

EVALUASI SETTING RELAY PROTEKSI GENERATOR DAN TRAFO GENERATOR DI PLTGU TAMBAK LOROK BLOK 1 EVALUASI SETTING RELAY PROTEKSI GENERATOR DAN TRAFO GENERATOR DI PLTGU TAMBAK LOROK BLOK Maria Oktavia Fitriyani *), Mochammad Facta, and Juningtyastuti Jurusan Teknik Elektro, Universitas Diponegoro Semarang

Lebih terperinci

BAB I PENDAHULUAN A. Latar Belakang

BAB I PENDAHULUAN A. Latar Belakang 1 BAB I PENDAHULUAN A. Latar Belakang Seiring berkembangnya zaman, teknologi pun juga ikut berkembang. Perkembangan teknologi ini mengakibatkan hampir semua peralatan bekerja dengan bersumber dari listrik

Lebih terperinci

BAB IV ANALISA HASIL PENYETINGAN RELAI DIFFERENSIAL

BAB IV ANALISA HASIL PENYETINGAN RELAI DIFFERENSIAL 60 BAB IV ANALISA HASIL PENYETINGAN RELAI DIFFERENSIAL 4.1 Data sistem di PLTGU Muara Karang Tabel 4.1 Data Transformator Step Up 11,5/150 kv PLTGU Muara Karang Pabrikan Daya Transformator Tegangan Primer

Lebih terperinci

BAB 2 KARAKTERISTIK SALURAN TRANSMISI DAN PROTEKSINYA

BAB 2 KARAKTERISTIK SALURAN TRANSMISI DAN PROTEKSINYA 3 BAB 2 KARAKTERISTIK SALURAN TRANSMISI DAN PROTEKSINYA 2. PENGERTIAN SALURAN TRANSMISI Sistem transmisi adalah suatu sistem penyaluran energi listrik dari satu tempat ke tempat lain, seperti dari stasiun

Lebih terperinci

BAB II TINJAUAN PUSTAKA

BAB II TINJAUAN PUSTAKA 7 BAB II TINJAUAN PUSTAKA 2.1 Gardu Induk Gardu Induk (GI) adalah salah satu komponen yang penting dalam menunjang kebutuhan listrik konsumen maupun sebagai pengatur pelayanan tenaga listrik yang didapatkan

Lebih terperinci

Analisa Relai Arus Lebih Dan Relai Gangguan Tanah Pada Penyulang LM5 Di Gardu Induk Lamhotma

Analisa Relai Arus Lebih Dan Relai Gangguan Tanah Pada Penyulang LM5 Di Gardu Induk Lamhotma Yusmartato,Yusniati, Analisa Arus... ISSN : 2502 3624 Analisa Arus Lebih Dan Gangguan Tanah Pada Penyulang LM5 Di Gardu Induk Lamhotma Yusmartato,Yusniati Jurusan Teknik Elektro, Fakultas Teknik, Universitas

Lebih terperinci

JURNAL TEKNIK POMITS Vol. 1, No. 1, (2012) 1-6

JURNAL TEKNIK POMITS Vol. 1, No. 1, (2012) 1-6 Proteksi Ground Fault Untuk Sistem 11 kv dengan Multiple Bus yang Terhubung Beberapa, Bus Ties, dan PLN, dengan Sistem Grounding yang Berbeda-Beda Luqman Erwansyah, Rony Seto Wibowo, dan Margo Pujiantara

Lebih terperinci

ANALISA SISTEM PROTEKSI RELE DIFERENSIALPADA TRANSFORMATOR DAYA 60MVA DI GARDU INDUK WONOGIRI

ANALISA SISTEM PROTEKSI RELE DIFERENSIALPADA TRANSFORMATOR DAYA 60MVA DI GARDU INDUK WONOGIRI ANALISA SISTEM PROTEKSI RELE DIFERENSIALPADA TRANSFORMATOR DAYA 60MVA DI GARDU INDUK WONOGIRI PUBLIKASI ILMIAH Disusun sebagai salah satu syarat menyelesaikan Program Studi Strata I pada Jurusan Teknik

Lebih terperinci

FEEDER PROTECTION. Penyaji : Ir. Yanuar Hakim, MSc.

FEEDER PROTECTION. Penyaji : Ir. Yanuar Hakim, MSc. FEEDER PROTECTION Penyaji : Ir. Yanuar Hakim, MSc. DIAGRAM SATU GARIS PEMBANGKIT TRAFO UNIT TRANSMISI SISTEM GENERATOR BUS HV TRAFO P.S BUS TM GARDU INDUK PERLU DIKOORDINASIKAN RELAI PENGAMAN OC + GF ANTARA

Lebih terperinci

STUDI PERENCANAAN KOORDINASI RELE PROTEKSI PADA SALURAN UDARA TEGANGAN TINGGI GARDU INDUK GAMBIR LAMA - PULOMAS SKRIPSI

STUDI PERENCANAAN KOORDINASI RELE PROTEKSI PADA SALURAN UDARA TEGANGAN TINGGI GARDU INDUK GAMBIR LAMA - PULOMAS SKRIPSI STUDI PERENCANAAN KOORDINASI RELE PROTEKSI PADA SALURAN UDARA TEGANGAN TINGGI GARDU INDUK GAMBIR LAMA - PULOMAS SKRIPSI Oleh ADRIAL MARDENSYAH 04 03 03 004 7 DEPARTEMEN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS

Lebih terperinci

BAB IV ANALISIA DAN PEMBAHASAN. 4.1 Koordinasi Proteksi Pada Gardu Induk Wonosobo. Gardu induk Wonosobo mempunyai pengaman berupa OCR (Over Current

BAB IV ANALISIA DAN PEMBAHASAN. 4.1 Koordinasi Proteksi Pada Gardu Induk Wonosobo. Gardu induk Wonosobo mempunyai pengaman berupa OCR (Over Current BAB IV ANALISIA DAN PEMBAHASAN 4.1 Koordinasi Proteksi Pada Gardu Induk Wonosobo Gardu induk Wonosobo mempunyai pengaman berupa OCR (Over Current Relay) dan Recloser yang dipasang pada gardu induk atau

Lebih terperinci

BAB 3 RELE PROTEKSI PADA SALURAN UDARA TEGANGAN TINGGI

BAB 3 RELE PROTEKSI PADA SALURAN UDARA TEGANGAN TINGGI BAB 3 RELE PROTEKSI PADA SALURAN UDARA TEGANGAN TINGGI 3.1 RELE JARAK Pada proteksi saluran udara tegangan tinggi, rele jarak digunakan sebagai pengaman utama sekaligus sebagai pengaman cadangan untuk

Lebih terperinci

ANALISIS GANGGUAN HUBUNG SINGKAT TRAFO TENAGA 60 MVA SHORT CIRCUIT ANALYSIS OF POWER TRANSFORMER 60 MVA

ANALISIS GANGGUAN HUBUNG SINGKAT TRAFO TENAGA 60 MVA SHORT CIRCUIT ANALYSIS OF POWER TRANSFORMER 60 MVA Techno, ISSN 1410-8607 Volume 16 No. 2, Oktober 2015 Hal. 125 130 ANALISIS GANGGUAN HUBUNG SINGKAT TRAFO TENAGA 60 MVA SHORT CIRCUIT ANALYSIS OF POWER TRANSFORMER 60 MVA Eka Purwito dan Fitrizawati* Program

Lebih terperinci

Studi Koordinasi Proteksi Sistem Kelistrikan di Project Pakistan Deep Water Container Port

Studi Koordinasi Proteksi Sistem Kelistrikan di Project Pakistan Deep Water Container Port PROCEEDING TUGAS AKHIR, (2014) 1-6 1 Studi Koordinasi Proteksi Sistem Kelistrikan di Project Pakistan Deep Water Container Port Adam Anas Makruf, Margo Pujiantara 1), Feby Agung Pamuji 2) Jurusan Teknik

Lebih terperinci

ANALISA SETTING RELAI PENGAMAN AKIBAT REKONFIGURASI PADA PENYULANG BLAHBATUH

ANALISA SETTING RELAI PENGAMAN AKIBAT REKONFIGURASI PADA PENYULANG BLAHBATUH ANALISA SETTING RELAI PENGAMAN AKIBAT REKONFIGURASI PADA PENYULANG BLAHBATUH I K.Windu Iswara 1, G. Dyana Arjana 2, W. Arta Wijaya 3 1,2,3 Jurusan Teknik Elektro, Fakultas Teknik Universitas Udayana, Denpasar

Lebih terperinci

BAB III SISTEM KELISTRIKAN DAN PROTEKSI

BAB III SISTEM KELISTRIKAN DAN PROTEKSI BAB III SISTEM KELISTRIKAN DAN PROTEKSI 3.1 Generator dan Transformator Unit Generator Suatu alat listrik yang merubah energi gerak berupa putaran dari turbin yang dipasang seporos dengan generator, kemudian

Lebih terperinci

Evaluasi Ground Fault Relay Akibat Perubahan Sistem Pentanahan di Kaltim 1 PT. Pupuk Kaltim

Evaluasi Ground Fault Relay Akibat Perubahan Sistem Pentanahan di Kaltim 1 PT. Pupuk Kaltim Evaluasi Ground Fault Relay Akibat Perubahan Sistem Pentanahan di Kaltim 1 PT. Pupuk Kaltim Istiqomah-2206100013 Jurusan Teknik Elektro-FTI, Institut Teknologi Sepuluh Nopember Kampus ITS, Keputih-Sukolilo,

Lebih terperinci

BAB II LANDASAN TEORI ANALISA HUBUNG SINGKAT DAN MOTOR STARTING

BAB II LANDASAN TEORI ANALISA HUBUNG SINGKAT DAN MOTOR STARTING BAB II LANDASAN TEORI ANALISA HUBUNG SINGKAT DAN MOTOR STARTING 2.1 Jenis Gangguan Hubung Singkat Ada beberapa jenis gangguan hubung singkat dalam sistem tenaga listrik antara lain hubung singkat 3 phasa,

Lebih terperinci

Studi Perencanaan Penggunaan Proteksi Power Bus di Sistem Kelistrikan Industri Gas

Studi Perencanaan Penggunaan Proteksi Power Bus di Sistem Kelistrikan Industri Gas JURNAL TEKNIK POMITS Vol. 1, No. 1, (2012) 1-6 1 Studi Perencanaan Penggunaan Proteksi Power Bus di Sistem Kelistrikan Industri Gas Sandi Agusta Jiwantoro, Margo Pujiantara, dan Dedet Candra Riawan Teknik

Lebih terperinci

Makalah Seminar Kerja Praktek APLIKASI SISTEM PENGAMAN ELEKTRIS CADANGAN GAS TURBIN GENERATOR PADA PLTGU TAMBAK LOROK BLOK II

Makalah Seminar Kerja Praktek APLIKASI SISTEM PENGAMAN ELEKTRIS CADANGAN GAS TURBIN GENERATOR PADA PLTGU TAMBAK LOROK BLOK II Makalah Seminar Kerja Praktek APLIKASI SISTEM PENGAMAN ELEKTRIS CADANGAN GAS TURBIN GENERATOR PADA PLTGU TAMBAK LOROK BLOK II 1 Mahasiswa dan 2 M. Hasbi Hazmi B. 1, Karnoto, ST, MT. 2 Dosen Jurusan Teknik

Lebih terperinci

Analisa Koordinasi Over Current Relay Dan Ground Fault Relay Di Sistem Proteksi Feeder Gardu Induk 20 kv Jababeka

Analisa Koordinasi Over Current Relay Dan Ground Fault Relay Di Sistem Proteksi Feeder Gardu Induk 20 kv Jababeka Analisa Koordinasi Over Current Relay Dan Ground Fault Relay Di Sistem Proteksi Feeder Gardu Induk 20 kv Jababeka Erwin Dermawan 1, Dimas Nugroho 2 1) 2) Jurusan Teknik Elektro Fakultas Teknik Universitas

Lebih terperinci

Ground Fault Relay and Restricted Earth Faulth Relay

Ground Fault Relay and Restricted Earth Faulth Relay Ground Fault Relay and Restricted Earth Faulth Relay Seperti telah disebutkan sebelumnya, maka tentang relay akan dilanjutkan dengan beberapa tipe relay. Dan kali ini yang ingin dibahas adalah dua tipe

Lebih terperinci

Analisis Koordinasi Rele Arus Lebih Pda Incoming dan Penyulang 20 kv Gardu Induk Sengkaling Menggunakan Pola Non Kaskade

Analisis Koordinasi Rele Arus Lebih Pda Incoming dan Penyulang 20 kv Gardu Induk Sengkaling Menggunakan Pola Non Kaskade Analisis Koordinasi Rele Arus Lebih Pda Incoming dan Penyulang 20 kv Gardu Induk Sengkaling Menggunakan Pola Non Kaskade Nandha Pamadya Putra¹, Hery Purnomo, Ir., MT.², Teguh Utomo, Ir., MT.³ ¹Mahasiswa

Lebih terperinci

STUDI PENGARUH UPRATING SALURAN TRANSMISI TEGANGAN TINGGI 150 kv TERHADAP SETTING RELE JARAK ANTARA GI KAPAL GI PADANG SAMBIAN GI PESANGGARAN

STUDI PENGARUH UPRATING SALURAN TRANSMISI TEGANGAN TINGGI 150 kv TERHADAP SETTING RELE JARAK ANTARA GI KAPAL GI PADANG SAMBIAN GI PESANGGARAN STUDI PENGARUH UPRATING SALURAN TRANSMISI TEGANGAN TINGGI 150 kv TERHADAP SETTING RELE JARAK ANTARA GI KAPAL GI PADANG SAMBIAN GI PESANGGARAN Supriana S.K. 1, Dyana Arjana, I.G. 2, Amrita, A.A.N. 3 1,2,3

Lebih terperinci

BAB IV. PERHITUNGAN GANGGUAN SIMPATETIK PADA PENYULANG 20 kv GARDU INDUK DUKUH ATAS

BAB IV. PERHITUNGAN GANGGUAN SIMPATETIK PADA PENYULANG 20 kv GARDU INDUK DUKUH ATAS BAB IV PERHITUNGAN GANGGUAN SIMPATETIK PADA PENYULANG 20 kv GARDU INDUK DUKUH ATAS 4.1. GARDU INDUK DUKUH ATAS GI Dukuh Atas merupakan gardu induk yang memiliki 2 buah trafo tenaga dengan daya masing-masing

Lebih terperinci

BAB 4 ANALISA KONSEP ADAPTIF RELE JARAK PADA JARINGAN SALURAN TRANSMISI GANDA MUARA TAWAR - CIBATU

BAB 4 ANALISA KONSEP ADAPTIF RELE JARAK PADA JARINGAN SALURAN TRANSMISI GANDA MUARA TAWAR - CIBATU 36 BAB 4 ANALISA KONSEP ADAPTIF RELE JARAK PADA JARINGAN SALURAN TRANSMISI GANDA MUARA TAWAR - CIBATU 4.1 DIAGRAM GARIS TUNGGAL GITET 5 KV MUARA TAWAR Unit Pembangkitan Muara Tawar adalah sebuah Pembangkit

Lebih terperinci

dalam sistem sendirinya dan gangguan dari luar. Penyebab gangguan dari dalam

dalam sistem sendirinya dan gangguan dari luar. Penyebab gangguan dari dalam 6 Penyebab gangguan pada sistem distribusi dapat berasal dari gangguan dalam sistem sendirinya dan gangguan dari luar. Penyebab gangguan dari dalam antara lain: 1 Tegangan lebih dan arus tak normal 2.

Lebih terperinci

Gambar 2.1 Skema Sistem Tenaga Listrik (3)

Gambar 2.1 Skema Sistem Tenaga Listrik (3) BAB II TINJAUAN PUSTAKA 2.1 Teori Umum Secara umum suatu sistem tenaga listrik terdiri dari tiga bagian utama, yaitu, pusat pembangkitan listrik, saluran transmisi dan sistem distribusi. Perlu dikemukakan

Lebih terperinci

ANALISA PROTEKSI TRANSFORMATOR 150 kv DENGAN MENGGUNAKAN RELE DIFERENSIAL DI PLTG PAYA PASIR

ANALISA PROTEKSI TRANSFORMATOR 150 kv DENGAN MENGGUNAKAN RELE DIFERENSIAL DI PLTG PAYA PASIR ANALISA PROTEKSI TRANSFORMATOR 150 kv DENGAN MENGGUNAKAN RELE DIFERENSIAL DI PLTG PAYA PASIR LAPORAN TUGAS AKHIR Ditulis Untuk Memenuhi Syarat Menyelesaikan Pendidikan Diploma III PROGRAM STUDI TEKNIK

Lebih terperinci

BAB IV SISTEM PROTEKSI GENERATOR DENGAN RELAY ARUS LEBIH (OCR)

BAB IV SISTEM PROTEKSI GENERATOR DENGAN RELAY ARUS LEBIH (OCR) 27 BAB IV SISTEM PROTEKSI GENERATOR DENGAN RELAY ARUS LEBIH (OCR) 4.1 Umum Sistem proteksi merupakan salah satu komponen penting dalam system tenaga listrik secara keseluruhan yang tujuannya untuk menjaga

Lebih terperinci

BAB III METODE PENELITIAN. Laptop/PC yang di dalamnya terinstal software aplikasi ETAP 12.6 (Electric

BAB III METODE PENELITIAN. Laptop/PC yang di dalamnya terinstal software aplikasi ETAP 12.6 (Electric BAB III METODE PENELITIAN 3.1 Alat dan Bahan 3.1.1 Alat Penelitian Alat yang digunakan untuk melakukan penelitian ini adalah berupa Laptop/PC yang di dalamnya terinstal software aplikasi ETAP 12.6 (Electric

Lebih terperinci

Analisa Perhitungan dan Pengaturan Relai Arus Lebih dan Relai Gangguan Tanah pada Kubikel Cakra 20 KV Di PT XYZ

Analisa Perhitungan dan Pengaturan Relai Arus Lebih dan Relai Gangguan Tanah pada Kubikel Cakra 20 KV Di PT XYZ ISSN: 1410-233 nalisa Perhitungan dan Pengaturan Relai rus Lebih dan Relai Gangguan Tanah pada Kubikel Cakra 20 KV Di PT XYZ Muhalan, Budi Yanto Husodo Program Studi Teknik Elektro, Fakultas Teknik Universitas

Lebih terperinci

Analisis Rele Pengaman Peralatan dan Line Transmisi Switchyard GITET Baru 500kV PT PLN (PERSERO) di Kediri

Analisis Rele Pengaman Peralatan dan Line Transmisi Switchyard GITET Baru 500kV PT PLN (PERSERO) di Kediri JURNAL TEKNIK POMITS Vol., No., (03) -6 Analisis Rele Pengaman Peralatan dan Line Transmisi Switchyard GITET Baru 500 PT PLN (PERSERO) di Kediri Muhammad Rafi, Margo Pujiantara ), dan R. Wahyudi ). Jurusan

Lebih terperinci

BAB I PENDAHULUAN. pendukung di dalamnya masih tetap diperlukan suplai listrik sendiri-sendiri.

BAB I PENDAHULUAN. pendukung di dalamnya masih tetap diperlukan suplai listrik sendiri-sendiri. BAB I PENDAHULUAN 1.1 Latar Belakang PLTU (Pusat Listrik Tenaga Uap) Suralaya mampu membangkitkan listrik berkapasitas 3400 MW dengan menggunakan tenaga uap. Tetapi perlu diketahui bahwa di dalam proses

Lebih terperinci

ABSTRAK. Kata kunci : Arus Transien, Ketahanan Transformator, Jenis Beban. ABSTRACT. Keywords : Transient Current, Transformer withstand, load type.

ABSTRAK. Kata kunci : Arus Transien, Ketahanan Transformator, Jenis Beban. ABSTRACT. Keywords : Transient Current, Transformer withstand, load type. Jurnal Reka Elkomika 2337-439X Januari 2013 Jurnal Online Institut Teknologi Nasional Teknik Elektro Itenas Vol.1 No.1 Analisis Arus Transien Transformator Setelah Penyambungan Beban Gedung Serbaguna PT

Lebih terperinci

KAJIAN PROTEKSI MOTOR 200 KW,6000 V, 50 HZ DENGAN SEPAM SERI M41

KAJIAN PROTEKSI MOTOR 200 KW,6000 V, 50 HZ DENGAN SEPAM SERI M41 Jurnal ELTEK, Vol 12 Nomor 01, April 2014 ISSN 1693-4024 KAJIAN PROTEKSI MOTOR 200 KW,6000 V, 50 HZ DENGAN SEPAM 1000+ SERI M41 Heri Sungkowo 1 Abstrak SEPAM (System Electronic Protection Automation Measurement)1000+

Lebih terperinci

BAB II TRANSFORMATOR DAYA DAN PENGUBAH SADAPAN BERBEBAN. Tenaga listrik dibangkitkan dipusat pusat listrik (power station) seperti

BAB II TRANSFORMATOR DAYA DAN PENGUBAH SADAPAN BERBEBAN. Tenaga listrik dibangkitkan dipusat pusat listrik (power station) seperti 6 BAB II TRANSFORMATOR DAYA DAN PENGUBAH SADAPAN BERBEBAN 2.1 Sistem Tenaga Listrik Tenaga listrik dibangkitkan dipusat pusat listrik (power station) seperti PLTA, PLTU, PLTD, PLTP dan PLTGU kemudian disalurkan

Lebih terperinci

TUGAS AKHIR. ANALISA PENGGUNAAN DAN PENYETINGAN RELAI DIFFERENSIAL PADA TRAFO STEP UP 11,5/150 kv di PLTGU BLOK I U.P MUARA KARANG

TUGAS AKHIR. ANALISA PENGGUNAAN DAN PENYETINGAN RELAI DIFFERENSIAL PADA TRAFO STEP UP 11,5/150 kv di PLTGU BLOK I U.P MUARA KARANG TUGAS AKHIR ANALISA PENGGUNAAN DAN PENYETINGAN RELAI DIFFERENSIAL PADA TRAFO STEP UP 11,5/150 kv di PLTGU BLOK I U.P MUARA KARANG Diajukan Guna Melengkapi Sebagian Syarat Dalam mencapai gelar Sarjana Strata

Lebih terperinci

BAB II TINJAUAN PUSTAKA. mendukung penulisan tugas akhir ini, antara lain : Kawat Menggunakan Zero Sequence Blocking Transformer.

BAB II TINJAUAN PUSTAKA. mendukung penulisan tugas akhir ini, antara lain : Kawat Menggunakan Zero Sequence Blocking Transformer. BAB II TINJAUAN PUSTAKA 2.1. Kajian Pustaka Berikut ini adalah beberapa rujukan penelitian yang pernah dilakukan untuk mendukung penulisan tugas akhir ini, antara lain : 2.1.1. T. Fakhrul Hadi, Zulkarnaen

Lebih terperinci

TEKNIK PROTEKSI DIFFERENSIAL DIJITAL PADA TRANSFORMATOR DAYA TIGA FASA DENGAN MENGGUNAKAN TRANSFORMASI HILBERT LAPORAN TUGAS AKHIR

TEKNIK PROTEKSI DIFFERENSIAL DIJITAL PADA TRANSFORMATOR DAYA TIGA FASA DENGAN MENGGUNAKAN TRANSFORMASI HILBERT LAPORAN TUGAS AKHIR TEKNIK PROTEKSI DIFFERENSIAL DIJITAL PADA TRANSFORMATOR DAYA TIGA FASA DENGAN MENGGUNAKAN TRANSFORMASI HILBERT LAPORAN TUGAS AKHIR Oleh: MUHAMMAD FAUZY ABDULLAH NIM : 132 03 087 / Teknik Tenaga Elektrik

Lebih terperinci

Studi Koordinasi Rele Pengaman Sistem Tenaga Listrik di PT. Plaza Indonesia Realty Tbk.

Studi Koordinasi Rele Pengaman Sistem Tenaga Listrik di PT. Plaza Indonesia Realty Tbk. JURNAL TEKNIK POMITS Vol. 1, No. 1, (2013) 1-6 1 Studi Koordinasi Rele Pengaman Sistem Tenaga Listrik di PT. Plaza Indonesia Realty Tbk. Galang Agung Asdany, Margo Pujiantara, dan Sjamsjul Anam. Teknik

Lebih terperinci

PENGESAHAN PUBLIKASI HASIL PENELITIAN SKRIPSI JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA

PENGESAHAN PUBLIKASI HASIL PENELITIAN SKRIPSI JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA KEMENTRIAN PENDIDIKAN DAN KEBUDAYAAN UNIVERSITAS BRAWIJAYA FAKULTAS TEKNIK JURUSAN TEKNIK ELEKTRO Jalan MT Haryono 167 Telp & Fax. 0341 554166 Malang 65145 KODE PJ-01 PENGESAHAN PUBLIKASI HASIL PENELITIAN

Lebih terperinci

BAB I PENDAHULUAN 1.1 Latar Belakang Masalah

BAB I PENDAHULUAN 1.1 Latar Belakang Masalah BAB I PENDAHULUAN 1.1 Latar Belakang Masalah Sistem proteksi sangat dibutuhkan untuk meningkatkan TMP (Tingkat Mutu Pelayanan) sehingga dapat mencegah/membatasi kerusakan peralatan akibat gangguan, dan

Lebih terperinci

BAB III PERHITUNGAN ARUS GANGGUAN HUBUNG SINGKAT

BAB III PERHITUNGAN ARUS GANGGUAN HUBUNG SINGKAT BAB III PERHITUNGAN ARUS GANGGUAN HUBUNG SINGKAT 3.1. JENIS GANGGUAN HUBUNG SINGKAT Gangguan hubung singkat yang mungkin terjadi di dalam Jaringan (Sistem Kelistrikan) ada 3, yaitu: a. Gangguan Hubung

Lebih terperinci

EVALUASI KEGAGALAN SETTING RELE DIFERENSIAL PADA BUS 18 KV DI SISTEM KELISTRIKAN PLTU UP PAITON UNIT 1

EVALUASI KEGAGALAN SETTING RELE DIFERENSIAL PADA BUS 18 KV DI SISTEM KELISTRIKAN PLTU UP PAITON UNIT 1 TUGAS AKHIR TE 141599 EVALUASI KEGAGALAN SETTING RELE DIFERENSIAL PADA BUS 18 KV DI SISTEM KELISTRIKAN PLTU UP PAITON UNIT 1 Rizkaurum Nur Fadliyah NRP 2213 100 042 Dosen Pembimbing Dr. Ir. Margo Pujiantara,

Lebih terperinci

BAB II TINJAUAN PUSTAKA

BAB II TINJAUAN PUSTAKA BAB II TINJAUAN PUSTAKA 2.1 Dasar Dasar Sistem Proteksi Suatu sistem t`enaga listrik dibagi ke dalam seksi-seksi yang dibatasi oleh PMT. Tiap seksi memiliki relai pengaman dan memiliki daerah pengamanan

Lebih terperinci

BAB III METODE PENELITIAN. Universitas Lampung dan PT. PLN (Persero) Cabang Tanjung Karang pada. bulan Maret 2013 sampai dengan selesai.

BAB III METODE PENELITIAN. Universitas Lampung dan PT. PLN (Persero) Cabang Tanjung Karang pada. bulan Maret 2013 sampai dengan selesai. 29 BAB III METODE PENELITIAN 3.1 Waktu dan Tempat Penelitian Penelitian tugas akhir ini bertempat di Laboratorium Terpadu Teknik Elektro Universitas Lampung dan PT. PLN (Persero) Cabang Tanjung Karang

Lebih terperinci

Perencanaan Koordinasi Rele Pengaman Pada Sistem Kelistrikan Di PT. Wilmar Gresik Akibat Penambahan Daya

Perencanaan Koordinasi Rele Pengaman Pada Sistem Kelistrikan Di PT. Wilmar Gresik Akibat Penambahan Daya Perencanaan Koordinasi Rele Pengaman Pada Sistem Kelistrikan Di PT. Wilmar Gresik Akibat Penambahan Daya Oleh : Duta Satria Yusmiharga 2208 100 162 Dosen Pembimbing : 1. Prof.Ir. Ontoseno Penangsang, M.Sc.,Ph.D

Lebih terperinci

D. Relay Arus Lebih Berarah E. Koordinasi Proteksi Distribusi Tenaga Listrik BAB V PENUTUP A. KESIMPULAN B. SARAN...

D. Relay Arus Lebih Berarah E. Koordinasi Proteksi Distribusi Tenaga Listrik BAB V PENUTUP A. KESIMPULAN B. SARAN... DAFTAR ISI HALAMAN JUDUL... i HALAMAN PENGESAHAN... ii HALAMAN PERNYATAAN... v MOTTO... vi HALAMAN PERSEMBAHAN... vii KATA PENGANTAR... viii DAFTAR ISI... x DAFTAR GAMBAR... xii DAFTAR TABEL... xiv INTISARI...

Lebih terperinci

BAB III PROTEKSI GANGGUAN TANAH PADA STATOR GENERATOR. Arus gangguan tanah adalah arus yang mengalir melalui pembumian. Sedangkan

BAB III PROTEKSI GANGGUAN TANAH PADA STATOR GENERATOR. Arus gangguan tanah adalah arus yang mengalir melalui pembumian. Sedangkan BAB III PROTEKSI GANGGUAN TANAH PADA STATOR GENERATOR III.1 Umum Arus gangguan tanah adalah arus yang mengalir melalui pembumian. Sedangkan arus yang tidak melalui pembumian disebut arus gangguan fasa.

Lebih terperinci

Analisa Stabilitas Transien dan Koordinasi Proteksi pada PT. Linde Indonesia Gresik Akibat Penambahan Beban Kompresor 4 x 300 kw

Analisa Stabilitas Transien dan Koordinasi Proteksi pada PT. Linde Indonesia Gresik Akibat Penambahan Beban Kompresor 4 x 300 kw Analisa Stabilitas Transien dan Koordinasi Proteksi pada PT. Linde Indonesia Gresik Akibat Penambahan Beban Kompresor 4 x 300 kw Nama : Frandy Istiadi NRP : 2209 106 089 Pembimbing : 1. Dr. Ir. Margo Pujiantara,

Lebih terperinci